Signal
Control
Manual
signal.
Control
the
window
by
the
buttons
on
itself,
external
dry
contact
manual
switch
and
RF
remote
Cascaded
signal.
As
a
master
controller
sends
signal
to
the
slave
controller,
can
also
be
used
as
slave
controller
to
receive
the
signal
from
the
master
controller
to
drive
the
window
Fire
signal.
Capable
of
receiving
a
signal
from
fire
center,
smoke
sensor,
gas
detector
open
the
window
automatically
Wind/Rain
signal.
After
receiving
the
signal
of
wind/rain
sensor
close
the
window
Temperature/humidity
signal.
Control
the
window
by
processing
external
temperature/humidity
sensor
Time
signal.
Control
the
window
by
working
with
external
timer
Signal
and
Priority
Signal
Manual
Signal
Fire
Signal
W/R
Signal
Time
Signal
T/H
Signal
Priority
1
2
3
4
5
Manual
signal
includes
the
signal
from
buttons
on
the
controller,
external
dry
contact
manual
switch,
wall
transmitter,
hand
held
remote,
wireless
W/R
sensor,
wireless
timer
and
cascaded
signal
Fire
signal
includes
the
signal
from
fire
centre,
smoke
sensor
and
gas
detector
W/R
signal
includes
the
signal
from
wired
wind
and
rain
sensor,
NOT
including
wireless
W/R
sensor
Time
signal
is
only
the
signal
from
WIRED
timer
T/H
signal
includes
the
signal
from
temperature
or
humidity
sensor
Reset
and
Shielding
After
manual
signal
processed
controller
resets
&
receives
input
signal
in
real
time
After
processing
the
signal
from
fire
centre,
smoke
sensor
or
gas
detector,
the
controller
immediately
shields
all
the
input
signals,
the
controller
must
be
reset
by
pressing
K1
manually.
After
wired
W/R
sensor
signal
processed,
the
controller
shields
lower
priority
signal,
only
receives
the
higher
priority
signal
until
reset
or
manual
signal
processed
After
wired
timer
signal
processed,
the
controller
shields
lower
priority
signal,
only
receives
the
higher
priority
signal
until
reset
or
manual
signal
processed
After
T&H
sensor
signal
processed
,
the
controller
is
in
the
reset
state
Option
switch
on
the
control
board
is
for
selection
of
shielding
priority
3
‐
5
signal
Option
1
‐
3
priorities
3
‐
5
respectively.
The
setting
takes
effect
after
reset
or
restart
Switch
Option
Function
Y
Wind/Rain
sensor
shielded
Option1
N
Not
shield
Wind/Rain
sensor
Y
T&H
sensor
shielded
Option2
N
Not
shield
T&H
sensor
Y
Timer
shielded
Option3
N
Not
shield
Timer
Cascaded
Control
LK
‐
CP711
/
722
/
744
can
be
used
as
a
master
controller,
a
slave
controller
or
play
a
dual
role
of
master
&
slave
controller
at
the
same
time.
LK
‐
CP721S
/
731S
/
741S
/742S
can
only
be
a
slave
controller
As
a
master
controller,
connects
to
the
motors
or
slave
controllers
to
drive
them
As
a
slave
controller,
input
terminals
S+
and
S
‐
are
connected
to
the
output
terminals
M+
and
M
‐
of
the
master
controller
to
receive
the
instructions
to
drive
motors,
or
drive
the
motors
independently
Play
a
dual
role
of
master
&
slave
controller,
not
only
controlled
by
higher
‐
level
controller,
but
also
drive
motors
or
lower
‐
level
controllers
independently
No
matter
master,
slave
or
both,
it
can
process
all
the
external
signals
such
as
manual
switch,
remote
and
sensors