background image

MAINTENANCE

Operation Testing

5

Operation Testing

1. Disconnect the pump from the power source.
2. Remove tank cover assembly.

• The cover snaps on to the reservoir.
• Pull out on the slot on the long side of the top. 

Place a finger in one of the larger corner holes 
and carefully lift off the cover. Hold level.

3. Turn on power to the pump.
4. Test pump operating switch by raising the pump 

switch float. 
•  The motor should turn on before the float contacts the tank cover. 

5. Test high level switch by raising the high level switch float. 

• The switch should activate before the float contacts the tank cover.
• If wired to NO terminal, air handling device should shut down.
• If wired to NC terminal, external component (alarm or relay) should activate.

6. Disconnect the pump from the power source.
7. Replace the tank cover assembly.
8. Turn on power to the pump.

MAINTENANCE

To inspect and clean the tank and other components, follow these steps:
1. Disconnect the pump from the power source.
2. Remove tank cover assembly from the tank.

• The cover snaps on to the reservoir.
• Pull out on the slot on the long side of the top. Place a finger in one of the larger corner holes 

and carefully lift off the cover. Hold level.

3. Be sure the floats move freely. Clean as necessary.
4. Remove the check valve and backwash the discharge port into the volute over a sink.
5. Clean the tank with warm water and mild soap.
6. Flush tank with fresh water to ensure that residual condensate does not create localized pockets of 

acid that could cause pitting.

7. Check inlet and outlet piping. Clean as necessary. Be sure there are no kinks that would inhibit flow.
8. Inspect the check valve and clean with warm water and mild soap if necessary.
9. Replace the tank cover assembly.
10. Test operation of the system.

Risk of bodily injury or property damage.

Do not allow the tank to overflow during this maintenance.

Inspect and test the condensate removal system condition and operation every 6 months (more frequently in heavy-use applica

-

tions).

Содержание VCMA Series

Страница 1: ...l and local electrical and plumbing codes and within Little Giant recommendations may result in electrical shock or fire hazard unsatisfactory performance or equipment failure Know the product s appli...

Страница 2: ...The pump should only be used with liquids compatible with pump component materials If the pump is used with liquids incom patible with the pump components the liquid can cause failure to the electric...

Страница 3: ...ameter maximum tubing or piping to prevent excessive flow back to unit 4 Route outlet tubing straight up not exceeding 75 of total dynamic head capacity of the pump 5 At the top slope discharge line d...

Страница 4: ...age circuit in the event of high water level activating an external alarm or relay purchased separately Use the following proce dure if an NC configuration is required Remove the pump s motor cover 4...

Страница 5: ...mponents follow these steps 1 Disconnect the pump from the power source 2 Remove tank cover assembly from the tank The cover snaps on to the reservoir Pull out on the slot on the long side of the top...

Страница 6: ...vy to operate correctly Check valve stuck or plugged Remove check valve and inspect for proper operation Outlet flow is blocked Check outlet tubing to ensure that it is not kinked or blocked Clear blo...

Страница 7: ...equipos y procedimientos adec uados El hecho de no cumplir con los c digos el ctricos y de plomer a nacionales y locales y con las recomendaciones de Little Giant puede provocar peligros de descarga...

Страница 8: ...r la bomba No use un prolongador La bomba solo se debe utilizar con l quidos compatibles con los materiales que componen la bomba Si la bomba se utiliza con l quidos incompatibles con los componentes...

Страница 9: ...orriente y aseg rela con la abraza dera de manguera no suministrada Utilice 3 8 pulgada de di metro interior m ximo tuber a para evitar un flujo excesivo de vuelta a la unidad 4 Dirija la tuber a de s...

Страница 10: ...raci n 2 El instalador puede reconfigurar este interruptor al terminal NC para cerrar un circuito de voltaje bajo en el caso de nivel de agua alto lo que podr a activar un rel o una alarma externa que...

Страница 11: ...ccionar y limpiar el tanque y otros componentes siga los pasos que se detallan a continu aci n 1 Desconecte la bomba de la fuente de alimentaci n 2 Quite el conjunto de la cubierta del tanque La cubie...

Страница 12: ...salida est bloqueado Verifique la tuber a de salida para asegurarse de que no est retorcida ni bloqueada Despeje la tuber a bloqueada de lodo y residuos Limpie la tuber a de entrada y de salida El imp...

Страница 13: ...es recommandations de Little Giant pourrait mener une lectrocution ou un incendie une mauvaise performance ou une d faillance de l quipement Lisez et suivez attentivement les instructions pour viter t...

Страница 14: ...e ce soit Il peut uniquement tre raccourci si cela est n cessaire pour le faire rentrer dans le panneau de commande Toute pis sure entre la pompeet le panneau de commandedoit tre r alis edans unebo te...

Страница 15: ...rieur maximum tubulure ou tuyauterie pour viter un coulement excessif de retour l unit 4 Acheminez la tubulure de sortie de la pompe vers le haut Ne d passez pas 75 de la charge hydraulique gal h de...

Страница 16: ...ompe La pompe doit tre connect e ou branch e sur son propre circuit sans autre prise ou quipement sur la ligne du circuit Ne le raccordez pas un ventilateur ou tout dispositif fonctionnant par inter m...

Страница 17: ...d activer une alarme ou un relais externe vendus s par ment Utilisez la proc dure suivante si une configuration NC est requise Retirer le couvercle du moteur de la pompe 4 Soutenir l interrupteur et p...

Страница 18: ...posants suivez ces tapes 1 D branchez l alimentation de la pompe 2 Retirez l ensemble de capot du r servoir Le capot se fixe au r servoir par pression Tirez sur la fente situ e sur le c t long de la p...

Страница 19: ...elle n est pas coud e ou obstru e Nettoyez la boue et les d bris de tout tuyau obstru Nettoyez la tuyauterie d entr e et de sortie La roue de la pompe ne tourne pas Nettoyez toute obstruction dans le...

Страница 20: ...ic Co Inc Oklahoma City OK 73157 2010 800 701 7894 littlegiant com Pour l aide technique entrez s il vous pla t en contact Form 998086 R v 002 03 20 Droits d auteur 2020 Franklin Electric Co Inc Tous...

Отзывы: