22
and W respectively. Ensure the motor and drive terminals are in same phase sequence or
the motor will rotate reversely.
Do not connect power cable to output terminals of the drive. Failure to comply could
cause drive damage and a fire.
4.2.2.3 Braking Unit Terminal:
If the drive is used in a high-frequency or heavy duty application which requires frequent
braking or shorter deceleration time, install an optional braking unit to increase the
braking torque.
+
-
Braking Unit
(option)
Please refer to the wiring diagram when installing braking unit.
4.2.2.4 Ground Terminal
Use grounding cables of dimensions regulated by electrical equipment standard. Shrink
wiring distance to prevent leakage current resulting unstable electrical potential at the
terminal distant from grounding terminal.
Do not use share the same grounding cable with welding machines or any device
requiring large current. Failure to comply could cause drive or equipment malfunction.
Do not wind the grounding cable when multiple drives are installed. Failure to comply
could cause drive or equipment malfunction.
Ensure the neutral of the input side and drive terminal "
“ are grounded according to
the local electrician regulations.
3WYE (e.g. TN and TT)
system are suggested for the drive
primary side.
4.2.2.5 Jumper
EVO6000 complies with the European LVD standard EN 61800-5-1 (2007) reducing the
current leakage to below 10mA DC under testing condition regulated by IEC 60990
(1999).