RULES FOR MAKING ELECTRICAL CONNECTIONS
Installation of this equipment must be done by personnel qualified.
Reverse polarity cause immediate and irreversible damage to the rescuer. The damage due to reverse polarity are
not in any case covered by the warranty of the Linergy
Use tools with the 'insulated handle.
1. Open the terminal cover positioned on the rear PANEL of the rescuer.
We recommend using cable with 4 mm².
The inputs MUST BE PROTECTED BY CIRCUIT BREAKER.
Before making connections open all the thermal magnetic breakers.
2. Make the ground connections to the terminals marked by the conventional symbol.
3. Perform the connection of the output line to the terminals marked OUTPUT, respecting the directions of phase (L) and
NEUTRAL (N).
4.
Ensure the cables firmly to the terminals.
4.
The CPS permanently connected to the mains are equipped with a single emergency stop command (ESD = Emergency
Switching Device or EPO = Emergency Power Off) embedded UPS or terminal for connection to an external device that allows l
' remote shutdown of the load and the supply of CPS energy in any operating state.
5. Optional: Perform the connection of 'remote off switch to the contact marked by
EPO (Emergency Power Off).
5. Optional: Perform the connection of 'remote off switch to the contact marked by
The EPO contact is normally closed. The rescuer turns off all 'opening of the contact.
.The rescuer is provided with the contact EPO bridged.
1 3