EM58 • HS58 • HM58 POWERLINK
Transmitted position =
6001 Measuring units per revolution
real position
6002 Total measuring range in measuring units
NOTE
is currently enabled, you can read the
of the
WARNING
Every time you enable the scaling function and/or change the scaling values (see
the
6001 Measuring units per revolution
objects) then you are required to set a new preset value
object) and finally save the new parameters (see the
function).
Restore default parameters
This function allows the operator to restore all parameters to default values
(default values are set at the factory by Lika Electronic engineers to allow the
operator to run the device for standard operation in a safe mode).
Default parameters are restored at each rising edge of the bit; in other words,
the default parameters uploading operation is performed each time this bit is
switched from logic level low (“0”) to logic level high (“1”). The complete list of
machine data and relevant default parameters preset by Lika Electronic
engineers is available on page 104.
WARNING
The execution of this command causes all parameters which have been set
previously to be overwritten!
Store parameters
This function allows to save all parameters on non-volatile memory.
Data is saved on non-volatile memory at each rising edge of the bit; in other
words, data save is performed each time this bit is switched from logic level low
(“0”) to logic level high (“1”).
NOTE
function to save the new parameter
values.
If the power is turned off, the parameters that are not saved will be lost.
MAN EM58_HS58_HM58 PL E 1.1.odt
POWERLINK interface
92 of 108