PGR-3200 Insulation Monitor

 

Page 1 

 

 

Rev. 3-E-040918 

 
 

 

1.  G

ENERAL

 

  The  PGR-3200  Insulation  Monitor  measures  phase-to-
ground  resistance  to  detect  electrical-insulation  failure  in 
an ungrounded power utilization system.  It provides three 
levels of detection with a 50-k

 warning with an LED and 

output  contact  indication,  a  30-k

  warning  with  LED 

indication, and a 10-k

 alarm with LED and output contact 

indication.    An  analog  output  is  provided  for  predictive 
maintenance trending. 
  The  PGR-3200  can  be  used  to  detect  faults  in 
ungrounded  systems  up  to  6  kV.    It  can  be  directly 
connected to a system up to 1.3 kV, single or three phase, 
50  or  60  Hz.    A  PGH-series  high-tension  coupler  is 
required for 5- and 6-kV systems. 

 

2.   O

PERATION

 

  The  PGR-3200  actively  monitors  insulation  resistance 
when it is connected to the supply voltage.  All conductors 
connected  to  the  monitored  circuit  are  included  in  the 
insulation measurement.  See Fig. 2. 

 

2.1  R

ELAY 

O

PERATING 

M

ODE

 

  The PGR-3200 output relays operate in the non-fail-safe 
mode; they energize when an insulation warning or alarm 
occurs.   

 

2.2  F

RONT-

P

ANEL 

C

ONTROLS 

2.2.1  R

ESET

 

  The  front-panel  RESET  switch  is  used  to  reset  latching 
trips.    Cycling  the  supply  voltage  will  also  reset  the  PGR-
3200.  See Section 2.5. 

 
2.2.2  T

EST

 

  All LED’s will light and output relays will energize when 
the TEST button is pressed for at least 8 s. 

 

2.3  F

RONT-

P

ANEL

 I

NDICATION 

2.3.1  P

OWER

 

  The  green  LED’s  labelled  PWR  indicates  presence  of 
supply voltage. 

 

2.3.2  I

NSULATION 

W

ARNING

 

  The red LED’s labelled 50 k

 and 30 k

 will light when 

those  respective  insulation  resistance  values,  or  lower  are 
measured. 

 

2.3.3  A

CTIVE

 

  The red LED labelled ACTIVE indicates the monitor is 
enabled. 

2.3.4  I

NSULATION 

A

LARM

 

  When insulation resistance measures 10 k

 or less, the 

red LED labelled <10 k

 will light. 

 

2.4  A

NALOG 

O

UTPUT

 

  A non-isolated, 0- to 1-mA output (terminals 25 and 26) 
indicates insulation resistance.  The metering output relates 
to  an  insulation-resistance  range  of  0  to  infinity  using 
optional meter PGA-0510.  See Figs. 2, 3, and 6. 

 

2.5  R

EMOTE 

R

ESET

 

  When remote-reset terminals 18 and 19 (alarm) or 21 and 
22  (warning)  are  connected,  a  warning  or  alarm  remains 
latched until the RESET switch is pressed or the remote-reset 
terminals are momentarily opened. 
  If  the  remote-reset  terminals  are  not  connected,  the  
PGR-3200  operates  in  non-latching  mode;  a  warning  or 
alarm will reset when the fault is removed. 

 

2.6  R

EMOTE 

T

EST

 

  When terminal 29 is connected to ground the monitor will 
alarm.  See Figs. 2 and 3.  Response to a test input can take 
several seconds. 

 

Содержание PGR-3200

Страница 1: ...32 3873 E mail techline littelfuse com www littelfuse com PGR 3200 MANUAL INSULATION MONITOR REVISION 3 E 040918 Copyright 2018 by Littelfuse Inc All rights reserved Document Number PM 1025 EN Printed...

Страница 2: ...PGR 3200 Insulation Monitor Page i Rev 3 E 040918 This page intentionally left blank...

Страница 3: ...gh Tension Couplers 7 5 Ordering Information 7 6 Performance Test 7 6 1 Insulation Test 7 Appendix A PGR 3200 Revision History 8 LIST OF FIGURES FIGURE PAGE 1 PGR 3200 Outline and Mounting Details 2 2...

Страница 4: ...PGR 3200 Insulation Monitor Page iii Rev 3 E 040918 This page intentionally left blank...

Страница 5: ...ng the supply voltage will also reset the PGR 3200 See Section 2 5 2 2 2 TEST All LED s will light and output relays will energize when the TEST button is pressed for at least 8 s 2 3 FRONT PANEL INDI...

Страница 6: ...PGR 3200 Insulation Monitor Page 2 Rev 3 E 040918 FIGURE 1 PGR 3200 Outline and Mounting Details...

Страница 7: ...l 5 L2 N as the neutral terminal Connect terminal 30 to ground For systems up to 1 3 kV connect terminal 2 to one phase on the load side of the starter Connect terminals for latching operation remote...

Страница 8: ...nd mounting details Connect protective ground terminal to ground Connect terminal E to ground or to PGR 3200 terminal 30 which must be grounded Connect terminal M to PGR 3200 terminal 29 PGR 3200 term...

Страница 9: ...PGR 3200 Insulation Monitor Page 5 Rev 3 E 040918 FIGURE 5 PGH 6000 Outline and Mounting Details FIGURE 6 PGA 0510 Analog Ohm Meter...

Страница 10: ...istance Output Relays Warning and Alarm Configuration N O and N C Form C Operating Mode Non Fail Safe UL Contact Rating 5 A 240 Vac resistive 0 28 A 30 Vdc resistive Switching Capacity 1 200 VA Supple...

Страница 11: ...h Tension Coupler PGH 6000 6 kV High Tension Coupler NOTES 1 UL not available for this supply option 6 PERFORMANCE TEST 6 1 INSULATION TEST Perform this test with the starter open and appropriate lock...

Страница 12: ...added REVISION 3 D 111915 SECTION 4 Terminal torque specifications added REVISION 3 D 111915 SECTION 4 Terminal torque specifications added SECTION 5 Ordering information updated REVISION 3 C 080415...

Отзывы: