Lightway PV Modules, Installation Manual, Page 

2

/36 

 

www.lightwaysolar.com 

 

which it may cause. 

To avoid the hazard of electric shock and fire, be sure that other system components do not cause    any hazard 

of any mechanical or electrical nature to the module. 

Since sparks may be generated, do not install module where flammable gases or vapors are present. 

Never  leave  a  module  unsupported  or  unsecured.  Do  not  drop  module  and  do  not  allow  objects  to  fall  on 

module to avoid the hazard of injury or any troubles in modules, which it may cause. 

Do not use or install broken modules to avoid the hazard of electric shock and injury. 

Artificially concentrate sunlight shall not be directed on the module to avoid the hazard of fire or any trouble. 

Do not touch the J-box terminals to avoid the hazard of electric shock and injury. 

Do not change wiring of bypass diodes to avoid the hazard of electric shock and injury. 

Use module for its intended function only. 

Do not treat the back sheet and front surface with paint or adhesives to avoid any troubles. 

Consult your local authority for guidelines and requirements for building or structural fire safety.

 

Roof  constructions  and  installations  may  affect  the  fire  safety  of  a  building;  improper  installation  may  create 

hazards in the event of a fire

 

Use components such as ground fault circuit breakers and fuses as required by local authority. 
Do not use panels near equipment or in places where flammable gases may be generated.

 

The modules have been rated 

Fire Class C, and are suitable for mounting on to a Class A roof. 

The wiring method contain the series connection and the parallel connection. The series connection means the 

positive pole of one module connect with the negative pole of another module. The parallel connection means the 
positive  pole  of  one  module  connect  with  the  positive  pole  of  another  module,  and  the  negative  pole  of  one 
module connect with the negative pole of another module.   

 

Cautions 

Follow all permission, installation and inspection requirements. 

Lightway Solar PV module should not be sited in locations where aggressive substances such as salt or salt-water, 

or  any  other  types  of  corrosive  agent,  where  could  affect  the  safety  and/or  performance  of  the  PV  modules. 
Although Lightway Solar PV module have passed IEC 61701(Ed.2,2011) Salt Mist Corrosion test, galvanic corrosion 
can occur between the aluminum frame of PV module and mounting or grounding hardware. 

Before installing module, contact appropriate authorities to determine permission, installation and inspection 

requirements,  which  should  be  followed.  This  should  be  done  not  only  for  installations  in  conjunction  with 
buildings, but also for marine and motor vehicle applications for which additional requirements may apply. 

About the mechanical loading test

the design loading is 3600Pa for the front side

and 1600Pa for the back side. 

The safety factor are

 

All 1.5 times.

 

Be  sure  that  the  construction  intended  to  install  modules  on  its  rooftop  has  enough  strength.  For  modules 

mounted  on  roof,  special  construction  may  be  required  to  help  provide  proper  installation.    Both  roof 
construction  and  module  installation  design  have  an  effect  on  the  fire  resistance  of  the  building.    Improper 
installation  may  contribute  to  hazards  in  the  event  of  fire.  Additional  devices  such  as  ground  fault,  fuses  and 
disconnects may be required. 

Do not use modules of different configurations in the same system. 

Sunlight shall not be concentrated on the module or other artificial light sources on to the module. 

Under normal conditions, a photovoltaic module is likely to experience conditions that produce more current 

and/or  voltage  than  reported  at  standard  test  conditions.  Accordingly,  the  value  of  Isc  and  Voc  marked  on  this 

Содержание LW6M60-260

Страница 1: ...Park Gaobeidian Hebei Province P R China Tel 86 312 2951122 Fax 86 312 2951166 P C 074000 Email info lightwaysolar com www lightwaysolar com The Energy Depot Australia Add 1 4 Bridge Rd Keysborough V...

Страница 2: ...rface of PV modules with a dense opaque material such as the cardboard box during installing and handling modules The shock hazard increases as modules are connected in parallel producing higher curre...

Страница 3: ...means the positive pole of one module connect with the positive pole of another module and the negative pole of one module connect with the negative pole of another module Cautions Follow all permiss...

Страница 4: ...the height of the mounting system So that the lowest edge of the Modules is not covered by snow for any length of time In addition ensure that the lowest portion of the Modules is placed high enough...

Страница 5: ...ansported in the supplied packaging Installation only and kept in the packaging until they are ready to be installed Protect pallets against movement and exposure to damage during transportation Secur...

Страница 6: ...les prior to installation the PV modules should remain inside the packaging and protected from exposure that could compromise the durability of the packaging Selecting the location Select a suitable l...

Страница 7: ...ries 1640 990 35series 1640 992 35series 1680 992 35series 1680 990 35series 1665 1002 35series 1684 1002 35series shall be installed with a rack structure by using 4 sets of an M8 screw two flat wash...

Страница 8: ...m Clamp material should be anodized aluminum alloy Floating type clamps are not authorized Clamp positions are of crucial importance for the reliability of the installation the clamp centerlines must...

Страница 9: ...under large current Please pay attention the temperature limit of cable is 85 Functional earth the negative pole of the system will prevent the PID effect from happening However the earthing applicati...

Страница 10: ...les because the current from other cells in the same series is forced to flow through the shaded area and then undesirable heating may occur The use of a diode to bypass the shaded area can minimize b...

Страница 11: ...inspected by the installer or other qualified person The purpose of the PV system inspection is to ensure that all system components are functioning properly At a minimum this inspection should confir...

Страница 12: ...bstances can leak into the groundwater and get into the food chain damaging your health and well being When replacing old appliances with new ones the retailer is legally obligated to take back your o...

Страница 13: ...Lightway PV Modules Installation Manual Page 12 36 www lightwaysolar com If it is inconsistent between the different languages the English version shall be prevail...

Страница 14: ...Lightway PV Modules Installation Manual Page 13 36 www lightwaysolar com REAR AND SIDE VIEW DIMENSIONS UNITS mm 1956 1960 990 992 40 Multi poly Mono poly Series...

Страница 15: ...Lightway PV Modules Installation Manual Page 14 36 www lightwaysolar com...

Страница 16: ...Lightway PV Modules Installation Manual Page 15 36 www lightwaysolar com 1650 990 992 40 Multi poly Mono poly Series...

Страница 17: ...Lightway PV Modules Installation Manual Page 16 36 www lightwaysolar com 1640 990 992 40 Multi poly Mono poly Series...

Страница 18: ...Lightway PV Modules Installation Manual Page 17 36 www lightwaysolar com 1650 990 992 35 Multi poly Mono poly Series...

Страница 19: ...Lightway PV Modules Installation Manual Page 18 36 www lightwaysolar com 1640 990 992 35 Multi poly Mono poly Series...

Страница 20: ...Lightway PV Modules Installation Manual Page 19 36 www lightwaysolar com 2006 992 990 40 Multi poly...

Страница 21: ...Lightway PV Modules Installation Manual Page 20 36 www lightwaysolar com 1680 992 990 40 Multi poly...

Страница 22: ...Lightway PV Modules Installation Manual Page 21 36 www lightwaysolar com 1680 992 990 35 Multi poly...

Страница 23: ...Lightway PV Modules Installation Manual Page 22 36 www lightwaysolar com 1979 1002 40 Mono poly Series...

Страница 24: ...Lightway PV Modules Installation Manual Page 23 36 www lightwaysolar com 2008 1002 40 Mono poly Series...

Страница 25: ...Lightway PV Modules Installation Manual Page 24 36 www lightwaysolar com 1845 1002 998 35 Mono poly Series...

Страница 26: ...Lightway PV Modules Installation Manual Page 25 36 www lightwaysolar com 1684 1002 40 35 Mono poly Series...

Страница 27: ...Lightway PV Modules Installation Manual Page 26 36 www lightwaysolar com 1665 1002 40 35 Mono poly Series...

Страница 28: ...310W LW6P72 340W LW6P60 270W LW6PH72 335 LW6PH60 305W LW6P72 335W LW6P60 265W LW6PH72 375W LW6PH60 300W LW6P72 330W LW6P60 260W LW6PH72 370W LW6PH60 295W LW6P72 325W LW6P60 255W LW6PH72 365W LW6PH60...

Страница 29: ...370W LW6MH60 330W LW6M72 335 LW6M60 270 LW6MH72 405W LW6MH66 365W LW6MH60 325W LW6M72 330 LW6M60 265 LW6MH72 400W LW6MH66 360W LW6MH60 320W LW6M72 325 LW6M60 260 LW6MH72 395W LW6MH66 355W LW6MH60 315...

Страница 30: ...y Series 1960 992 40 Mono poly Series 1665 1002 40 Mono poly Series 1684 1002 40 Mono poly Series 1845 1002 40 Mono poly Series 1979 1002 40 Mono poly Series 2008 1002 40 Mono poly Series 1845 998 40...

Страница 31: ...5 39 81 9 42 47 37 9 85 1500 15 20 4mm2 1680 992 40 Multi poly Series 1680 992 35 Multi poly Series 1680 990 40 Multi poly Series 1680 990 35 Multi poly Series LW6PH60 280 280 31 65 8 85 37 89 9 37 15...

Страница 32: ...tput tolerances Series Module Pmax Vmpp Impp Voc Isc Max system voltage V Max series fuse rating A Cable Diameter W V A V A 1956 990 40 Multi poly Series 1956 992 40 Multi poly Series 1960 990 40 Mult...

Страница 33: ...ly Series 1650 1640 9 92 40 Multi poly Series 1650 1640 9 90 35 Multi poly Series 1650 1640 9 92 35 Multi poly Series LW6P60 255W 255 30 31 8 42 37 31 8 93 1000 15 20 4mm2 LW6P60 260W 260 30 53 8 52 3...

Страница 34: ...ly Series 1650 1640 990 35 Mono poly Series 1650 1640 992 35 Mono poly Series 1665 1002 35 Mono poly Series LW6M60 260 260 30 78 8 45 37 61 9 02 1500 15 20 4mm2 LW6M60 265 265 31 04 8 54 37 82 9 10 15...

Страница 35: ...65 38 03 9 18 1000 15 20 4mm2 LW6M60 275W 275 31 43 8 75 38 24 9 28 1000 15 20 4mm2 LW6M60 280W 280 31 72 8 83 38 42 9 38 1000 15 20 4mm2 LW6M60 285W 285 31 92 8 93 38 62 9 48 1000 15 20 4mm2 LW6M60...

Страница 36: ...20 4mm2 LW6MH60 330 330 34 13 9 67 40 87 10 26 1500 15 20 4mm2 LW6MH60 325 325 33 86 9 60 40 62 10 19 1500 15 20 4mm2 LW6MH60 320 320 33 58 9 53 40 36 10 12 1500 15 20 4mm2 LW6MH60 315 315 33 30 9 46...

Страница 37: ...4 1002 3 5 Multi poly Series LW6MH60 345W 345 34 92 9 88 41 60 10 47 1500 15 20 4mm2 LW6MH60 340W 340 34 66 9 81 41 36 10 40 1500 15 20 4mm2 LW6MH60 335W 335 34 40 9 74 41 12 10 33 1500 15 20 4mm2 LW6...

Отзывы: