Littelfuse AF0100 Скачать руководство пользователя страница 5

AF0100 Arc-Flash Relay

GENERATOR APPLICATION GUIDE

5

Littelfuse.com/ArcFlash

© 2017 Littelfuse Products

GENERATOR PROTECTION USING AF0100

Generator to Generator Breaker Connection

While the generator breaker can protect the generator from overcurrent faults, there is often nothing protecting the 

connection from the generator to the generator breaker from overcurrent or arc flash. 

As a result, an arc in this connection will persist and its destructive energy will increase, being fed from other 

sources connected in parallel with the generator as well as the generator itself. Eventually, the amount of energy 

required may be enough to trip the generator breaker (assuming it isn’t engulfed in the arc’s plasma cloud) and the 

arc will extinguish when enough material has been vaporized that the generator cannot produce enough energy to 

maintain the arc, the generator is destroyed, or its fuel source consumed in the arc. Often a fault on the generator 

will burn the generator to the ground.

An arc-flash relay monitoring this section of the bus can dramatically reduce the total energy released and therefore 

the damage and risk to personnel. One or two point sensors are typically sufficient to monitor the busway/cables 

and the breaker cabinet. In the case that an arc is detected, all sources of energy to it must be cut off. The arc-flash 

relay must trip the generator breaker but also turn off the generator. The latter is usually accomplished by either 

connecting to the automatic voltage regulator (AVR), an emergency stop circuit, or generator controller. Often the 

voltages required to trip these two circuits are different and require isolated contacts. 

The AF0100 was specifically designed for generator applications, with two isolated Form-C  trip outputs to cut 

off all sources of energy from the arc. A 24-48 Vdc supply allows for power directly from the battery bank and 

withstands voltage sags and overvoltages, and the entire relay is designed to withstand vibration. As well, a unit 

health contact can be programmed for non-fail-safe so that loss of supply voltage when powering down the 

batteries will not cause nuisance alarms for remote monitoring. Finally, its compact design means that it can find a 

home in any generator control panel.

Transformer Enclosure

In applications where medium voltage distribution is required, parallel generators may be connected to a step-

up transformer. It is advantageous to protect the transformer from an arc flash, particularly if there is a shunt trip 

that can disconnect it from supply. In this case, one or two sensors in the enclosure monitoring the primary and 

secondary connections can dramatically reduce downtime and repair cost for the transformer if an arc flash occurs.

Generator Enclosure

To other parallel generators or utility

Transformer Enclosure

Trip 1

Trip 1

Trip 2

AF0100

AVR/

Control Circuit

AF0100

Sensor

Primary Side Sensor

Secondary Side Sensor

Breaker

Sensor

Generator

Transformer

To application

Содержание AF0100

Страница 1: ...GENERATOR APPLICATION GUIDE AF0100 ARC FLASH RELAY...

Страница 2: ...ckground 4 Methods 4 GENERATOR PROTECTION USING AF0100 5 Generator To Generator Breaker Connection 5 Transformer Enclosure 5 AF0100 CONNECTION DIAGRAM 6 SENSOR COVERAGE 7 EFFECT OF GENERATOR GROUNDING...

Страница 3: ...r maintenance In many cases arc flash calculations limit burn time to two seconds for workers to get clear of the danger In a generator application the personnel are trapped in the enclosure during an...

Страница 4: ...An instantaneous trip setting that is less than the available arcing current 6 An instantaneous override that is less than the available arcing current 7 An approved equivalent means ANSI Z10 RISK CON...

Страница 5: ...also turn off the generator The latter is usually accomplished by either connecting to the automatic voltage regulator AVR an emergency stop circuit or generator controller Often the voltages require...

Страница 6: ...spaces of mobile gensets PC CONNECTION TRIP OUTPUT 1 TRIP OUTPUT 2 100 240 VAC DC SUPPLY 24 48 VDC SUPPLY DIGITAL INPUTS OUTPUTS UNIT HEALTH AF0100 CONNECTION DIAGRAM Generators are often the last li...

Страница 7: ...sor design can withstand a detected arc flash event Sensor can be installed up to 50 m 164 ft away from relay electrical cable can be cut and easily re terminated in the field Fiber Optic Light Sensor...

Страница 8: ...or three phase fault levels only resulting in mechanical damage during a ground fault even if the fault is not arcing The Littelfuse SE 701 Ground Fault Relay can monitor for a wide range of current l...

Страница 9: ...ult relay especially suitable for rental units PGR 4300 Series Generator Ground Fault Relay Generator Ground Fault Relay for solidly grounded generators No CT required Generator ground fault current c...

Страница 10: ...tic configuration minimize labor costs Seamless to your customer no customer interaction required with arc flash relay We are a global partner for your global business Global certifications Global dis...

Страница 11: ...nit AF0100 Arc Flash Relay Date and Time Synchronize to PC Clock Disabled o Enabled o Disabled Light Sensors Common Settings Light Immunity Lower Limit 10 10 25 klux klux Arc Detection Time Before Tri...

Страница 12: ...ns contact our Technical Support Group 800 832 3873 Specifications descriptions and illustrative material in this literature are as accurate as known at the time of publication but are subject to chan...

Отзывы: