InSTALLATIon
FBC
1 - 4 - 7
20
/34
rev 20-02
Installations within floor
Refer to the section Construction supports characteristics
for further information.
Comply with the minimum distances indicated on section
Minimum distances .
Floor opening
A opening must be provided in the floor as indicated in
the drawing.
Damper positioning
Install the fire damper in the ventilation duct as shown in
the drawing.
Filling
Fill the space between ventilation duct and wall as indicat-
ed in the drawing.
Insulation
Apply the mineral fiber gaskets supplied with the damper
at a distance of 15 mm from the seal.
Fire damper model FBC1, FBC4, FBC7
1.
Mineral fiber gasket (supplied with the damper)
2.
Fire damper
3.
Mortar
4.
Ventilation duct
5.
Floor, minimum density 550 kg/m³
D
From nominal diameter min + 0 to nominal diameter max + 70
S
= min 100 mm for FBC1, FBC4
= min 150 mm for FBC7
L
= 45 mm for FBC1, FBC4
= 70 mm for FBC7
FBC
1 - 4 - 7
20
We reserve the right to make changes without prior notice