Constant temperature mode (F01 = 0) 

Heat by compressor (F02 = 0) 

If (water temperature) 

≥ (se F03), and the compressor has stopped for F06, the compressor starts cooling. 

If (water temperature) 

≤ (setpoint), the compressor de-energized. 

If (water temperature) 

≤ (setpoint-F03), and the compressor has stopped for F06, the compressor starts heating. 

If (water temperature) 

≥ (setpoint), the compressor de-energized. 

Control sequence: Compressor on, fan will be on after 10 seconds. Compressor off, fan will be off after 5 seconds. 
Heating cooling change sequence: the compressor will be energized 15 seconds after 4-way valve is set. 

Heat by electrical heater (F02 = 1) 

If (water temperature) 

≥ (se F03), and the compressor has stopped for F06, the compressor energized. 

If (water temperature) ≤ (setpoint), the compressor de-energized. 
If (water temperature) ≤ (setpoint-F03), the heater energized. 
If (water temperature) 

≥ (setpoint), the heater de-energized. 

Control sequence: Compressor on, fan will be on after 10 seconds. Compressor off, fan will be off after 5 seconds. 

Defrost (F02 = 0, and under heating mode) 

Intelligent defrost 

If (pipe temperature) 

≤ F07, and the compressor has been energized for F10, start defrost. 

If (pipe temperature) 

≥ F08, or (the defrosting time) ≥ F09, stop defrost.

 

Periodic defrost 

Without defrost sensor, or when defrost sensor fails, the controller will defrost periodically. 
When the compressor has been energized for F10, start defrost. 
When defrosting time reaches F09, defrost ends.

 

Defrost procedure 

Compressor stops

→valve switches after 30 seconds→compressor starts for defrost after 30 seconds→compressor stops 

when F08 or F09 condition meets

→valve switches after 30 seconds→start compressor heating after 30 seconds.   

Fan stops during defrosting. 

Forced defrost (F02 = 0, under heating mode) 

Keep

and

depressed simultaneously for one second to enter into forced defrosting. 

* Forced defrosting works the same way as periodical defrost.   
* Once launched forced defrost, it will not stop, till the full process finished. 
* Fan stops during forced defrosting.

 

 

Fast launch (Force the compressor energized)

 

Launch: when online, keep

and

S

depressed simultaneously for 6 seconds, there will be 3 short beeps and 1 long beep, 

and the compressor will be energized.   

The controller will keep working as the set of F01 for 90 seconds, then exit the status. 

Stop: It can stop and exit by keeping

and

S

depressed simultaneously for 6 seconds. 

Pump control 

When online, keep

PUMP

depressed for 3 seconds to switch pump on/off. 

* When power supplied, pump works in the same status as that of previous power supplied. 
* Press

to shut to offline, the pump will stop. 

Press

to switch to online, the pump keeps off!

 

* External alarm does not influence the pump status. 

External alarm input 

F12 = 0, disable external alarm function. 
F12 = 1, when short for F13 time, alarming. 
F12 = 2, when open for F13 time, alarming. 
During alarming, all outputs except pump de-energized, buzzing, E3 displays, power lamp blinking.

 

Delay protection for compressor 

Every time, the power supplied, the compressor is possible to be energized after F06 time. 
Every time, the compressor is de-energized, it is possible to be energized after F06 time. 

Auto restart 

When power supply loses, and then come back, the controller will work in the same status as that before power loses.

   

Calibration 

By setting F04/F05, we can compensate the error of the sensors.   

Warning for sensor failure 

When water sensor fails, display E1, compressor/valve or heater/fan will be de-energized, beeping, OnOff lamp blinking. 

When pipe sensor fails, display E2. 

 

 

Содержание ZL-807A

Страница 1: ...2 0 4 Heat by electrical heater F02 1 4 Defrost F02 0 and under heating mode 4 Forced defrost F02 0 under heating mode 4 Fast launch Force the compressor energized 4 Pump control 4 External alarm input 4 Delay protection for compressor 4 Auto restart 4 Calibration 4 Waring for sensor failure 4 Restore to factory settings 5 Wiring diagram 5 Diagram one heating by compressor 5 Diagram two heating by...

Страница 2: ...With 2 sensors we can check outdoor pipe temperature Water pump on off control Compressor delay protection Instant start compressor Temperature calibration Sensor failure warning External warning input Auto restart for power supply failure Specification Power supply 100 240Vac 50 60Hz Outputs Compressor 40A 250Vac relay can drive 2HP compressor Valve Heater 5A 250Vac resistance Fan 5A 250Vac resis...

Страница 3: ...erature In online status short press will blinkingly show pipe temperature for 10 seconds Short press could stop show the pipe temperature Parameter code table Code Function Setting range Remark Factory set F01 Temperature control mode 0 1 0 constant temperature 1 cooling only 0 F02 Heating mode 0 1 0 by compressor 1 by electrical heater 0 F03 Hysteresis 0 1 20 0 1 0 F04 Calibration for water sens...

Страница 4: ... seconds start compressor heating after 30 seconds Fan stops during defrosting Forced defrost F02 0 under heating mode Keep and depressed simultaneously for one second to enter into forced defrosting Forced defrosting works the same way as periodical defrost Once launched forced defrost it will not stop till the full process finished Fan stops during forced defrosting Fast launch Force the compres...

Страница 5: ...Pages Restore to factory settings Keep SET and depressed simultaneously for 2 seconds display UnL Press twice all settings will restore to factory default values Wiring diagram Diagram one heating by compressor Diagram two heating by heater ...

Страница 6: ...ages Dimension Case size Embedded hole If the cable protection rubbers could be removed during installation Hole size 136 1 86 5 mm R 7 mm If the cable protection rubbers could not be removed during installation Hole size 135 1 90 5 mm R 6 mm ...

Отзывы: