1. Features   

ZL-320A is an electronic thermostat for cooling. The device is ideally fitted to refrigeration equipment for cold 

storage. 

2. Main Function

 

  Temperature measurement                                         

  Temperature display 

  Temperature calibration                                               

  Compressor delay protection   

  Blustering when system warning   

  Sensor problem warning     

  External warning input 

  Defrost  control:  Periodical  defrosting,  temperature  and  time  combined  criteria,  dropping  water,  and 

manual forced defrosting 

3. Main Specification   

  Temperature Sensor:    NTC                                   

  Setting Range:                      -40

120

 

  Display Range:              -50

130

                       

  Working Temperature:          -10

45

 

  Storage Temperature:    -30

70

                         

  Humidity:        5

85%RH (without dewing) 

  Power Supply:                185 ~ 245VAC 50/60HZ 

  Terminal Wire:    <= 2 * 1.5mm

2

 or 1 * 2.5mm

2

 

  Load Current:          3A 250Vac

Resistive load

  Case:                PC + ABS Fire Proof 

  Protection Degree:          IP30 

4. Operation Instruction 

4.1 Display Indication 

Panel LED Indication 

LED 

On 

Off 

Blinking 

MAX TEMP 

Set max temperature 

Set max temperature 

(to be set) 

 

MIN TEMP 

Set min temperature 

Set min temperature (to 

be set) 

 

COOL 

Compressor on 

Compressor off 

Delay protecting now 

DEFROST 

Defrosting now 

Dropping water ends 

Dropping water now 

Panel Digit Indication 

Three red digits display the measured temperature and warning code. 

Warning Code: 

No. 

Display Code 

Warning Information 

E1 

Room sensor open circuit 

-E1 

Room sensor short circuit 

E2 

Defrosting sensor open circuit 

-E2 

Defrosting sensor short circuit 

Hi 

Room temperature exceeds the MAX TEMP 

Lo 

Room temperature exceeds the MIN TEMP 

EE 

Data access error 

Содержание ZL-320A

Страница 1: ...ge 50 130 Working Temperature 10 45 Storage Temperature 30 70 Humidity 5 85 RH without dewing Power Supply 185 245VAC 50 60HZ Terminal Wire 2 1 5mm2 or 1 2 5mm2 Load Current 3A 250Vac Resistive load Case PC ABS Fire Proof Protection Degree IP30 4 Operation Instruction 4 1 Display Indication Panel LED Indication LED On Off Blinking MAX TEMP Set max temperature Set max temperature to be set MIN TEMP...

Страница 2: ...ssword SET If correct enter into the mode else return After enter into the mode the display shows U01 Press or to select the parameter code Press SET will show the parameter value Then press or to set this parameters and press SET to return The factory setting password is 11 Exit the Mode Keep depressing SET for three seconds the set parameters will be saved the mode exits Or do not press any key ...

Страница 3: ... will power on if the following meets controller in non defrosting status controller in non dropping water status the compressor stops In compressor emergent on status press and hole key for five seconds the mode exits 5 2 Compressor Delay Protection After power supply the compressor is able to start only after the time U10 has passed After the compressor stops it is able to restart again only aft...

Страница 4: ...me reachs to U52 or U53 low temperature warning starts 5 6 External input warning There are several ways for the external warning input to this device On Close warning starts When ok input opens Off Open warning starts When ok input closes Lock when the external warning input signal disappears system keep warning Only press the key can warn stop Unlock when the external warning input signal disapp...

Страница 5: ...layout the sensors and switches line apart from inductive load lines and power supply lines The sensors and switches lines are not allowed go with the power supply lines and inductive load lines in a same pipeline and are not allowed to pass near the contactor breaker and the similar Reduce the length of sensors wiring as possible avoid forming a spiral line near the power device Sensors line must...

Отзывы: