ovER vIEw
FBC
1 - 4 - 7
6
/34
rev 20-02
EI 120 S
(300 Pa)
EI 90 S
(300 Pa)
EI 60 S
(300 Pa)
EI 30 S
(300 Pa)
Floor
Installation within floor with Fire Batt (Weichschott) sealing
Floor minimum thickness 150 mm
Floor minimum density 550 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ho (i
↔
o)
W
FBC7
FBC7
FBC4
FBC7
FBC4
FBC1
FBC7
FBC4
FBC1
Floor minimum thickness 100 mm
Floor minimum density 550 kg/m³
Rock wool 140 kg/m³ and endothermic varnish sealing
ho (i
↔
o)
W
-
FBC7
FBC4
FBC7
FBC4
FBC1
FBC7
FBC4
FBC1
W
Wet method sealing
D
Dry method sealing
ve
Vertical installation
ho
Horizontal installation
(i
↔
o) Origin of fire irrelevant
Pa
Pascal of depression
E Integrity
I
Thermal insulation
S
Smoke seal
Cert. N° FBC1 1812-CPR-1630,FBC4 1812-CPR-1632,FBC7 1812-CPR-1634