Operating Voltage: 120VAC, 50/60Hz
Number of Circuits:
OPT22400RL/OPT22400RL15: 2
OPT42400RL/OPT42400RL15: 4
Min Rated Load (Per circuit): 0.5W
Max Rated Load (Per circuit):
OPT22400RL: 2400 Watts
OPT22400RL15: 1800 Watts
OPT42400RL: 2400 Watts
OPT42400RL15: 1800 Watts
Operating Voltage: 277VAC, 60Hz
Number of Circuits:
OPT24000RL7: 2
OPT44000RL7: 4
Min. Rated Load (Per Circuit): .5W
Max Rated Load (Per Circuit):
OPT24000RL7: 4000W
OPT44000RL7: 4000W
Supported Load Types: Incandescent, Inductive, Magnetic Low
Voltage, Electronic Low Voltage, HID *
Cooling: Natural convection
Ambient Operating Temp: 0 to 40 degrees C
Relative Humidity: 5 to 95% (non-condensing)
*
When controlling HID lamps, derating of the relay circuit by 20%
is required.
R
ELAY
M
ODULES
Lightolier Controls
2828 Trade Center Drive
•
Suite 130B
Carrollton, Texas 75007
For technical/sales assistance, call: 1-800-526-2731
Printed in U.S.A. ©Philips Controls 2007
www.lolcontrols.com P/N
85-6349A0
Installation
Instructions
The Optio Relay Modules offer economical and reliable switching of non-dim loads including
lighting, signs, and motors. The modules utilize rugged relays and feature dual-color status indica-
tors, and focus buttons for manual operation and testing.
All Optio Dimmer Modules have identical mounting dimensions, allowing them to be easily
swapped within any of the Optio Lighting Control Panels. (Use caution to ensure that quad mod-
ules are not installed into spaces wired for dual modules.)
Description
WARNING
: Installing the module with power applied to the cabinet may expose you to
dangerous voltage and damage the device. Remove power before installing. A qualified
electrician should perform this installation.
Any combination of Optio dimming and relay modules may be installed in the Lighting Control
Panel. Blank covers MUST be installed in any unused spaces. Pull the jumper (shorting plugs)
before installing.
To install modules:
1. Unpack module and recycle or properly discard packaging materials. (Be sure to keep this
instruction sheet for future use.) Inspect relay module for signs of damage during transit.
2. Disconnect main power to Optio Lighting Control Panel.
3. Open relay module side of panel front cover.
4. If present, remove blank cover from location where module is to be installed (
Figure 1
).
When possible, lower modules should be installed first.
5. Remove shorting plugs from the load terminal block. (The shorting plug is the red tab pro-
truding from the green load terminal block. To remove, grasp the shorting plug and gently
pull.)
Note: The module will not operate properly if the shorting plug is left in circuit.
6. Gently insert module into lighting control panel with the relays facing you. Secure module
using four screws (provided).
Note: The connectors of 277VAC Optio modules are keyed,
preventing the insertion of modules into panels of the incorrect voltage. Do not force modules
into slots.
7. Close panel front cover.
Blank Cover
Screw (4)
Screw (4)
Load Terminal Block
Shorting
Plug
Terminal
DETAIL
Relay
Module
Focus Button
& Status LEDs
Figure 1: Installing Modules and Blank Covers
Installation Procedure
NOTE: The Optio 9-
Module Panel is used to
illustrate the installation in
Figure 1
. However, the
module installation is iden-
tical for all Lighting Control
Panel models.
Electrical Specifications
Operation
O p t i o R e l a y M o d u l e s a r e
equipped with a "Focus Button" on
each circuit (
Figure 1
). Tapping
the focus button will turn the circuit
on, tapping it again will turn the cir-
cuit off.
Red LED
Green LED
Condition
Off
Off
Normal
Off
On
Focus Mode
(controlled at module)
On
Off
Communication Error
Flashing
Flashing
Miswire to Line
Status LED Indications: