![Littelfuse Startco SE-601 Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/littelfuse-startco/se-601/se-601_manual_1928671015.webp)
Page 11
SE-601 DC Ground-Fault Monitor
Rev.
2-B-073014
Electrostatic
Discharge
........
IEC
61000-4-2
± 6 kV contact discharge
(direct and indirect)
± 8 kV air discharge
Radiated
RF
Immunity
........
IEC
61000-4-3
10 V/m, 80-1000 MHz,
80% AM (1 kHz)
10 V/m, 900 MHz,
200 Hz pulse modulated
Fast
Transient
......................
IEC
61000-4-4
4 kV on AC mains and
I/O
lines
Surge
Immunity
..................
IEC
61000-4-5
Zone B
± 1 kV differential mode
± 2 kV common mode
Conducted
RF
Immunity
....
IEC
61000-4-6
10 V, 0.15-80 MHz,
80% AM (1 kHz)
Magnetic Field Immunity ... IEC 61000-4-8
50 Hz and 60 Hz , 30 A/m
and 300 A/m
Voltage
Interruption
...........
IEC
61000-4-11,
IEC 61000-4-29,
0% for 5, 10, 20, 50,
100 & 200 ms 3x each
Power
Frequency
................ IEC 61000-4-16
Zone
A:
differential
mode 150 Vrms
Zone A: common mode
300 Vrms
1 MHz Burst ....................... IEC 61000-4-18
± 1 kV differential mode
(line-to-line)
± 2.5 kV common mode
RFI Compliance ....................... FCC Part 15, Subpart B,
Class A – Unintentional
Radiators
Certification .................................CSA, Canada and USA
LR 53428
US
C
R
UL Listed
Australia
N11659
FCC
CE,
European
Union
Complies to IEC 61010-1:2001 (2
nd
Edition);
EN 61010-1:2001 (2
nd
Edition) Safety Requirements for
Electrical Equipment for Measurement, Control, and
Laboratory Use – Part 1.
NOTES:
(1)
Over operating temperature range of -40 to 60
C (-40
to 140°F).
(2)
Trip time at 3 × trip-level setting.
5.2 G
ROUND
R
EFERENCE
M
ODULES
Nominal Current ..........................12.5 mA
Maximum Fault Current ..............25 mA
Duty Cycle ...................................Continuous
Environment:
Operating
Temperature
.......
40 to 60
C (-40 to
140°F)
Storage
Temperature
...........
55 to 80
C (-67 to
160°F)
Humidity
................................85%
Non-Condensing
SE-GRM024:
Power
Dissipation
At 24 Vdc ........................... Unfaulted 0.3 W,
Ground Fault 0.6 W
maximum
Shipping Weight ................... 300 g (0.7 lb)
SE-GRM048:
Power
Dissipation
At 48 Vdc ........................... Unfaulted 0.6 W,
Ground Fault 1.2 W
maximum
Shipping Weight ................... 300 g (0.7 lb)