3
EB40 OPERATING INSTRUCTIONS
• Litetronics Emergency Battery Backup unit (EB40) delivers 90-minutes of power to fixtures in
the event of a power outage.
• Once installed and receiving power, the unit will charge fully and remain in stand-by mode,
and the indicator light will remain on.
INDICATOR LIGHT
• In AC operation, the indicator light will remain on/solid
• In emergency operation, the light will flash slowly (on for 2 seconds,
off for 2 seconds)
• If a failure were to occur, the light will flash quickly (on for 0.2 seconds,
off for 0.2 seconds)
• The Indicator Light / Test Switch may be mounted on a switch box near the
fixture. Although easy accessibility is not required, it must be visible to
occupants.
• The Red Button/Indicator Light is required via Class 2 wiring to enable full
functionality of the EB40.
TEST SWITCH
• In AC operation, press the test button once to conduct a 30 second emergency test
• In AC operation, press the test button twice (in 2 seconds timespan)
to conduct a 90-minute full discharge test.
• During emergency operation, press the test switch once to shut off the unit
REMOTE TEST SWITCH
• In AC operation, press test button A once to conduct a 30 second
emergency test
• In AC operation, press test button B once (in 2 seconds timespan)
to conduct a 90-minute full discharge test.
• During emergency operation, press the test switch once to shut off the unit
• Range - With the antenna extended, the range will be up to 40’.
AUTOMATIC SELF-TESTING
• The EB40 includes a self-testing function, which will perform a 30-second discharge test once
a month and a full discharge test one a year. At this time, the unit will simulate an AC power
failure and automatically switch to emergency mode. During routine testing, the unit will
monitor the operation of the LED load, battery voltage, an emergency duration. If the unit
detects any problems, the indicator light will flash quickly.
MAINTENANCE
Although no routine maintenance is required to keep the emergency battery backup functional,
it should be checked periodically to ensure that it is working. The following schedule is recom-
mended:
• Visually inspect the charge indicator light monthly. It should be illuminated.
• Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds.
• Conduct a 90-minute discharge test once a year. LED fixture should operate at up to 40W for
at least 90 minutes.
SERVICE
Should be performed as indicated above by qualified personnel.
A
B
30
SECONDS
90
MINUTES
Operation Manual for Remote Test Switch
Pictures:
Size:
92
M
M
40MM
antenna
test button A
test button B
1,Remote Test Switch: Signal distance 33 Ft
Features:
2,One test switch could control as many as EM pack,
as long as they are within the range of 33 feet.