DB612 DISTRIBUTED DIMMING BAR 

 Version: 1.1  

 

 

 

 

 

 

 

 

 

OWNERS MANUAL

  

 

 

 

 

 

 

 

 

 

  01/06/2022 

www.lightronics.com 

Lightronics Inc   

 

 

 

 

 

 

 

509 Central Drive, Virginia Beach, VA  23454 

 

 

 

 

 

 

   Tel  757 486 3588 

matter which phase is connected to the L1 terminal 
but L2 and L3 must be in the correct order.  The unit 
will not be damaged if these two connections are 
reversed but dimming will not occur correctly and 
some channels will appear to be in an on/off mode.  
If this occurs – see the “Phase Sensing Jumper” 
section in this manual and set the jumper block for 
three phase reverse operation. 
 
 
 
 

 

 

SINGLE PHASE POWER CONNECTIONS 

 
The DB612 may be field converted to accommodate 
a SINGLE PHASE 120/240 VAC  power  service.  
Consult the applicable electrical codes for your 
location for exact wire specifications.  The unit must 
be powered from a circuit providing a minimum of 30 
Amps per line (2 pole 30 Amp circuit breaker).  The 
minimum wire size is AWG#10.  Wire may be either 
stranded or solid.  The terminals are intended for 
copper wire only. 
 
 

 

 
 
 
1  Remove the access cover at the end of the unit. 
2  Connect the two "HOT" power input wires to the 

L1

 and 

L3 

terminals. 

 

Note the terminal marked L2 is not used for 
single phase operation. 
 

3  Connect the neutral wire to the terminal marked 

N

.  

4  Connect a ground wire to the CHASSIS 
GROUND terminal marked 

G

 
There are two blue wires in the 

L2

  terminal on the 

opposite side of the power input terminal strip.  
These wires have color coded shrink tubing markers 

on  them. One of them is marked with BLACK.  The 
other is marked with RED. 
 
5  Move the BLUE wire with the BLACK marker 
from the 

L2

 terminal to the 

L1

 terminal.   

6  Move the BLUE wire with the RED marker from 
the 

L2

 terminal to the 

L3

 terminal.   

 
A diagram  of single phase power connections is 
shown below: 
 
 
 

 

 

PHASE SENSING JUMPER 

 
There is a small black jumper block located on the 
back of the control circuit board which must be set to 
correspond to either single phase or three phase AC 
input power.  Install the jumper according to the 
power at your facility using the diagram below.  The 
positions are shown below and are marked on the 
circuit board.  The control circuit board is mounted in 
the inside of the main control panel which is the front 
center panel on the unit.  The Three Phase Reverse 
setting is provided only to correct “out of sequence” 
power input connections.  Also see the section 
“Three Phase Power Connections”  for more 
information concerning the Three  Phase Reverse 
setting. 
 
The  DB612  is usually shipped from the factory set 
for Three Phase Normal operation. 
 

Disconnect or turn off power to the unit 

before changing jumper settings. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

Factory Supplied Configuration 

 

 
 

  

 

 

MAKE CERTAIN THE INPUT  

POWER SOURCE IS DE-ENERGIZED  

BEFORE MAKING CONNECTIONS.

 

 

SINGLE PHASE POWER 

INPUT CONNECTIONS 

THREE PHASE POWER    

INPUT CONNECTIONS 