Page 6
SE-601 DC Ground-Fault Monitor
Rev.
2-B-073014
CAUTION XXX V
SE-GRMXXX
SE-GRM780 TO SE-GRM1000
91.7
(3.61)
78.5
(3.09)
14.1
(0.56)
63.5
(2.50)
5.0
(0.20)
203.2
(8.0
0)
21
2.7
(8.37)
MOUNTING DETAIL
SIDE
FRONT
NOTES:
1. DIMENSIONS IN MILLIMETRES (INCHES).
2. MOUNTING SCREWS: M4 OR 8-32.
3. ADDITIONAL HEAT SINK REQUIRED IF OPERATED MORE THAN TWO MINUTES WITH A GROUND FAULT.
XXX VDC
GROUND
REFERENCE
MODULE
+
-
S
UNFAULTED
GROUND
FAULT
FAULT
CURRENT
DUTY
CYCLE
MODULE
SE-GRM780
9.6 W
19.2 W MAX
24.6 mA
CONTINUOUS
SE-GRM1000
12.5 W
25 W MAX
25 mA
CONTINUOUS
CONTACT FACTORY FOR OTHER VOLTAGES
FIGURE 5. SE-GRM-Series Ground-Reference Modules – 780 to 1,000 V.