RANGER 8+ DIESEL
A-6
INSTALLATION
A-6
AUXILIARY POWER RECEPTACLES,
PLUGS, AND HAND-HELD EQUIPMENT
The control panel of the RANGER 8+ DIESEL fea-
tures three auxiliary power receptacles: See Figure
B.1.
• Two 15 amp, 115 volt duplex (double outlet) recepta-
cles.
• One 50 amp 115/230 volt simplex (single outlet)
receptacle.
Through these receptacles the machine can supply up
to 9,000 rated continuous watts of single-phase, 60
Hz AC power.
For further protection against electric shock, any elec-
trical equipment connected to the generator recepta-
cles must use a three-blade, grounded type plug or an
Underwriter’s Laboratories (UL) approved double
insulation system with a two-blade plug. Lincoln
offers an accessory plug kit that has the right type of
plugs. See the ACCESSORIES section of this manual
for more information.
CIRCUIT BREAKERS
The RANGER 8+ DIESEL machines are equipped
with 50 amp circuit breakers on the 115/230 V recep-
tacle and 15 amp circuit breakers on the 115 recepta-
cles for overload protection. Under high heat a break-
er may tend to trip at lower loads than it would normal-
ly.
Never bypass the circuit breakers. Without overload
protection, the RANGER 8+ DIESEL could overheat
and/or cause damage to the equipment being used.
------------------------------------------------------------------------
CAUTION
PREMISES WIRING
The RANGER 8+ DIESEL is suitable for temporary,
standby, or emergency power using the engine manu-
facturer’s recommended maintenance schedule. With
its three-wire grounded neutral generator, it can be
permanently installed as a standby power unit for 230
volt, three wire, single phase 40 ampere service.
Only a licensed, certified, trained electrician should
install the machine to a premises or residential elec-
trical system. Be certain that:
• The installation complies with the National Electrical
Code and all other applicable electrical codes.
• The premises is isolated and no feedbacking into
the utility system can occur. Certain state and local
laws require the premises to be isolated before the
generator is linked to the premises. Check your
state and local requirements.
• A double pole, double throw transfer switch in con-
junction with the properly rated double throw circuit
breaker is connected between the generator power
and the utility meter.
------------------------------------------------------------------------
The following information and the connection diagram,
Figure A.1, can be used as a guide by the electrician
for most applications to premises wiring.
1. Install a double pole, double throw switch between
the power company meter and the premises dis-
connect. The switch rating must be the same as or
greater than the premises disconnect and service
overcurrent protection.
2. Take the necessary steps to assure that the load is
limited to the capacity of the RANGER 8+ DIESEL
by installing a 40 amp 230 volt double pole circuit
breaker. Maximum rated load for the 230 volt auxil-
iary is 40 amperes. Loading above 40 amperes will
reduce output voltage below the allowable -10% of
rated voltage. This may damage appliances or
other motor-driven equipment.
3. Install a 50 amp 115/230 volt plug (NEMA type 14-
50) to a double pole circuit breaker using No. 8 or
larger, 4 conductor cable of the desired length.
(The 50 amp 120/240 volt plug is available in the
optional power plug kit.
4. Plug this cable in to the 50 amp 115/230 volt recep-
tacle on the RANGER 8+ DIESEL case front.
WARNING
Содержание RANGER 8 + DIESEL
Страница 37: ...NOTES RANGER 8 ...