Page 9
SE-601 DC Ground-Fault Monitor
Rev.
2-B-073014
%
100
0
20
40
80
60
®
67.5
(2.657)
R1.25(0.049)
MAXIMUM
67
.5
(2.657)
66.0
(2.598)
48.0
(1
.890)
TOP
MOUNTING CUTOUT
71
.0
(2.795)
65.0
(2.559)
ANALOG % CURRENT METER
PGA-0500
REAR
SIDE
FRONT
NOTE 1
NOTES:
1. CONVERSION KIT FOR 0-5 V ANALOG
OUTPUT. SEE PGA-0500 DOCUMENTATION.
2. DIMENSIONS IN MILLIMETRES (INCHES).
FIGURE 8. PGA-0500 Analog Percent Current Meter.
4. SE-601 C
OMPATIBILITY
The current SE-601 has been enhanced with the
addition of non-volatile trip memory for the fail-safe
relay operating mode. Prior to hardware revision 01, a
mechanical flag was used instead of non-volatile
memory. The current revision of the SE-601 can directly
replace previous revision-00 units. The hardware-
revision number is listed on the SE-601 model/serial-
number label affixed to the SE-601 enclosure. Both
generations are compared in Table 2.
TABLE 2. T
RIP-
F
EATURES
C
OMPARISON
H
ARDWARE
R
EVISION
00
01
LED trip indication
Yes
Yes
Mechanical flag trip indication
Yes
No
Non-volatile trip memory
No
Yes
Device state after supply voltage cycled
when tripped (ground-fault removed)
Fail-safe
Trip LED: Off
Trip relay: Energized
Trip flag: Red
Trip LED: On
Trip relay: De-energized
Non-fail-safe
Trip LED: Off
Trip relay: De-energized
Trip flag: Red
Trip LED: Off
Trip relay: De-energized