4.0 Product and system specification
4.1 Material data
Architect Luna, Prisma, Circum
Dry weight, [kg/m]
11
Water content, cooling, [l/m]
0.50
Water content, heating, [l/m]
0.25
Copper pipes, quality
SS/EN 12449
Pressure class
PN10
4.2 Environmental declaration
Please follow the links below
•
•
•
4.3 Pressure class
– The waterborne products in Lindab, active chilled beams (battery products), passive
chilled beams (battery and strips products), façade units (battery) and radiant panels
(strips and panels) are produced according to pressure class PN 10 according to EN
1333: 2006.
– This means the maximal working pressure for the products at a water temperature of
20°C must not exceed 10 bar.