PGR-3200 Insulation Monitor
Page 7
Rev. 3-E-040918
4.2 PGH
H
IGH-
T
ENSION
C
OUPLERS
Maximum Line Voltage:
PGH-5000 ............................... 5,000 Vac
PGH-6000............................6,000 Vac
Current to Ground .....................2.5 mA maximum
Terminal M Maximum
Voltage ......................................50 Vac
Terminals:
E, E, and M ......................Wire Clamping,
26 to 12 AWG
(0.13 to 3.3 mm
2
)
conductors
Tightening Torque ...........0.50 N∙m (4.43 lbf∙in)
......................................Wire Clamping,
10 AWG (5.3 mm
2
)
maximum
High Tension Lead A ................8 AWG (8.4 mm
2
),
40 kVdc, 915 mm (36”)
5. O
RDERING
I
NFORMATION
PGA-0510 ..................................... Analog Ohm Meter
PGH-5000 ..................................... 5 kV High Tension
Coupler
PGH-6000 ..................................... 6 kV High Tension
Coupler
NOTES:
(1)
UL not available for this supply option.
6. P
ERFORMANCE
T
EST
6.1 I
NSULATION
T
EST
Perform this test with the starter open and appropriate
lock-out procedures.
Connect a 20 k
resistor between one phase and ground
at the line side of the starter or motor terminal box. Select
a phase that is not connected to PGR-3200 terminal 2 (or
the
PGH-5000
or
PGH-6000).
The
PGR-3200 will indicate a warning by lighting the 50 k
and 30 k
LED’s and energizing the 50 k
insulation
relay.
Replace the 20-k
resistor with an 8 k
resistor.
The PGR-3200 will indicate an alarm by lighting the
< 10 k
LED and energizing the 10 k
insulation relay.