Lightway PV Modules, Installation Manual, Page
3
/36
www.lightwaysolar.com
module should be multiplied by of 1.25 when determining component voltage ratings, conductor current ratings,
fuse sizes, and size of controls connected to the PV output.
⊙
The safety factor of 1.25 for the minimum voltage rating of the components can be modified during the design
of a system according to the minimum temperature of the location of the installation and the temperature
coefficient for Voc and Isc can be adjusted based on maximal temperature, irradiance and orientation of the
module. To this end a full simulation for the specific location is required using long term weather data.
⊙
Module application: Class A (modules rated for use in this application class maybe used in systems operating at
greater than 50V DC or 240W, there general contact access is anticipated, Modules qualified for safety through this
part of IEC61730 and IEC61730-2 and within this application class are considered to meet the requirements for
safety Class
Ⅱ
.)
⊙
The recommended stand-off height is about 115mm, if other mounting means are employed, this may affect
the Listing for Fire Class Ratings. When installed on a roof, the module shall be mounted over an fire-resistant roof
covering rated for the application, the mounting design may have an impact on the fire resistance.
⊙
Ensure that the installation method and supporting system of modules is strong enough to make the modules to
able to withstand all the load conditions. The Installer must provide the guarantee. The installation supporting
system must be tested by the third-party organization with the analysis ability of Static Mechanical, according to
the local national or international standards such as DIN1055 or equivalent standards.
⊙
The Modules mounting structure must be made of durable, corrosion-resistant and UV-resistant material.
⊙
Modules must be securely attached to the mounting structure.
⊙
In regions with heavy snowfall in winter, select the height of the mounting system. So that the lowest edge of
the Modules is not covered by snow for any length of time. In addition, ensure that the lowest portion of the
Modules is placed high enough so that it is not shaded by plants or trees or damaged by flying sand.
⊙
In case of installed on metal sheet roof, flush mounting is recommended. In case of installed on concrete roof,
the module could be tilted and a minimum of 10 degrees tilt angle should be follow for cleaning.
⊙
Do not attempt to drill holes in the glass surface and the frames of the Modules .Before installing Modules on a
roof, ensure that the roof construction is suitable. In addition, any roof penetration required to mount the
Modules must be properly sealed to prevent leaks.
⊙
Always keep the back sheet of the module free from foreign objects or structural elements, which could come
into contact with the module, especially when the module is under mechanical load.
⊙
Please wear special labor protection gloves to avoid leaving fingerprints and perspiration stains and other dirt
on glasses. Regularly replace the dirty gloves in time.
⊙
For module,external factors may lead the result such as thermal expansion and contraction, the same matrix is
recommended to reserve a certain distance between any two modules
,
at least 20mm.
⊙
There are three colors in Lightway modules, light blue, blue and dark blue. In order to have a beautiful visual
effect, please install modules with the neighboring color. Light blue and dark blue should not be installed together.
⊙
Please keep the connectors in tough while installing module. The cable should keep a certain length to ensure
that the both ends of cable have no stress.
When mounting modules in snow
⊙
-prone or high-wind environments, special care should be taken to mount the
modules in a manner that provides sufficient design while meeting local code requirements.
Product identification
Each module has two labels providing the following information:
Nameplate:
describes the product type; rated power, rated current, rated voltage, open circuit voltage, short
circuit current, all as measured under standard test conditions; dimension etc. The maximum system voltage is
Содержание LW6M60-260
Страница 15: ...Lightway PV Modules Installation Manual Page 14 36 www lightwaysolar com...
Страница 20: ...Lightway PV Modules Installation Manual Page 19 36 www lightwaysolar com 2006 992 990 40 Multi poly...
Страница 21: ...Lightway PV Modules Installation Manual Page 20 36 www lightwaysolar com 1680 992 990 40 Multi poly...
Страница 22: ...Lightway PV Modules Installation Manual Page 21 36 www lightwaysolar com 1680 992 990 35 Multi poly...
Страница 23: ...Lightway PV Modules Installation Manual Page 22 36 www lightwaysolar com 1979 1002 40 Mono poly Series...
Страница 24: ...Lightway PV Modules Installation Manual Page 23 36 www lightwaysolar com 2008 1002 40 Mono poly Series...
Страница 25: ...Lightway PV Modules Installation Manual Page 24 36 www lightwaysolar com 1845 1002 998 35 Mono poly Series...
Страница 26: ...Lightway PV Modules Installation Manual Page 25 36 www lightwaysolar com 1684 1002 40 35 Mono poly Series...
Страница 27: ...Lightway PV Modules Installation Manual Page 26 36 www lightwaysolar com 1665 1002 40 35 Mono poly Series...