background image

4

English

EN.33.C.28.0904

Assembly instructions | LK Wired Room Control NC

Valve

When the actuator has been disconnected the 
valve function can be controlled by pressing the 
spring loaded valve spindle.

Fuse

Blown fuse; please check for incorrect wiring or 
shortcircuits. If programmers, timers or other 
switches are used, ensure that they are connected 
to the pump-relay terminal only. DO NOT switch 
the live on and off to the LK Connnection Box, 
which must be kept permanently live. 

Technical data

LK Connection Box NC

Article no. 

241 81 18 

Sizes 

350 x 100 x 60 mm 

Primary voltage 

230 V 

Secondary voltage 

24 V 

Power supply unit capacity 

40 VA 

Cable protection class 

IP 20 

Protection class 

Primary fuse 

200 mAt according 
to IEC 127-2/V 

Pump relay, volt-free relay 

4 Amp 

Max number of actuators / connection 
box 

12 

Max number of actuators / terminals 

Max number of thermostats / connec-
tion box 

LK Actuator NC

Article no. 

241 81 20 

Sizes 

44 x 47 x 53 mm 

Voltage 24 

Rated output 

2,0 W 

Cable protection class 

IP 54 

Ambient temperature 

0-60 grader 

LK Room Thermostat NC

LK Room Thermostat NC, Article no 

241 81 09 

LK Room Thermostat NC Dti, Article no 

241 81 23 

Sizes 

75 x 75 x 27 mm 

Voltage 24 

Max number of actuators / thermostats 

Temperature range 

5-30 degrees 

Cable protection class 

IP 30 

LK Clip Rail 12

Place a conduit along the long sides of the fl oor 
heating installation facing the nearest short end. 
Place the conduit at the short end between two 
heating pipes and end it approx. 2 meters in. Seal 
the end of the conduit with tape or similar to pre-
vent concrete from getting into the conduit. The 
external sensor is slipped into the conduit before 
pouring the concrete and is connected to the room 
thermostat as instructed above. 

Function control test

Once installation is complete a function control 
test should be carried out.

Turn all the thermostats on fully and ensure 

1. 

that all LEDs are lit up on the thermostats 
and the box. Wait for approx 6 minutes 
and ensure that the status indicator for the 
actuators is in its highest position.
Turn down all the thermostats to minimum, 

2. 

all the LEDs should be switched off and all 
the actuators should be closed after approx 
6 minutes.

Troubleshooting, room control

Connection box

The LED should light up when the thermostat is 
turned on fully. If the LED does not light up en-
sure that there is a mains connection and that the 
fuse for the box is intact.

Room thermostat

The LED is lit up when the room thermostat is re-
questing heat. Ensure that all wires are properly 
connected. When the room thermostat is turned 
on fully there should be a voltage of 24 V between 
terminal 1 and 4.

Actuator

The top of the actuator is equipped with a status 
indicator that indicates whether the actuator is 
open or closed. When the status indicator is at the 
top the actuator is open and vice versa. Actuation 
time approx 6 minutes.

Содержание Wired Room Control NC

Страница 1: ...ators are signalled via the connection box Settings requirements All distribution flows must be adjusted according to the installation guide for the unit The heat set tings for the control unit are regulated according to the requirements of the heat system and the cli mate zone A control zone consists of 1 LK Room Thermostat NC that can control one or more un der floor heating areas each equipped ...

Страница 2: ...ure is to be ad justed Remote switching The LK Control is a complete unit for outdoor tem perature dependent flow temperature control and adapted for LK s shunt programs If LK Control is used then the volt free pump relay of LK Connec tion box can be connected to LK Control connec tions M and H1 By connecting LK Connection box to the LK Control gives the function that when all actuators on the man...

Страница 3: ...d is connected to the room thermostat as instructed above Floor heating in secondary spaced boarding Place a conduit right between two heat distribu tion plates attach the conduit on the edge of the secondary spaced boarding using a clip for con duits Take into consideration that the placement is at a representative point for the area that is going to be adjusted The external sensor is slip ped in...

Страница 4: ...ong sides of the floor heating installation facing the nearest short end Place the conduit at the short end between two heating pipes and end it approx 2 meters in Seal the end of the conduit with tape or similar to pre vent concrete from getting into the conduit The external sensor is slipped into the conduit before pouring the concrete and is connected to the room thermostat as instructed above ...

Страница 5: ...ectric connections LK Connection Box NC L N zone 2 zone 5 1 4 zone 4 2 1 1 4 zone 1 6 2 4 2 1 7 4 1 zone 2 2 4 zone 1 2 3 zone 2 1 8 4 1 zone 4 4 2 200 mAT 4 A pot free 200 mAt 4 A pot free N L N L zone1 2 4 1 230 V 24 V 40 VA Transformer 98927 2 1 4 ZONE 1 ZONE 2 ZONE 2 ZONE 1 2 1 98927 2 1 4 1 2 1 7 2 3 4 5 6 7 9 11 10 8 Sample connections for a zone Terminal 1 9 on the room thermostat is connec...

Страница 6: ...6 English Wiring with LK Shunt LK Zone Valve and Time Switch if req d LK Connection Box with LK Shunt and LK 2 port Zone Valve 10 Mar 06 EN 33 C 28 0904 Assembly instructions LK Wired Room Control NC ...

Отзывы: