Suzhou Lily Tech. Co., Ltd. 

 

[email protected]        www.suzhoulily.com.cn        Page 3, Total pages 5 

 

               

 

13 

U50 

High-temperature warning deviation 

value to Max Temp 

0~6

0℃

 

0: Disable 

14 

U51 

Low-temperature warning deviation 

value to Min Temp 

0~6

0℃

 

0: Disable 

15 

U52 

Over-temperature warning delay time

 

1

180min 

 

30 

16 

U53 

First  over-temperature  warning  delay 

time after power supply

 

0~180 hour 

0: Disable 

 

 

17 

 

 

U60 

 

 

External input warning   

 

 

0~1 

0:Warning off 

1:

On, Lock

 

2:On, Unlock 

3:Off, Lock 

4:Off, Unlock 

 

 

18 

U61 

External warning input delay 

0~120min 

 

19 

U62 

Buzzer warning 

0~1 

0:Warning off 

1:Warning on 

 

20 

U99 

Password 

0~99 

 

11 

5. Control Function Description 

5.1 Compressor Control

 

● When the temperature 

“MAX TEMP”, and the time that the compressor has stopped 

“the valve of 

U10”, the compressor starts. 

● When the temperature 

“MIN TEMP”, and the time that the compressor has run 

“the valve of U11”, 

the compressor stops. 

● Compressor emergent on 

Press and hold “▼” key for five seconds, the compressor will power on if the following meets:

 

◆ 

controller in non-defrosting status 

◆ 

controller in non-dropping water status 

◆ 

the compressor stops 

In compressor emergent on status, press and hole “▼” key for five seconds, the mode exits. 

5.2 Compressor Delay Protection   

● After power supply, the compressor is able to start only after the time(U10) has passed. 

● After the compressor stops, it is able to restart again only after the time(U10) has passed. 

● After the compressor starts, it is able to stop only after the time(U11) has passed. 

5.3 Temperature Sensor Failure Protection: Protected Running Mode

 

● 

When the room temperature sensor fails, the system will  automatically run in the protected running 

mode. In this mode, the compressor will run and stop with the period of 30 minutes. Compressor works 

for U12* 3 minutes, stop for 

30 - (U12* 3) 

minutes. 

Note: If U12=0, system stops when sensor fails

 

5.4 Defrosting Function 

5.4.1 Automatic Defrosting 

● 

When the compressor continuously running time reaches the time of defrost cycle (U30), the system 

starts to defrost. 

● 

When one of the conditions (defrosting end time(U31) and defrosting end temperature(U32)) meets, 

the defrosting stops.   

5.4.2Manual Forced Defrosting   

Содержание ZL-320A

Страница 1: ...ge 50 130 Working Temperature 10 45 Storage Temperature 30 70 Humidity 5 85 RH without dewing Power Supply 185 245VAC 50 60HZ Terminal Wire 2 1 5mm2 or 1 2 5mm2 Load Current 3A 250Vac Resistive load Case PC ABS Fire Proof Protection Degree IP30 4 Operation Instruction 4 1 Display Indication Panel LED Indication LED On Off Blinking MAX TEMP Set max temperature Set max temperature to be set MIN TEMP...

Страница 2: ...ssword SET If correct enter into the mode else return After enter into the mode the display shows U01 Press or to select the parameter code Press SET will show the parameter value Then press or to set this parameters and press SET to return The factory setting password is 11 Exit the Mode Keep depressing SET for three seconds the set parameters will be saved the mode exits Or do not press any key ...

Страница 3: ... will power on if the following meets controller in non defrosting status controller in non dropping water status the compressor stops In compressor emergent on status press and hole key for five seconds the mode exits 5 2 Compressor Delay Protection After power supply the compressor is able to start only after the time U10 has passed After the compressor stops it is able to restart again only aft...

Страница 4: ...me reachs to U52 or U53 low temperature warning starts 5 6 External input warning There are several ways for the external warning input to this device On Close warning starts When ok input opens Off Open warning starts When ok input closes Lock when the external warning input signal disappears system keep warning Only press the key can warn stop Unlock when the external warning input signal disapp...

Страница 5: ...layout the sensors and switches line apart from inductive load lines and power supply lines The sensors and switches lines are not allowed go with the power supply lines and inductive load lines in a same pipeline and are not allowed to pass near the contactor breaker and the similar Reduce the length of sensors wiring as possible avoid forming a spiral line near the power device Sensors line must...

Отзывы: