Manual F5021B - SM02/SM03 cabin module
Terminal
Name
Descripion
Function
Advise
15
TX13 Light gate door B
input N
16
TX14 button door keep open
input N
17
TX15 button inspection fast
input N
18
TX16 Cabin light monitoring
input N
19
TX17 Firedepartement-key-switch
input N
20
TX18 Free
input N
JP6
1
TXV+ +24V supply SM02
2
TXV- GND supply SM02
3
TXA+ CAN_H
4
TXA- CAN_L
JP15
1
D0
output to control of a voice announcement up to 255
annoucements.
output NPN
2
D1
output NPN
3
D2
output NPN
4
D3
output NPN
5
D4
output NPN
6
D5
output NPN
7
D6
output NPN
8
D7
output NPN
9
GND Voltage supply voice message
10
+24V
JP1
Jumper for CAN Bus termination. Only if the termination
is not activated yet in the cabin indicator board. (SM04)
JP7
Connector for button-connection-module SM03
J2/J3
In case voltage supply is only via JP6 install both bridges.
In no case
install if JP2.19 and JP2.20 get supplied in
separate!
SM03 button module
It is possible to connect up to eight SM03 each with 8 buttons (up to 64 floor buttons)
Plug
SM03 Nr.1
SM03 Nr.2
...
SM03 Nr.8
JP1
floor 1
floor 9
...
floor 57
JP2
floor 2
floor 10
...
floor 58
JP3
floor 3
floor 11
...
floor 59
JP4
floor 4
floor 12
...
floor 60
JP5
floor 5
floor 13
...
floor 61
JP6
floor 6
floor 14
...
floor 62
JP7
floor 7
floor 15
...
floor 63
Page 31
Содержание F5021
Страница 1: ...Manual F5021B Lift controller 32 bit system version E02 2 MA ...
Страница 4: ......
Страница 6: ......
Страница 16: ......
Страница 24: ...Manual F5021B Menu tree parameter Page 20 ...
Страница 36: ...Manual F5021B SM02 SM03 cabin module Plug SM03 Nr 1 SM03 Nr 2 SM03 Nr 8 JP8 floor 8 floor 16 floor 64 Page 32 ...
Страница 40: ......
Страница 50: ......