LK Actuator 24V AC  

Connect the actuators, bearing in mind the following:
A control zone consists of 1 LK Room Thermostat (trans-
mitter) but can contain one or more under 

ß

 oor heating 

loops equipped with actuators. All actuators in a control 
zone must be connected to a common channel on the 
receiver unit.

LK Actuator.

Cq 4 and Cq 6 Control Unit 

For the Cq 4 and Cq 6 Receiver Unit, a maximum of 4
actuators can be connected to each channel. The circuit
diagram shows that all channels in Cq 4, and 2 channels in
Cq 6, have double terminal boards, a or c respectively, for
connecting the actuators. Cq4 and Cq6 receiver units can
operate a maximum of 16 actuators.

When connecting two or more actuators to the same 
channel, the connections must be only to the double circuit
boards.

Fig. 1. Circuit diagram Cq 4, (M = actuator).

Fig. 2. Circuit diagram Cq 6, (M = actuator).

DESIGN

The LK Room Thermostat Cq (transmitter) regulates the 
temperature in a zone (e.g. a room) via radio signals to 
the receiver unit. Note: locate the receiver unit close to 
the heating circuit manifold.

The receiver unit converts radio signals to control signals
to activate the actuators.

The receiver unit is available in three sizes: 

•  LK Cq 1 intended for 1 control zone. 
•  LK Cq 4 for a maximum of 4 control zones, (channel 1 - 4).
 • LK Cq 6 for a maximum of 6 control zones, (channel 1 - 6).

The receiver unit functions along the same principles, but
the Cq 1 unit, which only has one receiver channel, differs
somewhat in its design. The instructions for this model 
therefore contain a few additions.

REQUIREMENTS

A suitably quali

Þ

 ed electrician or installation engineer, must

carry out electrical installation in accordance with the 
circuit diagram 

Þ

 gs. 1 + 2. To achieve protection class 2,

all necessary installation measures must be taken.

Installation and start-up (memorizing) is best carried out
in the following order:

The receiver unit  

The receiver unit should be located close to heating circuit
manifold to avoid lengthening the actuator connection 
cables.

In certain circumstances, the transmitters (thermostat)
signal may be too weak, e.g. if the receiver unit is assembled
in a metal enclosure (e.g. LK Manifold Cabinet). In these
cases, the LK Antenna Cq. Should is used. (See separate
section, LK Antenna Cq.)

Assembly instructions

LK Wireless Room Control Cq (NO)

a

channel 1

Mains
AC 230V

Supply AC 24V 
LK Transformer

BR3

channel 2

a b b c c

a a b b c c

channel 3

channel 4

a a b

7 8 9

b c c

a a b b c c

M

M

a

channel 1

Mains
AC 230V

channel 2

a b b c c

a b c

channel 3

a a b

7 8

b c c

M

M

M

a b c

channel 4

a b c

channel 5

a b c

channel 6

Supply AC 24V

LK Transformer

EN-33.C.14.1-6.0501

1

Содержание Cq

Страница 1: ...r 1 control zone LK Cq 4 for a maximum of 4 control zones channel 1 4 LK Cq 6 for a maximum of 6 control zones channel 1 6 The receiver unit functions along the same principles but theCq1unit whichonlyhasonereceiverchannel differs somewhat in its design The instructions for this model therefore contain a few additions REQUIREMENTS AsuitablyqualiÞedelectricianorinstallationengineer must carry out e...

Страница 2: ...ght actuators can be connected Up to two actuators can be connected direct to Cq1 However if necessary it is possible to connect up to eight actuators to Cq1 by using an external wiring junction box In both cases the actuators are connected parrallel to each other and in line between terminal 9 and the LK Transformer Fig 3 Circuit diagram Cq 1 M Actuator LK Transformer 230 24 V AC A transformer 60...

Страница 3: ...rds the heat symbol See the section LK Room Thermostat Cq If the setting was right and the problem continues see the section Heat Cool NB During set up only the indicator light on channel 4 or channel 6 comes on when one or more other channels trigger the heating This function continues until all the channels are activated For more informa tion see the section Pump Control ADDITIONAL MEASURES Asse...

Страница 4: ...ess the Reset button and the button for Channel 4 at the same time First release Reset followed by Channel 4 NB FortheCq1unit thechangeismadeontheroom thermostat Alarm Whenafaultoccurs theindicatorlightbeginstoßashwith anirregulartimeintervalandasoundsignalisheard During signaldisruption theaffectedchannelwilldeliverapproxi mately 70 heat output Temporary interruption If no signal is received from...

Страница 5: ... Room Thermostat Controloccursusingpulsewidthmodulation PBM which isintendedforactuators Thecontrolsignal whichiscalcu lated from the difference between the actual temperature and the temperature entered is emitted in the form of a signal with different pulse and rest ratios The sum of the signal and rest period is always 10 minutes With large temperature variations the thermostat is constantly sw...

Страница 6: ...pproximately 3 years Control function PBM optional 2 point Cycle time approximately 10 minutes total on and off time Measurement interval approximately 10 minutes Type Heat Cool Valve exercising Once a day for 3 minutes can be switched off BR1 Temperature sensor NTC Transfer frequency 868 MHz Modulation FM Aerial Intern Transmission interval 10 minutes Range typical 100 metres free air or 2 ßoors ...

Отзывы: