SFA-5000 • SFA-10000 Profibus
6.7 DDLM_Slave_Diag
The Master device can send a request for diagnostic information at any time to
the Slave device.
Lika devices provide two types of diagnostics (see the
parameter on page 50):
•
reduced diagnostics (16-byte diagnostics)
•
extended diagnostics (63-byte diagnostics).
Class 1 devices only provide 16-byte reduced diagnostics. Class 2 and Class 2
(+VEL) devices can provide either 16-byte reduced diagnostics or 63-byte
extended diagnostics.
Set the diagnostic type during DDLM_Set_Prm, operating parameters (byte 10),
see the “6.4.1 Byte 10 - Operating parameters” section on page 48.
16-byte reduced diagnostics:
Byte
Description
Byte
Description
0
Status 1
8
Operating status
1
Status 2
9
Encoder type
2
Status 3
10
Physical singleturn resolution
3
Master ID
11
4
Manufacturer ID
12
5
13
6
Extended diagnostic header
14
Number of physical
distinguishable revolutions
7
Alarms
15
MAN SFA_5000_10000_PB E 1.0
Profibus® interface
62 of 72