Programming
248083201-1 Rev 6
4-11
Type:
<sb>
Response:
<sb>STOP
GET CURRENT VERSION NUMBER
<gv>
Shows current version number of the device firmware.
Type:
<gv>
Response:
<gv> Version: 010
SET CHANNEL RANGES
Note:
Range 1 should
always be greater than or
equal to Range 2; Range 2
should never be greater
than Range 1.
When using the DIP switch
programming, both
channels are set to the
same range value.
<ra#>
-- sets upper range of channel 1 where # is the range value
<rb#>
-- sets upper range of channel 2 where # is the range value
Sets upper limit to counting range. The upper limit will be equal to
20mA, and the lower range will always be 0 counts = 4 mA. If the
counts exceed range limit, the counts will be set to the range limit. The
maximum range is 10,000,000.
Type:
<ra10000>
Response:
<ra10000>Range1= 10000.
Type:
<rb7500>
Response:
<rb7500>Range2= 7500.
Содержание REMOTE 2 Series
Страница 1: ......
Страница 2: ...00...
Страница 6: ......
Страница 10: ...Lighthouse REMOTE 2012 3012 5012 3102 5102 Operating Manual t iv 248083201 1 Rev 6...
Страница 12: ...Lighthouse REMOTE 2012 3012 5012 3102 5102 Operating Manual ii 248083201 1 Rev 6...
Страница 18: ...Lighthouse REMOTE 2012 3012 5012 3102 5102 Operating Manual 2 4 248083201 1 Rev 6...
Страница 46: ...Lighthouse REMOTE 2012 3012 5012 3102 5102 Operating Manual 5 4 248083201 1 Rev 6...
Страница 50: ...Lighthouse REMOTE 2012 3012 5012 3102 5102 Operating Manual A 2 248083201 1 Rev 6...
Страница 53: ...Index 248083201 1 Rev 6 I 3 Weight 2 3 Z Zero Count Check Troubleshooting 6 2 Zero Count Level 2 3...
Страница 54: ...Lighthouse REMOTE 2012 3012 5012 3102 5102 Operating Manual I 4 248083201 1 Rev 6...
Страница 55: ...00...
Страница 56: ......