24
Host send format
:
Machine
Code
Function
Code
Register First
Address
Number of
Registers
CRC Check
1-254
(1 Byte)
0x04
(1 Byte)
0x083A
(2 Byte)
0x0009
(2 Byte)
0x****
(2 Byte)
Slave return correctly
:
Machine
Code
Function
Code
Register
First
Address
Number of
Registers
CRC Check
1-254
(1 Byte)
0x04
(1 Byte)
0x12
(1 Byte)
*****
(0x12 Byte)
0x****
(2 Byte)
Slave error returned:
Machine
Code
Function
Code
Error Code
CRC Check
1-254
(1 Byte)
0x84
(1 Byte)
0x01
(
Check does not pass
)
or 0x03
(
Remote control OFF
)
(1 Byte)
0x****
(2 Byte)
Read a single parameter (example: read cumulative flow):
Host send format
:
Machine
Code
Function
Code
Register First
Address
Number of
Registers
CRC Check
1-254
(1 Byte)
0x04
(1 Byte)
0x084A
(2 Byte)
0x0001
(2 Byte)
0x****
(2 Byte)