23
SPECIFICATIONS
MECHANICAL
Case dimensions: 10” W x 6-1/8” H x 4” D
ELECTRICAL
Voltage: 16 Volts AC or 12-24 Volts DC
Current: 650 mA AC typical, 1300 mA AC maximum
Backup Battery: Externally charged 12-24 Volt DC source
Backup Battery Current: with 12-volt backup battery
250 mA standby
600 mA ringing one phone
1100 mA maximum
with 24-volt backup battery
200 mA standby
350 mA ringing one phone
600 mA maximum
Outputs:
Relay
#1
Form “C” 3 Amps @ 30 Volts maximum
Relay
#2
Form “C” 3 Amps @ 30 Volts maximum
Inputs: Two normally closed door sense/inhibit inputs
Two normally open request to exit inputs
RADIO
Frequency: 318 Mhz ± 500 KHz @ 23°C
RF 3db Bandwidth: 4 MHz Typical
Sensitivity: -97 dBm Minimum (-100 dBm Typical)
Encoding:
Linear
MegaCode® Format
ENVIRONMENTAL
Temperature: -22°F to 149°F (-30°C to 65°C)
Humidity: 5% to 95% non-condensing
DIMENSION DRAWING
HELP
CALL
6-1/
8
"
4"
10"
REAR CA
S
E MOUNTING HOLE
S
& WIRE ACCE
SS
2.75"
2.75"
.2
8
" DIA.
4 PLACE
S
1.75" DIA.
TROUBLESHOOTING
System will not go into programming mode
1. Wrong master code entered.
System completely dead
1. No power from transformer. Check voltage at RE-2 transformer
terminals.
2. Verify that terminal blocks are fi rmly plugged into circuit board.
Buzz on speaker
1. Check for 24 volt AC power shorted to wiring conduit.
2. Check for telephone line shorted to ground.
3. Verify that telephone wires are twisted pair.
4. Verify that the RE-2 and the Telephone Bypass Module are connected
to earth ground.
5. Check 16 VAC voltage at RE-2 transformer terminals.
Buzz on telephone line
1. Switch the Telephone Bypass Module to bypass. Connect line ring
and tip to house ring and tip. Check line for buzz with test set.
2. Disconnect 16 VAC wires from terminal strip, if buzz goes away, one
side of the transformer wires is grounded.
3. Check all connections for any shorts to ground.
Telephones in residence will not ring
1. Verify that the “Do Not Disturb” feature is not on while testing.
2. Verify that the Call Forwarding feature is not forwarding the calls at
the time.
3. Check 16 VAC voltage at RE-2 transformer terminals.
4. Disconnect the house telephone line and connect a test telephone to
the RE-2 house ring and tip terminals. See if the test telephone rings.
System will not answer an incoming call
1. Modem ring detect (PPN #33) disabled.
2. Calling pattern incorrect. Let telephone ring once, hang up, wait 10-30
seconds, then call again.
Call forwarding feature is not working
1. Incorrect phone number has been programmed (PPN #54)
✦
NOTE:
If you are programming the call forwarding feature as “on at all
times”, no programming entry is needed for the time zone (see example
in PPN #54).
Entry code will not activate relay
1. Entry code not set up for proper relay (PPN #2).
2. Time zone is active for the relay.
Remote keypad does not work
1. Remote keypad address is not enabled (PPN #28).
2. Remote keypad relay is not selected (PPN #23).
Main or remote keypad will not activate a relay
1. Keypad is not assigned to a relay (PPN #23).
2. Entry code is not assigned to correct relay (PPN #2).
Gate does not open/close at programmed time
1. Time was not entered as
local
time (PPN #20).
2. Auto Daylight Saving Time disabled in area that observes daylight
saving (PPN #46).
3. Automatic Door/Gate time zone is not properly programmed (PPN
#53).
Relay #1 will not latch from the keypad
1. Add an entry code with the relay programmed as a 4 (latch relay #1,
PPN #2).