Page 8 of 80
Mounting guidelines
LINAK
®
linear actuators are quickly and easily mounted by slipping pins through the holes on each end of the units
and into brackets on the machine frame and the load.
The mounting pins must be parallel to each other as shown in Figure 1. Pins, which are not parallel to each other,
may cause the actuator to bend and be damaged.
The load should act along the stroke axis of the actuator since off centre loads may cause bending and lead to
premature failure. See Figure 2.
Make sure the mounting pins are supported in both ends. Failure to do so could shorten the life of the actuator.
Cantilever mounts are unacceptable.
The actuator can rotate around the pivot point in the front and rear end. If this is the case it is of high importance
that the actuator is able to move freely over the full stroke length, both during the development and daily operation.
Please pay special attention to the area around the housing where parts can be trapped and cause damages to
the application and actuator.
In applications with high dynamic forces LINAK recommends not to use the fully extended or retracted position
over longer time, as this can damage the end stop system permanently.
X
X
E
F
7
8
9
A
B
C
D
1
2
3
4
5
6
E
A
B
C
D
Right
Wrong
Wrong
Wrong
Figure 1
Figure 2
Chapter 2
Please be aware that if the LA37 is used for solar applications the actuator must be mounted with the
motor housing turned upwards and the wires pointing downwards.
Содержание TECHLINE LA37
Страница 1: ...Page 1 of 80 LINAK COM TECHLINE Actuator LA37 User manual...
Страница 69: ...Page 69 of 80 Load and stroke curves LA37 Trunnion mounted...
Страница 78: ...Page 78 of 80...
Страница 79: ...Page 79 of 80...