Setting the DIP switches:
Your thermostat may have up to (7) configurable DIP switches depending on the
features specified for your application. DIP switches may be configured in accordance with
the following table.
For TGHC Models, switch positions 1 through 5 should be set. Positions 6 and 7 have no
function.
For TGHP Models, all switch positions (1 through 7) should be set accordingly.
Position
Off (left position)
On (right position)
1
Fahrenheit
Celsius
2
45 Second Lockon/lockoff
Timers Active
45 Second Lockon/lockoff
Timers Inactive
3
Lesser setback number
Greater setback number
4
Fan controlled by thermostat
in heat mode.
Fan controlled by external
device in heat mode.
5
Fan locked in auto when in
setback.
Fan on allowed when in set-
back.
6
Backup Heat
Operating Differential
1.5 ° F
(0.8 ° C)
Backup Heat
Operating Differential
3.0 ° F
(1.7 ° C)
7
O output with cool
O output with heat
Note:
If any DIP switch is changed during operation, the thermostat will reset and the new
dipswitch setting(s) will be read.
7