8
/14
Installations within vertical rigid wall EI 60 S hole Ø+30
1. Positioning brackets
2. Screw Ø 3,5 X 35 mm or equivalent
3. Fire damper
4. Ventilation duct
5. Rock wool 35 kg/m³, or mortar or plaster putty
6. Fire stopping sealant (reference Soudal Firecryl or equivalent with
resistance and reaction to fire equal or higher) between refractory ring
and construction support
7. Fire stopping sealant (reference Soudal Firecryl or equivalent with
resistance and reaction to fire equal or higher) to cover the sealing
D Hole size: see table above
Installations within vertical rigid wall EI 60 S hole Ø+10
1. Positioning brackets
2. Screw Ø 3,5 X 35 mm or equivalent
3. Fire damper
4. Ventilation duct
5. Corner support (es. TS11/TS12 Lindab)
6. Fire stopping sealant (reference Soudal Firecryl or equivalent with
resistance and reaction to fire equal or higher) between refractory ring
and construction support
7. Self-drilling screw Ø3,5 X 25 mm
D Hole size: see table above
rev 20-12
8