background image

1 (9)

Pipe installation

Installation should be carried out according to the 

applicable regulations and standards.

The boiler should be assembled indoors, moun-

ted to a wall or similar with the pipe connections 

underneath. 

The ambient temperature must not exceed 30°C.

The gap between the underside of the boiler and 

the surface beneath it must be at least 300 mm to 

enable electric cartridges to be replaced, if neces-

sary.

Hard, calciferous water is not suitable for use with 

this heating system. To avoid corrosion damage 

the pH value should not be too low. 

The blow-off pipe from the electric boiler safety 

valve flows into a drip tray in the boiler cabinet.

The installation inspection should be carried out 

according to the applicable regulations on a unit 

with a sealed expansion vessel, before the unit is 

operated. The inspection should be conducted by a 

suitably qualified person. The replacement of parts 

and the expansion vessel must not occur without 

a repeat inspection of the installation.

A counter torque wrench should be used during 

connection to avoid damaging the internal piping.

Design

LK Electric Boiler 4,5 kW is a wall-mounted elec-

tric boiler, intended primarily for low-temperature 

heating systems, e.g. under floor heating.

LK Electric Boiler 4,5 kW is delivered as a complete 

unit. The boiler is ready for use once the water and 

electricity are connected. 

The boiler includes:

•  Thermostat 
•  Overheating (maximum safe temperature) 

protection 

•  Indication power on and triggered overhea-

ting (maximum safe temperature) protection

•  Control switch 
•  Circulation pump, Grundfos UPM3 Auto L 

15-50

•  Expansion vessel 
•  Pressure gauge 
•  Thermometer 
•  Safety valve, 2,5 bar 
•  Automatic air bleeding valve 
•  Bypass valve 

The electric boiler is not fitted with a water heater, 

this is installed separately.

Function/Requirements

The boiler output meets the heat requirements 

for up to 90 m² of living space, depending on the 

insulation and ventilation. Depending on the con-

nection the boiler can supply 1,5, 2,25, 3 or 4,5 kW. 

The boiler is controlled by an in-built thermostat. 

If necessary, the boiler can also be controlled by an 

external thermostat, for more information please 

refer to the heading “External switching/room 

thermostat”.

Assembly

The boiler is mounted to the wall, or in a cabinet.

The boiler dimensions 420 x 700 x 200 mm (W x H 

x D) mean that it can be installed in most kitchen 

cabinets.

LK Electric Boiler - 4,5

EN.33.C.111.1804

Assembly instructions | LK Electric Boiler - 4,5

Содержание Electric Boiler-4.5

Страница 1: ...wall mounted elec tric boiler intended primarily for low temperature heating systems e g under floor heating LK Electric Boiler 4 5 kW is delivered as a complete unit The boiler is ready for use once the water and electricity are connected The boiler includes Thermostat Overheating maximum safe temperature protection Indication power on and triggered overhea ting maximum safe temperature protectio...

Страница 2: ...stment valve should be open by at least half a revolution 1 2 1 Isolation valve supply and return 2 By pass valve accessible after the protective plug has been unscrewed Installation system outline Below is a system outline Units should always be installed according to regulations and standards 4 1 2 3 1 LK Electric Boiler 4 5 2 Filling valve Drain valve 3 Manifolds under floor heating 4 Under flo...

Страница 3: ...de any one of 10 curves can be selected by turning the button When the button has been released for 10 sec the pump returns to operat ing mode the LEDs stop flashing and the selected curve becomes active A lit red LED indicates an alarm or warning Indication Fault Status Measure Red fourth yellow Motor blocked Pump tries to restart at 1 5 sec intervals Release motor impeller or wait Red third yel ...

Страница 4: ...ied out under the supervision of an authorized installer Electric installation Electric installation should be carried out in accor dance with the applicable regulations under the supervision of an authorized electrician The boiler must not be connected to the electrical supply before it is filled with water The boiler should be preceded by all pole circuit switches The ambient temperature must no...

Страница 5: ...capacitor 5 Circulation pump 6 Overheating maximum safe temperature protection 7 Thermostat 8 Electric cartridge 9 Control switches 10 Alarm indication overheating maximum safe temperature protection triggered 11 On off indicating light goes on when vol tage is supplied to the boiler 12 Contacts External switching room thermostat The boiler can be blocked by external equipment e g room thermostat ...

Страница 6: ...perature protection triggered Inspect together with installer after the instal lation that the unit is in a satisfactory condition Have the installer demonstrate how the unit works and should be handled The boiler and the heating system must be filled with water before the circuit switch is set to on The boiler cover should be assembled during ope ration Note Monitor the amount of water in the ves...

Страница 7: ...ox 35 40 C and for wooden joists approx 40 45 C The desired temperature varies according to the time of year Safety valve The safety valve should be exercised regularly to maintain the safety function Overheating maximum safe temperature protection The overheating maximum safe temperature pro tection on the boiler is triggered when the boiler temperature exceeds 80 The protection is restored on th...

Страница 8: ... the boiler temperature falls below 65 C push the button hard for reset No or insufficient heat Thermostatic valves on the heating system or boiler thermostat set at too low temperature Inspect and adjust Faulty adjustment of bypass valve Inspect and adjust Group fuses for boiler are triggered The electric cartridge is broken Inspect the electric cartridge by testing it in isolation Measure betwee...

Страница 9: ...iler no Cogeneration space heater no Combination heater no Rated heat output Prated 5 kW Useful heat output at rated heat output P4 4 5 kW Energy class D Seasonal space heating energy efficiency boiler boiler with UTK ηs ηs 36 38 Useful efficiency η4 39 7 Auxiliary electricity consumption in stand by mode PSB 0 019 kW Standby heat loss Pstby 0 037 kW Material recycling After dismantling the boiler...

Отзывы: