background image

6

/14

 

„

Installation of flexible connectors in order to balance out the 

ventilation ducts expansion

ATTENTION: the following indications must be considered 

binding only if legislation or local regulation where the fire 

dampers are installed require the use of flexible connectors.

Flexible connectors compensate any duct thermal expansion and 

wall bending in case of fire.

Flexible connectors are used to limit fire damper stresses due to ex-

ternal forces in case of fire and to preserve fire resistance class.

In general it is always appropriate the use of flexible connectors for 

the followings installations:

– light walls;

– Plasterboard and rock wool or Fire Batt (Weichschott) sealing;

– Applique fixing system.

Flexible connector must be normal flammability and in case of fire 

the grounding bonding should disconnet to guarantee the comple-

te separation between fire damper and connected air duct.

When flexible connectors made of conductive material (e.g. alumi-

num) are used, no additional grounding bonding is required.

Despite flexible connector installation, the fire damper must be in-

stalled in the construction support so that its weight does not affect 

damper’s installation position both during normal operation and in 

case of fire.

It is recommended not to compress flexible connectors in the in-

stallation phase.

Flexible connector must be at least 100mm long and in order that 

possible duct thermal expansions are balanced. 

Take care that the flexible connector does not interfere with opening 

/ closing movement of the blade.

Refer to the section Technical data  for blade exposition values.

 

„

Minimum distances

It is recommended to keep enough space (about 200mm) for using 

or replacing the control mechanism or for maintenance. Also provide 

the necessary space to remove the ventilation duct from the damper 

whenever necessary.

In accordance with Articles 7 and 13 of EN 1366-2 respect the mini-

mum distances indicated below.

1.  Vertical lateral wall

2.  Floor

 

†

Minimum distances for remote installation from vertical wall/floor

1.  Side wall/ floor

2.  Construction supports (floor/ wall)

 

„

Construction supports characteristics

The European standard for fire dampers foresees a precise correlation 

between the wall/floor characteristics and the fire resistance class 

obtained, as well as the correlation between wall/floor used for the 

test and wall/floor used for the actual installation.

The test results obtained on a type of wall/floor are valid also for wal-

ls/floor of the same type but with greater thickness and/or density 

than those used in the test.

For plasterboard walls, the test results are also valid for walls with a 

greater number of plasterboard layers on each side.

As a result, the indicated thickness and density characteristics are to 

be considered as minimum values.

The wall/floor in which the fire dampers are installed must be fire 

resistance classified according to the standards foreseen for the 

structure.

 

†

Rigid walls

Can be made with aerated concrete blocks, poured concrete, concre-

te panels, perforated cell elements in concrete or brick in accordance 

with the following characteristics:

•  minimum thickness 95 mm;

•  Wall minimum resistance class EI 60.

The use of a reinforcing beam above the opening is recommended 

for walls made from concrete blocks, bricks or in concrete cell ele-

ments.

For walls built with perforated elements, it is also recommended that 

the area of the opening be made from full elements (for example 

aerated concrete blocks) to guarantee the correct adhesion of the 

mortar.

1.  Reinforcing beam

 

†

Light plasterboard vertical walls

During testing, light plasterboard walls have been used with the fol-

lowing characteristics:

•  U-shaped horizontal metal frame 45mm and C-shaped vertical 

frame 44mm made from 0,6 mm thick metal sheet, or timber 

45x45mm;

•  vertical profiles placed with a maximum spacing of 1000 mm;

•  Filling made of rock wool with density up to 35 kg/m³ (optional);

•  Each side is made from two plasterboard layers 12,5 mm thick, una-

linged to avoid alignment between the joints of the layer above 

and below.

The following indications are given for the installation walls:

•  metal profiles minimum width: 44 mm;

•  metal profiles minimum thickness: 0,6 mm, or timber studs mini-

mum section 45 x 45mm;

•  vertical profiles placed with a maximum spacing of 1000 mm 

between each other;

•  vertical profile fixing with selfthreading screws or by clinching to 

the bottom horizontal profile and insertion in the top horizontal 

profile;

•  profiles fixed using self-threading screws or by clinching on every 

intersection.

•  Filling made of rock wool with density up to 35 kg/m³ (optional);

•  each side is made from two plasterboard layers 12,5 mm minu-

mum thick, unalinged to avoid alignment between the joints of 

the layer above and below.

•  the front plasterboards layers are fixed using long enough screws 

to pass through the lower plasterboard and attach to the steel pro-

file underneath.

rev 20-12

6

We reserve the right to make changes without prior notice

Содержание FNC1

Страница 1: ...p3 italia it 1MUBFNC1EN rev 20 12 1MUBFNC1EN FNC1 FNC1 l indab we simplify co nstruc tio n www lindab com Fire dampers are manufactured by MP3 Srl www mp3 italia it 1MUBFNC1EN LIND rev 20 12 1MUBFNC1E...

Страница 2: ...tuds made of steel or timber Acrilic sealant sealing ve i o D min 100 max 400 min 100 max 400 Floor EI 60 S 300 Pa EI 30 S 300 Pa Installation within floor Floor minimum thickness 100 mm Floor minimum...

Страница 3: ...2 C or 95 C for the 95 C version To close the damper when the motor is connected press the switch on the temperature sensor or cut off the power supply Blade opening mode Make sure that the damper is...

Страница 4: ...uest ELECTRICAL CONNECTIONS Electrical wiring Electrical connections must be done by qualified and trained people Switch off the power supply before starting any work on the electric elements Never sw...

Страница 5: ...Check the servomotor electrical wiring for damage where appli cable Check end switch wiring for damage where applicable Check damper cleanliness and clean where necessary Check the condition of blades...

Страница 6: ...The test results obtained on a type of wall floor are valid also for wal ls floor of the same type but with greater thickness and or density than those used in the test For plasterboard walls the tes...

Страница 7: ...be provided in the wall as indicated in the table and in the drawing Damper positioning Position the damper in the opening so that the side of the closing mechanism extends as indicated in the drawing...

Страница 8: ...Firecryl or equivalent with resistance and reaction to fire equal or higher to cover the sealing D Hole size see table above Installations within vertical rigid wall EI 60 S hole 10 1 Positioning brac...

Страница 9: ...ion duct 5 Rock wool 35 kg m or mortar or plaster putty 6 Fire stopping sealant reference Soudal Firecryl or equivalent with resistance and reaction to fire equal or higher between refractory ring and...

Страница 10: ...in the drawing For distance between fire damper and wall less than or equal to 1m only one support is enough as indicated in the drawing The support at 20 mm from the fire damper is always mandatory...

Страница 11: ...her to cover the sealing D Hole size see table above a 1000mm MAX n of threaded rods depending on the length of the duct use 1 threaded bar for a 1000 mm EI 60 S Installation remote from the vertical...

Страница 12: ...ed in the drawing Fire resistance classification D hole size mm Wall minimum thickness S mm Sealing EI 60 S Installation remote from the vertical light wall Wall resistance class EI 60 EI 60 S 300 Pa...

Страница 13: ...fire equal or higher between insulation and construction support 8 Self drilling screw 4 2 X 13 mm x4 9 Insulation rock wool Pro Wired Mat 80 AL 1 Paroc or equivalent see Installation remote from ver...

Страница 14: ...ess 70 mm or equi valent A metallic mesh is installed around the rock wool The junctions between the insulation and the damper are made by an acrylic fire stopping sealant es Soudal Firecryl or equiva...

Отзывы: