ZL-807A Controller 

Instruction Manual V1.0

b

 

 

Feature 

ZL-807A is water temperature controller. It could work in cooling mode, or constant temperature control mode. 
It can drive 2 HP compressor directly. And it has water pump on/off control function. 
With IP60 panel, friendly to operate, easy to install. It could con

trol sea food chiller, aquarium pool, or water tank’s temperature. 

 

Function 

● Control mode: constant temperature, cooling only. 
● Heating method: by compressor, by electrical heater. 
● Periodic defrost (when install 1 sensor). 

Intelligent defrost (when install 2 sensors) 

* Default packing is with one sensor. 
* Pipe sensor could be purchased standalone.   

Pipe sensor can be found by controller when installed. 
If the outdoor evaporator frosts serious, 2 sensors is better. 
With 2 sensors, we can check outdoor pipe temperature.   

● Water pump on/off control 
● Compressor delay protection

 

● Instant start compressor 
● Temperature calibration 
● Sensor failure warning 
● External warning input 
● Auto restart for power supply failure 

 

 

Specification 

● Power supply: 100 ~ 240Vac, 50/60Hz 
● Outputs:   

Compressor: 40A/250Vac relay, can drive 2HP compressor. 
Valve/Heater: 5A/250Vac, resistance. 
Fan: 5A/250Vac, resistance. 
Pump: 5A/250Vac, resistance. 

● Set range: -9.9 ~ 65.0

 

● Display range: -9.9 ~ 70.0

 

●    Working: -10 ~ 45

, <85%RH without dew 

●    Deposit: -30 ~ 70

     

●    Case: fireproof ABS   
●    Protection level: IP60 
●    Sensor: NTC, 5K@25

, B=3470K. 

Water sensor, plastic sealed, 5 meters cable. 
Pipe sensor, copper sealed nickel coated, 2 meters cable. 

●    Size: See last page of this manual.

  

 

Display 

Panel 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Display indication 

Lamp 

On 

Off 

Blinking 

OnOff

  (red) 

Online 

Offline 

Alarming 

SET (yellow) 

Setting temperature 

 

Setting parameters 

PUMP (green) 

Pump energized 

Pump de-energized 

 

COOL (green) 

Cooling 

 

Under delay protection 

HEAT (red) 

Heating 

 

DEF (yellow) 

Defrosting 

 

Forced defrosting 

Содержание ZL-807A

Страница 1: ...2 0 4 Heat by electrical heater F02 1 4 Defrost F02 0 and under heating mode 4 Forced defrost F02 0 under heating mode 4 Fast launch Force the compressor energized 4 Pump control 4 External alarm input 4 Delay protection for compressor 4 Auto restart 4 Calibration 4 Waring for sensor failure 4 Restore to factory settings 5 Wiring diagram 5 Diagram one heating by compressor 5 Diagram two heating by...

Страница 2: ...With 2 sensors we can check outdoor pipe temperature Water pump on off control Compressor delay protection Instant start compressor Temperature calibration Sensor failure warning External warning input Auto restart for power supply failure Specification Power supply 100 240Vac 50 60Hz Outputs Compressor 40A 250Vac relay can drive 2HP compressor Valve Heater 5A 250Vac resistance Fan 5A 250Vac resis...

Страница 3: ...erature In online status short press will blinkingly show pipe temperature for 10 seconds Short press could stop show the pipe temperature Parameter code table Code Function Setting range Remark Factory set F01 Temperature control mode 0 1 0 constant temperature 1 cooling only 0 F02 Heating mode 0 1 0 by compressor 1 by electrical heater 0 F03 Hysteresis 0 1 20 0 1 0 F04 Calibration for water sens...

Страница 4: ... seconds start compressor heating after 30 seconds Fan stops during defrosting Forced defrost F02 0 under heating mode Keep and depressed simultaneously for one second to enter into forced defrosting Forced defrosting works the same way as periodical defrost Once launched forced defrost it will not stop till the full process finished Fan stops during forced defrosting Fast launch Force the compres...

Страница 5: ...Pages Restore to factory settings Keep SET and depressed simultaneously for 2 seconds display UnL Press twice all settings will restore to factory default values Wiring diagram Diagram one heating by compressor Diagram two heating by heater ...

Страница 6: ...ages Dimension Case size Embedded hole If the cable protection rubbers could be removed during installation Hole size 136 1 86 5 mm R 7 mm If the cable protection rubbers could not be removed during installation Hole size 135 1 90 5 mm R 6 mm ...

Отзывы: