background image

HSLG OPERATOR INSTALLATION GUIDE

- 11 -

CURRENT SENSING ADJUSTMENTS

Because gates vary in construction and may have different force requirements in the open and close directions to move, the 
LINEAR control board has separate Multi-turn potentiometers for adjusting in both directions independently. The adjustment 
should be set light enough to maintain minimal force (50-75 lbs.) should an obstruction occur, but high enough to keep the 
gate moving under normal conditions without interruption.

Prior to adjusting the operator current sensing functions, make sure the gate moves freely in both directions. A badly aligned 
or poorly maintained gate may cause false triggering of the current sensor. Refer to page 

9

 when following the instructions 

below. A factory adjustment tool has been supplied to make these adjustments easier. This tool has been taped to the control 
box for your convenience.

CLOSE DIRECTION CURRENT SENSE ADJUSTMENT

When the gate operator leaves the factory, it has been preset for a relatively light gate function and will require additional 
adjustment. Begin by starting the gate going closed. If the operator stops and reverses, turn the close direction potentiometer 
(see page 

9

) one turn higher, press the 

STOP

 button, and try again. Repeat this process until the gate no longer causes 

false tripping of the current sensor. Note that each time the gate operator reverses, the 

STOP

 button must be pressed. Next, 

turn the close direction potentiometer lower slowly while the operator is running the gate closed until the gate operator stops 
and reverses again. From this point, turn the close direction potentiometer higher by 1 1/2 turns for all 115 Volt AC and 24 
Volt DC operators, and by 3/4 of a turn higher for all 230 Volt AC operators. Additional fi ne adjustment by 1/4 turns may be 
necessary to eliminate false triggering.

OPEN DIRECTION CURRENT SENSE ADJUSTMENT

Repeat the same process with the open direction potentiometer while running the gate in the open direction. Once this is 
done, run the gate through several complete cycles and make sure the gate does not false trip in either direction.

MAXIMUM RUN TIMER ADJUSTMENT

This adjustable potentiometer sets the maximum length of time the motor will run before shutting down. It should be confi gured 
for the time it takes to run the gate fully open or closed, plus an additional 15 seconds. See page 

9

 for details.

Multi-turn Potentiometer

Remember it is important not to set the adjustment 
too high! Doing so will defeat the purpose of the cur-
rent sensing as an obstruction detecting feature.

MASTER/SLAVE CONNECTION

A three-wire shielded conductor cable is required to connect master and slave operators. You must use Belden 8760 Twisted 
Pair Shielded Cable (or equivalent) 

only

 – LINEAR part number 2500-1982, per foot). See page 

9

 for details of this connec-

tion, as well as dip switch selection.

 

Note: The SHIELD wire should be connected in both the master and slave operators.

 In addition, 

you must run power to both the master and slave operators.

AUTO CLOSE TIMER ADJUSTMENT

This adjustable potentiometer sets the length of time which elapses before the gate operator automatically closes the gate, 
from the fully open position, provided no open, reversing, or obstruction signals are present. This feature can be turned on 
or off via dip switch selection. See page 

9

 for details. 

Do not use the auto close timer without an appropriate reversing 

device installed!

Содержание HSLG

Страница 1: ...325 COMPLIANCE REQUIRES THE USE OF CONTACT EDGES OR PHOTOELECTRIC CONTROLS ON ALL AUTOMATIC OR REMOTELY CONTROLLED GATE OPERATORS USA Canada 800 421 1587 800 392 0123 760 438 7000 Toll Free FAX 800 46...

Страница 2: ...board L E D Indicator Descriptions 12 Important Notes for Installation of Master Slave Applications 13 Surge Protector Instructions 13 Control and Accessory Connection Illustrations 14 17 ILLUSTRATION...

Страница 3: ...ate does not seem to operate properly it may affect the operator performance or greatly shorten the life of the unit The gate should be designed so that airflow through the fabric is ample to prevent...

Страница 4: ...e 9 for details of this connection as well as dip switch selection Note The SHIELD wire should be connected in both the master and slave operators MODEL HSLG SINGLE PHASE g n i r i W r e w o P s t l o...

Страница 5: ...tes which should be mounted on the outside top and bottom of the cabinet two 3 16 side plates which go on the top inside and two 1 2 side plates which should be mounted on the inside top of the cabine...

Страница 6: ...dler over the drive sprocket and then under the last idler Make sure you feed most of the chain through the sprockets for attaching to the back end of the gate Assemble the other gate bracket on the r...

Страница 7: ...and must be adjusted during installation Adjust the torque limiter tight enough to keep it from slipping during normal operation To adjust the torque limiter in model HSLG 1 Loosen the jam nut 2 To i...

Страница 8: ...perator after the limit switch is tripped Once the gate is in this position adjust the open limit nut until it activates the limit switch for open LSO 1 Press down on the detent plate and rotate the n...

Страница 9: ...nection Block This terminal block is used in conjunction with two operators to configure two gates to open and close together Dip Switches 1 This switch turns the auto close timer off on 2 This switch...

Страница 10: ...in prior to reaching a limit the gate will stop again and this time will sound the emergency alarm and lock out 4 51 CLOSE This function works exactly like the OPEN OBSTRUCTION except that it will onl...

Страница 11: ...tentiometer higher by 1 1 2 turns for all 115 Volt AC and 24 Volt DC operators and by 3 4 of a turn higher for all 230 Volt AC operators Additional fine adjustment by 1 4 turns may be necessary to eli...

Страница 12: ...or wired to the safety loop terminals SHADOW LOOP This indicator is lit when a shadow hold open signal is present This signal is generated by a loop detector wired to the shadow loop terminals This in...

Страница 13: ...d Lock Release Three Second Pre Start Warning Right Left Hand Selections SURGE PROTECTOR INSTRUCTIONS The optional surge protector should be connected to any inputs that have an accessory connected to...

Страница 14: ...HSLG OPERATOR INSTALLATION GUIDE 14 CONTROL and ACCESSORY CONNECTION ILLUSTRATIONS...

Страница 15: ...HSLG OPERATOR INSTALLATION GUIDE 15 CONTROL and ACCESSORY CONNECTION ILLUSTRATIONS...

Страница 16: ...HSLG OPERATOR INSTALLATION GUIDE 16 CONTROL and ACCESSORY CONNECTION ILLUSTRATIONS...

Страница 17: ...HSLG OPERATOR INSTALLATION GUIDE 17 CONTROL and ACCESSORY CONNECTION ILLUSTRATIONS...

Страница 18: ...HSLG OPERATOR INSTALLATION GUIDE 18 LOOP LAYOUT ILLUSTRATION Refer to Connection Descriptions on page 10 and Loop Accessory Connections on page 17 for details...

Страница 19: ...HSLG OPERATOR INSTALLATION GUIDE 19 EDGE LAYOUT ILLUSTRATION 1 Refer to Connection Descriptions on page 10 and Contact Edge Connections on page 16 for details...

Страница 20: ...HSLG OPERATOR INSTALLATION GUIDE 20 EDGE LAYOUT ILLUSTRATION 2 Refer to Connection Descriptions on page 10 and Contact Edge Connections on page 16 for details...

Страница 21: ...HSLG OPERATOR INSTALLATION GUIDE 21 PHOTO EYE ILLUSTRATION Refer to Connection Descriptions on page 10 and Photo Eye Connections on page 16 for details...

Страница 22: ...HSLG OPERATOR INSTALLATION GUIDE 22 PICKET GATE ILLUSTRATION Refer to Connection Descriptions on page 10 and Accessory Connections on pages 14 17 for additional details...

Страница 23: ...HSLG OPERATOR INSTALLATION GUIDE 23 TRACK GATE ILLUSTRATION...

Страница 24: ...pen or closed but no visible obstruction A The control board may have received a false obstruction input triggered by current sensing set too low Make sure the gate moves freely through its entire tra...

Страница 25: ...HSLG OPERATOR INSTALLATION GUIDE 25 MODEL HSLG MECHANICAL PARTS EXPLODED VIEW...

Страница 26: ...lf for Single Phase Models only REF NO PART NO DESCRIPTION Motors 95 2500 2307 1 2 HP 115V 1 Phase 2500 2308 1 2 HP 208 230V 1 Phase 2500 2309 3 4 HP 115V 1 Phase 2500 2310 3 4 HP 208 230V 1 Phase 250...

Страница 27: ...10 2510 249 Input Wire Harness Assembly 11 2510 250 Output Wire Harness Assembly 12 2510 261 Control Box Motor Harness Assembly 13 2500 071 Terminal Strip 16 141 14 2500 212 Transformer 115 24VAC 40VA...

Страница 28: ...Control Board only 10 2500 1980 3 Phase Motor Board 11 2500 1966 2 Amp Fuse for Control Board 12 2500 1975 3 Amp Fuse for Control Board 13 2510 253 Limit Switch Harness REF NO PART NO DESCRIPTION 14 2...

Страница 29: ...ace as necessary Check for proper tension and adjust if required Check all pulley setscrews for tightness and tighten if necessary 3 For operators with internal chain drives inspect chain and sprocket...

Страница 30: ...that these signs must remain at all times 8 Controls intended for user activation are located at least six feet 6 away from any mov ing part of the gate and where the user is prevented from reaching...

Отзывы: