LKDS LNGS.465213.270-10 Скачать руководство пользователя страница 38

LNGS.465213.270-10 OM 

 

Table 2 Lift unit parameters  

No.

 

LU State

 

Algorithm 

resolution bit 

address

 

Trigger states bit 

address

 

Lift power off enable 

bit address

(see Note 2)

 

Address of value of 

LU time intervals

 

Number of ‘ERR’ LED 

flashes on power

 

1

 

Maintenance mode 

19

 

99

 

147

 

200

 

21

 

2

 

Firmware restart

 

20

 

100

 

148

 

201

 

22

 

3

 

Multiple doors reversing

 

21

 

101

 

149

 

202

 

23

 

4

 

Machine room penetration 

22

 

102

 

150

 

203

 

24

 

5

 

Cabin door opening

 

23

 

103

 

151

 

204

 

25

 

6

 

Lift cabin movement detected

 

24

 

104

 

152

 

205

 

26

 

7

 

Cabin door starts opening

 

25

 

105

 

153

 

206

 

27

 

8

 

Landing door opening

 

26

 

106

 

154

 

207

 

28

 

9

 

Lift is not powered

 

27

 

107

 

155

 

208

 

29

 

10

 

‘STOP’ button clamped

 

28

 

108

 

156

 

209

 

30

 

11

 

Cabin door opened (see Note 

4)

 

29

 

109

 

157

 

210

 

31

 

12

 

Safety chain open (

see Note 5)

 

30

 

110

 

158

 

211

 

32

 

13

 

Door is not closed

 

31

 

111

 

159

 

212

 

1

 

14

 

Safety chain short circuit

 

32

 

112

 

160

 

213

 

2

 

15

 

Dispatcher call

 

33

 

113

 

161

 

214

 

3

 

16

 

Unauthorized cabin movement

 

34

 

114

 

162

 

215

 

4

 

17

 

Main drive fault

 

35

 

115

 

163

 

216

 

5

 

18

 

Door drive fault

 

36

 

116

 

164

 

217

 

6

 

19

 

shaft penetration

 

37

 

117

 

165

 

218

 

7

 

20

 

Safety Device fault

 

38

 

118

 

166

 

219

 

8

 

21

 

Out of service (see Note 1)

 

39

 

119

 

167

 

220

 

9

 

22

 

Machine room open

 

40

 

120

 

168

 

221

 

10

 

23

 

Voltage at safety chain 

begin checkpoint 

41

 

121

 

169

 

222

 

11

 

24

 

Movement with safety chain 

open

 

42

 

122

 

170

 

223

 

12

 

25

 

Cabin between floors

 

43

 

123

 

171

 

224

 

13

 

26

 

Cabin door sensor malfunction

 

44

 

124

 

172

 

225

 

14

 

27

 

Lack of serial port 

communication

 

45

 

125

 

173

 

226

 

15

 

28

 

Main drive is on

 

46

 

126

 

174

 

227

 

16

 

29

 

User bit (see Note 1)

 

47

 

127

 

175

 

228

 

17

 

30

 

RESERVED

 

48

 

128

 

176

 

229

 

18

 

Содержание LNGS.465213.270-10

Страница 1: ...LNGS 465213 270 10 OM Lift Complex DS OOO Lift Monitoring Diagnostics System LIFT UNIT ver 7 2 OPERATION MANUAL LNGS 465213 270 10 OM rev 23 Novosibirsk 2021...

Страница 2: ...IX A 36 Table 1 The LU 7 2 Status formation algorithm 36 Table 2 Lift unit parameters 38 Table 3 Service codes 40 Table 4 interval code correspondence to the real time 42 Table 5 Mapping of USER1 USER...

Страница 3: ...nical equipment and qualified personnel The present manual covers all options of lift unit ver 7 2 During operation of the lift unit of LMDS it is required to follow the recommendations of the present...

Страница 4: ...LU 7 2 KLEEMANN LNGS 465213 270 27 Lift unit ver 7 2 DOPPLER LU 7 2 DOPPLER LNGS 465213 270 28 Lift unit ver 7 2 BLT LU 7 2 BLT LNGS 465213 270 29 Lift unit ver 7 2 EXPRESS LU 7 2 EXPRESS LNGS 465213...

Страница 5: ...YO LU 7 2 KOYO LNGS 465213 270 74 Lift unit ver 7 2 BL6 LU 7 2 BL6 LNGS 465213 270 75 Lift unit ver 7 2 WEBER LU 7 2 WEBER LNGS 465213 270 76 Lift unit ver 7 2 GTE LU 7 2 GTE LNGS 465213 270 77 Lift u...

Страница 6: ...Lift unit ver 7 2 KONE KCE LU 7 2 KONE KCE LNGS 465213 270 122 Lift unit ver 7 2 IFE LU 7 2 IFE LNGS 465213 270 123 Lift unit ver 7 2 EAGLE LU 7 2 EAGLE LNGS 465213 270 124 LU 7 2 is used with seriall...

Страница 7: ...with NETIS control board DOPPLER ACT with lifts equipped with ACT ACH AYBEY control boards INV with platforms for persons with disabilities E9 with UNGERT lifts equipped with E9 controller ECLIPSE wi...

Страница 8: ...d with ARCA 3 control board HD ONE with lifts equipped with HD ONE control board manufactured by HEDEFSAN INVT with lifts equipped with 100 160 and 300 control boards GPS with MITSUBISHI lifts equippe...

Страница 9: ...thout serial interface as well as for lifts having relay logic controller as additional adaptor the Relay Station Adapter should be usrd LNGS 465213 161 01 Changes to connecting for option LNGS 465213...

Страница 10: ...opened 1 Multiple door reversing Door drive fault Dispatcher call Unauthorized cabin movement Main drive fault Shaft penetration 3 Out of service Machine room penetration Machine room open Maintenance...

Страница 11: ...M Page 11 There are few sockets can be found on the top cover of the LU 7 2 USB to connect the LU to PC Laptop for making settings ATTENTION When LU is connected to a PC via MiniUSB cable CAN bus oper...

Страница 12: ...devices CAR backlit button to initiate a call and to trigger the direction of a call between a cabin and cabin roof PIT backlit button to establish the communication with pit lower landing platform RS...

Страница 13: ...ercom with MR is turned on call direction from operator to lift ERR flash series red Error code that resulted in lift power off flashing Red Service key is inserted or service tool is connected lit Re...

Страница 14: ...ery power On the LU 7 2 housing base the following sockets are located DC IN J2 external power supply of 9 24V DC XP2 Serial bus connector U2 Ethernet LAN connector XP3 Contactor control module socket...

Страница 15: ...dicates signal door opening for automatic door the safety chain state prior to door 2 LED depending on lift door type the LED indicates signal door closing for automatic door the safety chain state af...

Страница 16: ...ation is established CAN LED indicates CAN bus communication established Fig 3 Intercom unit general view Intercom unit 7 2 indicators and their modes are shown in Table 5 Table 5 Name Status Colour D...

Страница 17: ...green LED pictogram 3 YLED Output to control yellow pictogram 4 BAT Battery wiring 5 GND Common Ground 6 CALL Call 7 MIC Microphone input 8 SPC Loudpseaker output XP3 1 CAN P Power supply 9 24V outpu...

Страница 18: ...has registered Flashing Green Voice communication is ON Flashing Green red No data transfer between the LU and CAN bus Flashing Yellow CAN bus address conflict Connecting more than 3 landing intercoms...

Страница 19: ...can be supported by using CAN bus internal wired interface or Wi Fi see Fig 6 Fig 6 An example of internal network A Lift unit CAN bus The physical layer of the bus is a four wire line Two bus conduc...

Страница 20: ...t for creating an internal network The internal network is designed to connect intercom units 7 2 via a Wi Fi network The identifier SSID of the internal Wi Fi network is set by the manufacturer and d...

Страница 21: ...ion The performance of the LU is provided by the microcontroller and the LU firmware The LU is continuously communicating with a lift controller Depending on the status of the controller the LU s firm...

Страница 22: ...firmware versions is located on site www lkds ru After firmware update it is necessary to perform a function test in accordance with section 3 of the manual The manufacturer recommends update the LU f...

Страница 23: ...in a cabin control For the LU of R option an algorithm for determining the presence of a passenger in a lift cabin is implemented For LUs communicating with a lift controller via a serial bus the stat...

Страница 24: ...94 of EEPROM Thus the USER4 input output is assigned an input for receiving data from the CSMA pin of the sensor while the output OUT1 provides power to the sensor In this case any previously assigned...

Страница 25: ...or the LU it is possible to enable the hardware filtering of Dispatcher s calls To enable hardware filtering on the USER1 4 input it is necessary to set the value 200 at the address 6 9 respectively T...

Страница 26: ...nd wait for voice confirmation of Call has been registered Wait for an answer Green LED lit means the request has been registered Pressing RST button will cancel the request for communication from the...

Страница 27: ...ERR LED The interval between bursts is four seconds The correspondence between the error number and the number of indicator flashes is given in Appendix A When the power supply of the lift is cut off...

Страница 28: ...it it is necessary to install jumper between terminals 1 and 3 of XP4 XS4 jack as shown on Fig 11 To connect the battery of 14500 type and with capacity of 750 mA h to the intercom unit circuit it is...

Страница 29: ...rm the following press and hold the Call button on the intercom unit close pins 6 and 5 of XP1 terminal of the intercom unit to set the normally closed type of the Call button of the lift cabin close...

Страница 30: ...way communication between dispatcher and the MR Initiate a voice call with the MR from PC Make sure communication is available 5 Checking of intercom voice communication repair communication and voice...

Страница 31: ...ed control device installed 2 Powering OFF a lift off is to be performed only when the LU protection against the shaft penetration is used When the lift has its own protection system powering lift off...

Страница 32: ...equipment installed in the MR is carried out by electricians of dispatching equipment and teleautomatics Safety precautions When carrying out work the requirements of both safety and industrial instru...

Страница 33: ...sportation storage installation and operation as specified in operating and installation manuals instructions on usage commissioning fine tuning and run in Repair of the LU is carried out by the manuf...

Страница 34: ...LU originally packed must be stored in enclosed spaces with natural ventilation without artificial climate regulators where the humidity and temperature fluctuation is less than in open air located in...

Страница 35: ...must ensure their stable positioning eliminating any possibility of their displacement and rough knocking onto each other and transportation vehicles walls Allowed stacking not more than 5 crates up...

Страница 36: ...mon Ground terminals 16 Unauthorized cabin movement Impulses from OGS while impulses UP DOWN are absent 17 Main drive fault Cabin upward downward motion while no impulses from OGS 18 Door drive fault...

Страница 37: ...ER1 and Common Ground contacts 34 USER2 state Closing USER2 and Common Ground contacts 35 USER3 state Closing USER3 and Common Ground contacts 36 USER4 state Closing USER4 and Common Ground contacts 3...

Страница 38: ...door opened see Note 4 29 109 157 210 31 12 Safety chain open see Note 5 30 110 158 211 32 13 Door is not closed 31 111 159 212 1 14 Safety chain short circuit 32 112 160 213 2 15 Dispatcher call 33 1...

Страница 39: ...182 243 37 No mains power 55 135 183 244 38 Safety circuit AC voltage 56 136 184 245 39 Fire hazard 57 137 185 246 40 Backup battery fault 58 138 186 247 Notes The algorithms for processing the Out of...

Страница 40: ...ding 1 48 state 51 98 enables mapping of the USER input onto the corresponding control point 151 198 enables inverse mapping of the USER input onto the corresponding control point 210 Dispatcher contr...

Страница 41: ...Lift unit ver 7 2 Operational manual Appendix D 18 EEPROM table usage enabled 0 standatd table 85 EEPROM table 83 Turning on lift on request from the line enabled 0 prohibited 1 allowed 84 Inverse bit...

Страница 42: ...ick Time in seconds One second tick Time in seconds 10 second tick Time in seconds 0 0 0 0 0 1 3 0 3 3 30 2 4 0 4 4 40 3 5 0 5 5 50 4 6 0 6 6 60 5 10 1 10 100 6 15 1 5 15 150 7 20 2 20 200 8 30 3 30 3...

Страница 43: ...58 Door closing relay 158 RZD 59 Movement relay 159 RD 60 Out of service 160 ABL 61 Machine room door sensor 161 MPR 62 Cabin or machine room CALL button 162 CALL 63 Overspeed governor sensor impulses...

Страница 44: ...erved 181 82 Door zone sensor 182 DTO 83 Landing door leaf open 183 UB1 84 Both landing door leafs open 184 UB2 Notes 1 Should several inputs are assigned to the same checkpoint so the resulting value...

Страница 45: ...2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Terminal block LNGS 465213 270 050 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Wiring Harness LNGS 465213 270 060 2 2 2 2 2 2 2 2 2 2 1 2 2 2 2 Screw 3x20 DIN84 2 2 2 2 2 2 2 2 2 2...

Страница 46: ...S 465213 270 050 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Wiring Harness LNGS 465213 270 060 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Screw 3x20 DIN84 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Holder LNGS 465213 270 002 01 1 1 1 1 1 1...

Страница 47: ...NGS 465213 060 610 10 1 Cable ECLIPSE LNGS 465213 060 690 01 1 Power adaptor 220 12 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Terminal block LNGS 465213 270 050 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Wiring Harness LNGS 4...

Страница 48: ...S 465213 160 270 01 1 Power adaptor 220 12 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Terminal block LNGS 465213 270 050 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Wiring Harness LNGS 465213 270 060 2 2 2 2 2 2 2 2 2 2 2 2 2 2...

Страница 49: ...wer adaptor 220 12 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Terminal block LNGS 465213 270 050 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Wiring Harness LNGS 465213 270 060 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Screw 3x20 DIN8...

Страница 50: ...g harness LNGS 465213 270 090 1 Power adaptor 220 12 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Terminal block LNGS 465213 270 050 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Wiring Harness LNGS 465213 270 060 2 2 2 2 2 2 2 2...

Страница 51: ...20 DIN84 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 Door sensor IO 102 2 31 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Holder LNGS 465213 270 002 01 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Buckle CV 300 2 2 2 2 2 2 2 2 2 2 2...

Страница 52: ...1 1 Wiring Harness LNGS 465213 270 060 2 2 2 2 2 Screw 3x20 DIN84 2 2 2 2 2 Door sensor IO 102 2 31 1 1 1 1 1 Holder LNGS 465213 270 002 01 1 1 1 1 1 Buckle CV 300 2 2 2 2 2 Holder LNGS 465213 270 00...

Страница 53: ...LNGS 465213 270 10 OM Page 53 APPENDIX C LU 7 2 input output types and their usage...

Страница 54: ...ddress 14 Voice signal Audio notification Floor arrival notification Sound accompaniment No No No No 0 Yes No No No 1 No Yes No No 2 Yes Yes No No 3 No No Yes No 4 Yes No Yes No 5 No Yes Yes No 6 Yes...

Страница 55: ...OPPLER 30 EXPRESS 31 THYSSEN 50 32 SCHINDLER 33 BG 15 37 SODIMAS QI 39 ORONA ARCA1 42 KONE 43 VEGA 45 NICE 46 S9 48 iAStar 49 FST2 50 CANNY 56 VASSLER 58 BETACONTROL 67 KOLLMORGEN 68 THYSSEN CMC 70 TH...

Отзывы: