background image

4

/14

Blade opening mode

Make sure that the damper is open before the ventilation system 

start-up, otherwise there is a risk of product malfunction.

To open the damper with the electric motor driven actuator, provi-

de power supply to the motor. Refer to the section Electrical con-

nections  for further information.

To manually open the damper, use the handle supplied and carefully 

rotate counterclockwise to the 90 °C indicator. To hold the damper 

in open position, rotate the screw anticlockwise as shown in the pi-

cture.

During the manual opening of the damper, power must not be sup-

plied to the motor.

Position indication microswitches

The motorized versions are supplied with two microswitches to 

show the blade's position (open or closed). Refer to the section 

Electrical connections  for further information.

Closing by remote control

If power to the motor is cut off, the blade will close.

Temperature calibration of thermosensitive element for auto-

matic damper closing

72 °C±7 °C (Standard)

95 °C±9 °C (On request).

ELEC TRICAL CONNEC TIONS

 

„

Electrical wiring

Electrical connections must be done by qualified and trained people.

Switch off the power supply before starting any work on the electric 

elements. Never switch on the power supply during electrical con-

nections.

 

†

Motorized version

Belimo servomotor:

BFL24T, BFL230T

Siemens servomotor:

GRA126

Siemens servomotor:

GRA326

Motorized fire dampers electical wiring

To connect the dampers to the power supply, proceed as follows:

•  Check that the voltage and electrical frequency are equivalent to 

those of the motor of the servomotor (check the motor's informa-

tion label);

•  Make the connections as shown in the below diagram.

Electrical wiring for motorized version

24V AC/DC power supply

 /-  Negative (DC) or neutral (AC) black wire

~/+ Positive (DC) or phase (AC) red wire

230V AC power supply

N  Neutral blue wire

L  Phase brown wire

Microswitches position contacts

S1  Common closed damper microswitch

S2  Normally closed, closed damper microswitch

S3  Normally opened, closed damper microswitch

S4  Common open damper microswitch

S5  Normally closed, open damper microswitch

S6  Normally opened, open damper microswitch

rev 20-12

4

We reserve the right to make changes without prior notice

Содержание FNC1

Страница 1: ...p3 italia it 1MUBFNC1EN rev 20 12 1MUBFNC1EN FNC1 FNC1 l indab we simplify co nstruc tio n www lindab com Fire dampers are manufactured by MP3 Srl www mp3 italia it 1MUBFNC1EN LIND rev 20 12 1MUBFNC1E...

Страница 2: ...tuds made of steel or timber Acrilic sealant sealing ve i o D min 100 max 400 min 100 max 400 Floor EI 60 S 300 Pa EI 30 S 300 Pa Installation within floor Floor minimum thickness 100 mm Floor minimum...

Страница 3: ...2 C or 95 C for the 95 C version To close the damper when the motor is connected press the switch on the temperature sensor or cut off the power supply Blade opening mode Make sure that the damper is...

Страница 4: ...uest ELECTRICAL CONNECTIONS Electrical wiring Electrical connections must be done by qualified and trained people Switch off the power supply before starting any work on the electric elements Never sw...

Страница 5: ...Check the servomotor electrical wiring for damage where appli cable Check end switch wiring for damage where applicable Check damper cleanliness and clean where necessary Check the condition of blades...

Страница 6: ...The test results obtained on a type of wall floor are valid also for wal ls floor of the same type but with greater thickness and or density than those used in the test For plasterboard walls the tes...

Страница 7: ...be provided in the wall as indicated in the table and in the drawing Damper positioning Position the damper in the opening so that the side of the closing mechanism extends as indicated in the drawing...

Страница 8: ...Firecryl or equivalent with resistance and reaction to fire equal or higher to cover the sealing D Hole size see table above Installations within vertical rigid wall EI 60 S hole 10 1 Positioning brac...

Страница 9: ...ion duct 5 Rock wool 35 kg m or mortar or plaster putty 6 Fire stopping sealant reference Soudal Firecryl or equivalent with resistance and reaction to fire equal or higher between refractory ring and...

Страница 10: ...in the drawing For distance between fire damper and wall less than or equal to 1m only one support is enough as indicated in the drawing The support at 20 mm from the fire damper is always mandatory...

Страница 11: ...her to cover the sealing D Hole size see table above a 1000mm MAX n of threaded rods depending on the length of the duct use 1 threaded bar for a 1000 mm EI 60 S Installation remote from the vertical...

Страница 12: ...ed in the drawing Fire resistance classification D hole size mm Wall minimum thickness S mm Sealing EI 60 S Installation remote from the vertical light wall Wall resistance class EI 60 EI 60 S 300 Pa...

Страница 13: ...fire equal or higher between insulation and construction support 8 Self drilling screw 4 2 X 13 mm x4 9 Insulation rock wool Pro Wired Mat 80 AL 1 Paroc or equivalent see Installation remote from ver...

Страница 14: ...ess 70 mm or equi valent A metallic mesh is installed around the rock wool The junctions between the insulation and the damper are made by an acrylic fire stopping sealant es Soudal Firecryl or equiva...

Отзывы: