AF0100 Arc-Flash Relay

GENERATOR APPLICATION GUIDE

7

Littelfuse.com/ArcFlash

© 2017 Littelfuse Products

SENSOR COVERAGE (

Distance where a line-of-sight arc will be detected)

Light Sensor

2m

2.5m

Up to 

   50 m cable

Connect to Relay

180" 2-Meter Half-Sphere  
Sensor Viewing Angle

Up to 

   50 m cables

Receiver

Black Shield 

    (no light detection)

Transmitter

Connect to Relay

PGA-LS20 Series

 

Fiber-Optic Sensor

PGA-LS10 Series

 

Point Sensor

Point Light Sensor

 

Line-of-sight light sensor detects an arc as small 

as 3 kA in a 2-meter half-sphere radius.

 

§

 Visual LED indication for “Ready” or 

“Tripped” state to assist with fault location

 

§

 Robust sensor design can withstand a 

detected arc-flash event

 

§

 Sensor can be installed up to 50 m (164 ft) 

away from relay; electrical cable can be cut 

and easily re-terminated in the field

Fiber-Optic Light Sensor

 

The 360° light sensor detects light throughout 

the entire length of the fiber. Ideal to protect 

bus bars, multiple compartment installations 

like motor control centers, or areas with  

many obstructions.

 

§

 Visual LED indication for “Ready” or 

“Tripped” state to assist with fault 

location

 

§

 Durable resin fiber material allows small 

bending radius (>5 cm) and greater 

flexibility without breaking

 

§

 Ready to install from the factory, no need 

to terminate in the field or polish as with 

glass fiber

 

§

 Fiber sensors can be installed in locations 

up to 50 m

 

§

 (164 ft) away from relay; electrical cable 

can be cut and easily re-terminated in  

the field

Содержание AF0100

Страница 1: ...GENERATOR APPLICATION GUIDE AF0100 ARC FLASH RELAY...

Страница 2: ...ckground 4 Methods 4 GENERATOR PROTECTION USING AF0100 5 Generator To Generator Breaker Connection 5 Transformer Enclosure 5 AF0100 CONNECTION DIAGRAM 6 SENSOR COVERAGE 7 EFFECT OF GENERATOR GROUNDING...

Страница 3: ...r maintenance In many cases arc flash calculations limit burn time to two seconds for workers to get clear of the danger In a generator application the personnel are trapped in the enclosure during an...

Страница 4: ...An instantaneous trip setting that is less than the available arcing current 6 An instantaneous override that is less than the available arcing current 7 An approved equivalent means ANSI Z10 RISK CON...

Страница 5: ...also turn off the generator The latter is usually accomplished by either connecting to the automatic voltage regulator AVR an emergency stop circuit or generator controller Often the voltages require...

Страница 6: ...spaces of mobile gensets PC CONNECTION TRIP OUTPUT 1 TRIP OUTPUT 2 100 240 VAC DC SUPPLY 24 48 VDC SUPPLY DIGITAL INPUTS OUTPUTS UNIT HEALTH AF0100 CONNECTION DIAGRAM Generators are often the last li...

Страница 7: ...sor design can withstand a detected arc flash event Sensor can be installed up to 50 m 164 ft away from relay electrical cable can be cut and easily re terminated in the field Fiber Optic Light Sensor...

Страница 8: ...or three phase fault levels only resulting in mechanical damage during a ground fault even if the fault is not arcing The Littelfuse SE 701 Ground Fault Relay can monitor for a wide range of current l...

Страница 9: ...ult relay especially suitable for rental units PGR 4300 Series Generator Ground Fault Relay Generator Ground Fault Relay for solidly grounded generators No CT required Generator ground fault current c...

Страница 10: ...tic configuration minimize labor costs Seamless to your customer no customer interaction required with arc flash relay We are a global partner for your global business Global certifications Global dis...

Страница 11: ...nit AF0100 Arc Flash Relay Date and Time Synchronize to PC Clock Disabled o Enabled o Disabled Light Sensors Common Settings Light Immunity Lower Limit 10 10 25 klux klux Arc Detection Time Before Tri...

Страница 12: ...ns contact our Technical Support Group 800 832 3873 Specifications descriptions and illustrative material in this literature are as accurate as known at the time of publication but are subject to chan...

Отзывы: