Err 

Password error or max/min temperature set invalid 

iA 

External warning 

10 

dEF 

Defrosting now 

11 

Frd 

Forced cooling 

12 

UnL 

Restore the default password ”11” 

4.2 Keypad Operation 

Set Max and Min Temperature

 

  Press 

SET

, MAX TEMP LED will be on, and the digits will show the current max temperature. 

Press key 

  or 

  to change the max temperature setting.   

Press 

SET

  again, we can set the min temperature limit.   

Keeping depressing 

SET

  for 3 seconds, or do not press any key for 30 seconds, the device will leave 

the temperature testing mode.   

 

  The factory setting: max temperature is -15

, min temperature is 

-18

.

 

  The MAX TEMP must be higher than the MIN TEMP 

1℃,

otherwise could not be saved.   

Note: Only after the

SET

being depressed for three seconds, will the set data be confirmed and saved. 

4.3 Set System Parameters   

Enter Into System Parameter Setting Mode 

Keep depressing 

SET

  for three seconds, digits show “POO”. Input pa 

SET

. If correct, 

enter into the mode, else return. 

After enter into the mode, the display shows “U01”. Press 

  or 

  to select the parameter code.   

Press

SET

  will show the parameter value. Then press 

  or 

  to set this parameters, and 

press

SET

  to return. 

The factory setting: password is “11”. 

Exit the Mode 

Keep depressing “SET” for three seconds, the set parameters will be saved, the mode exits. 

Or do not press any key for 30 seconds, the mode exits, and the set parameters are not saved. 

Parameter Code and Description Table: 

N

o. 

Parameter code 

Function 

Range 

Explain 

Factory 

setting 

U10 

Compressor power on delay time 

1

100min 

 

U11 

Compressor MIN continuous work time 

0

100min 

 

U12 

Compressor run frequency 

0

0: Disable 

U20 

Room temperature sensor calibration 

-9.9

+9.9 

 

U21 

Defrosting sensor calibration 

-9.9~+9.9 

 

U30 

Defrosting cycle 

0~180 hour 

0: Not defrost 

12 

U31 

Defrosting

end

time 

1

180min 

 

30 

U32 

Defrosting end temperature 

0.5

5

0

℃ 

 

15 

U33 

Dropping water time 

0

180min 

 

10 

U34 

Over  temperature  warning  delay  time 

after defrost ends 

0~180 hour 

0: Disable 

11 

U35 

Defrost when the device starts 

0~1 

0: Disable 

1:Enable 

12 

U36 

Defrost delay time when the device start 

0

180min 

0: Disable 

Содержание ZL-320A

Страница 1: ...ge 50 130 Working Temperature 10 45 Storage Temperature 30 70 Humidity 5 85 RH without dewing Power Supply 185 245VAC 50 60HZ Terminal Wire 2 1 5mm2 or 1 2 5mm2 Load Current 3A 250Vac Resistive load Case PC ABS Fire Proof Protection Degree IP30 4 Operation Instruction 4 1 Display Indication Panel LED Indication LED On Off Blinking MAX TEMP Set max temperature Set max temperature to be set MIN TEMP...

Страница 2: ...ssword SET If correct enter into the mode else return After enter into the mode the display shows U01 Press or to select the parameter code Press SET will show the parameter value Then press or to set this parameters and press SET to return The factory setting password is 11 Exit the Mode Keep depressing SET for three seconds the set parameters will be saved the mode exits Or do not press any key ...

Страница 3: ... will power on if the following meets controller in non defrosting status controller in non dropping water status the compressor stops In compressor emergent on status press and hole key for five seconds the mode exits 5 2 Compressor Delay Protection After power supply the compressor is able to start only after the time U10 has passed After the compressor stops it is able to restart again only aft...

Страница 4: ...me reachs to U52 or U53 low temperature warning starts 5 6 External input warning There are several ways for the external warning input to this device On Close warning starts When ok input opens Off Open warning starts When ok input closes Lock when the external warning input signal disappears system keep warning Only press the key can warn stop Unlock when the external warning input signal disapp...

Страница 5: ...layout the sensors and switches line apart from inductive load lines and power supply lines The sensors and switches lines are not allowed go with the power supply lines and inductive load lines in a same pipeline and are not allowed to pass near the contactor breaker and the similar Reduce the length of sensors wiring as possible avoid forming a spiral line near the power device Sensors line must...

Отзывы: