Follow the instructions below to remove the jumper if an even lower current leakage to a
even lower level.
Removing the jumper may increase the signal interference.
1. Front right corner of the machine, remove the screw using a screwdriver.
2. Remove the top right corner of the right side of the ground blade screw and save.
4.2.3 Main Circuit Cable Size and Tightening Torque
Select the cables and crimp terminals according to Table 4.2.2.
1. The recommended cables(
copper conductors
) are 600 V vinyl-sheathed cables which has
continuous temperature tolerance up to 75°C with ambient temperature tolerance up to 40 °C
and wiring distance up to 100 meters.