LD25x
7.4 Model LD252: additional settings for preselections and switching
outputs
The basic set-up menu provides the following additional parameters:
Menu
Default
CHAr 1
Switching characteristics of output 1
__r GE
__r GE
Greater/Equal:
output to switch
statically
”ON”
when display value
≥
preselection 1.
__r LE
Lower/Equal:
output to switch
statically
”ON”
when display value
≤
preselection 1.
_n_ GE
Greater/Equal:
output to switch
dynamically
”ON” when display value
≥
preselection 1.
(timed pulse output *)
_n_ LE
Lower/Equal:
output to switch
dynamically
”ON”
when display value
≤
preselection 1.
(timed pulse output *)
CHAr 2
Switching characteristics of output 2
__r GE
__r GE
See
CHAr 1
, referred to preselection 2.
__r LE
See
CHAr 1
, referred to preselection 2.
_n_ GE
See
CHAr 1
, referred to preselection 2.
_n_ LE
See
CHAr 1
, referred to preselection 2.
__r 1-2
Output switches
statically
ON when display value
≥
Preselection 1 – Preselection 2 **.
_n_ 1-2
Output switches
dynamically
ON when display
value
≥
Preselection 1 – Preselection 2 **.
H
Y
St 1
Hysteresis 1:
adjustable hysteresis for output 1.
Setting range 0 ... 99999 display units.
0
H
Y
St 2
Hysteresis 2:
adjustable hysteresis for output 2.
Setting range 0 ... 99999 display units.
0
*
Timed output pulses have a fixed duration of 500 msec (factory adjustable
only).
** Trailing Preset to generate an anticipation signal with a fixed distance to the
main signal.
MAN LD25x E 1.0.odt
Set-up procedure
21 of 44