IF50
11.4 Channel B settings
These parameters are significant only when either A+B or A-B operation modes
are enabled (see parameter
Factor B
Impulse scaling factor for counter input B. Setting 1.0000 results in one
increment at each input pulse, whereas setting 0.5000 would need 10 input
pulses to increment by 5 etc.
Round Loop B
Using this register the counting range is limited to a repeating loop. If you set
1000, when count is increasing 999 is followed by 000, while when count is
decreasing the counter sets to 1000 when reaching zero.
Setting this register to 000 000 provides counting over the full range.
Set value B
Using the external CONTROL input (terminal 10, see section “5 - Electrical
connections” on page 46 and section “5.4 CONTROL input” on page 47), the
input B counter presets to the value set next to this item (range -/+100 000
000). The analogue output complies with the new counter state according to
the set output scaling. See the register
Multiplier B
Multiplier for multiple count of one input impulse on input B (001 – 999).
MAN IF50 I_E 1.0.odt
11 - Parameter settings
62 / 80
Содержание IF50
Страница 36: ...This page intentionally left blank...
Страница 37: ...This page intentionally left blank...
Страница 38: ...This page intentionally left blank...
Страница 39: ...This page intentionally left blank...