When the LED driver power is less than the emergency power (40W)

BEFORE BEGINNING INSTALLATION, TURN OFF POWER AT THE CIRCUIT BREAKER.

1. 

Choose a location for the Emergency Battery Backup unit. The indicator light/ test switch should 

be mounted where they can be easily seen by inspectors. 

2. 

The input voltage to the dimmable wires (DIM+, DIM-) of the EB40 must be less than 20Vdc.

3. 

Once mounted, select the appropriate wiring diagram to connect the EB40 to the AC driver. Use 

wirenuts to cap unused wires and make sure all connections are in accordance with the NEC and 

any local regulations.

4. 

Restore power to the fixture. When power is received, the red indicator light should appear, 

indicating that the unit is charging. An initial full charge could take up to 24 hours. 

INSTALLATION 

 

WIRING DIAGRAMS

 

Emergency

 

LED

 

Driver

 

EMAXXFY Series

Rev

:

V02

pg2

A: For 30 seconds/Off

B: For 90 minutes

In AC operation, press test switch or “A” on remote test switch, the fixtures will switch into emergency model 

for 30 seconds.
In AC operation, press “B” on remote test switch, the fixtures will switch into emergency model for 90 minutes. 
In emergency operation, 30 senconds later, press “A” on remote test switch 10 seconds later, the fixtures will 

switch into AC model. 
The antenna shall be extended before test, the remote signal could reach about 12M. 

 

 *When the led driver power less than the emergency power

Wiring Diagram

A)Normal

USE WIRE NUTS TO COVER 

UNUSED WIRES

WHITE

AC

-

N

AC

-

N

AC

-

L

AC

-

L

BLACK

BLACK/WHITE

ORANGE

PINK

CHARGE

 

INDICATOR

CHARGE

 

INDICATOR-

TEST

 

SWITCH

KIT

BROWN

BLUE

DRIVER N

DRIVER L

PURPLE

GRA

Y

YELLOW

RED

CHARGING

 

INDICATOR

 

         

TEST

 

SWTCH

Driver L 

Driver N

Сharging

Indicator

Сharging

Indicator-

Test Switch

Wall Switch

Connect to

Connect to

Connect to

Connect to

Connect to

Connect to

Connect to

Connect to

LED

 

LAMP

 

with

 

internal

 

driver

LED

 

TUBE

No connect

WALL

 

SWITCH

GR

AY(-)

PINK(-)

)

Содержание EB40

Страница 1: ...g Code EB40 WHAT COMES IN THE BOX 1 EB40 unit 1 Installation instructions 1 Charging indicator test switch with 2 screws 1 Test switch cover 2 Waterproof nuts 1 Remote control 11 Wire nuts TOOLS NEEDED Wire stripper Wire cutter Phillips screwdriver Step ladder ...

Страница 2: ... Lighting emergency backup Use with grounded UL ETL listed dry or damp location rated fixtures CAUTION The EB40 provides more than one power supply output source To reduce the risk of electrical shock disconnect both normal and emergency source by turning off the A C branch circuit CAUTION Servicing of this equipment should be performed by qualified personnel only CAUTION Do not attempt to service...

Страница 3: ...press test button B once in 2 seconds timespan to conduct a 90 minute full discharge test During emergency operation press the test switch once to shut off the unit Range With the antenna extended the range will be up to 40 AUTOMATIC SELF TESTING The EB40 includes a self testing function which will perform a 30 second discharge test once a month and a full discharge test one a year At this time th...

Страница 4: ...0 seconds Off B For 90 minutes In AC operation press test switch or A on remote test switch the fixtures will switch into emergency model for 30 seconds In AC operation press B on remote test switch the fixtures will switch into emergency model for 90 minutes In emergency operation 30 senconds later press A on remote test switch 10 seconds later the fixtures will switch into AC model The antenna shall...

Страница 5: ...arging Indicator Сharging Indicator Test Switch DIM DIM Dimmer DIM Driver Wall Switch Connect to Connect to Connect to Connect to Connect to Connect to Connect to Connect to Connect to Connect to Connect to C Without Dimmer USE WIRE NUTS TO COVER UNUSED WIRES W H IT E AC N AC N AC L AC L B L A C K BLACK WHITE ORANGE PINK CHARGE INDICATOR CHARGE INDICATOR TEST SWITCH KIT B R O W N B L U E DRIVER N ...

Страница 6: ...ol monitor circuit which will perform a 30 second discharge test once a month and a discharge test once a year At this time the unit simulate an AC power failure and automatically switch to emergency mode During routine testing the unit will monitor the operation of the LED load battery voltage and emergency duration if the unit detect any problems the indicator will flash quickly emergency LED dri...

Страница 7: ...s Location Rated Must be remote mounted The EB40 is compatible with all LED fixtures using less than 300W All fixtures must also include 0 10V dimming UL924 STATEMENT OF COMPLIANCE AND COMPATIBILITY PLEASE NOTE When used with a sensor equipped fixture from the Approved List of Litetronics fixtures below the sensor will be bypassed and disabled by the EB40 when wired correctly per the installation ...

Страница 8: ... without incurring liability If you have questions regarding specific product details please contact us at 800 860 3392 or via email at customerservice litetronics com To check for an updated version of these instructions please visit www litetronics com www Litetronics com CustomerService Litetronics com or 1 800 860 3392 6969 W 73rd Street Bedford Park IL 60638 Thank you for choosing 11 2 22 V2 ...

Отзывы: