LifeSafety Power FlexPower RA100 Series Скачать руководство пользователя страница 4

RA Series, RD Series Rackmount Installation Manual

iv

1

Installation and Operation

Introduction

RA Models

Power

Outputs

Description

RA100 Series

100VA

8, 16, 24

4 .16A @  24VAC 3 .57A @  28VAC programmable outputs 24 or 28VAC

RA150 Series

150VA

8, 16, 24

6 .2A  @ 24VAC 5 .4A  @ 28VAC programmable outputs 24 or 28VAC

RA300 Series

300VA

8, 16, 24

12 .5A @  24VAC 10 .7A @  28VAC programmable outputs 24 or 28VAC

RA600 Series

600VA

8, 16, 24

25A  @ 24VAC 21A  @ 28VAC programmable outputs 24 or 28VAC

RA-N Models with remote reset

RA150-16N

150VA

16

6 .2A  @ 24VAC 5 .4A  @ 28VAC 16 programmable outputs, remote reset

RA300-16N

300VA

16

12 .5A @  24VAC 10 .7A @  28VAC 16 programmable outputs, remote reset

RA600-16N

600VA

16

25A  @ 24VAC 21A  @ 28VAC 16 programmable outputs, remote reset

RD Models

Power

Outputs Description

RD75 Series

75W

2

Single Voltage

  6A @ 12VDC or 3A @ 24VDC /  dual output     

RD150 Series

150W

2

Single Voltage

12A @ 12VDC or 6A @ 24VDC /  dual output

RD250 Series

250W

2

Single Voltage

20A @ 12VDC or 10A @ 24VDC /  dual output

RD75/75 Series

150W

8, 16 Dual Voltage

  6A @ 12VDC or 3A @ 24VDC (X2) /  multiple outputs     

RD150/150 Series 300W

8, 16 Dual Voltage

12A @ 12VDC or 6A @ 24VDC (X2) /  multiple outputs     

RD250/250 Series 500W

8, 16 Dual Voltage

20A @ 12VDC or 10A @ 24VDC (X2) /  multiple outputs     

RD-N Models with network monitoring

RD75-XN

75W

8, 16 Single Voltage / Network   6A @ 12VDC or 3A @ 24VDC  /  multiple outputs / network

RD150-XN

150W

8, 16 Single Voltage / Network 12A @ 12VDC or 6A @ 24VDC  /  multiple outputs / network

RD250-XN

250W

8, 16 Single Voltage / Network 20A @ 12VDC or 10A @ 24VDC  /  multiple outputs / network

The 

FLEX

POWER

 rackmount series of power supplies 

provide AC or DC  power for lifesafety applications . De-

signed to fit neatly into standard 19" equipment racks, the 

streamlined cabinetry and exceptional features combine to 

significantly reduce installation and service costs . Features 

include removable terminal strips for field wiring, input and 

output surge suppression, automotive blade fuses for im-

proved reliability, a front removable chassis face plate for 

serviceability and is enclosed in a 16 gauge steel 2U rack 

mount chassis .

The 

FLEX

POWER

 

RA Series

 of AC power supplies 

provide 24 and 28 VAC power at 100W - 600W of total 

power . They are available with 8, 16, or 24 outputs and the 

capability of remote power reset by output bank via internet 

or intranet connection (with RA-N option)

 . Ideal for CCTV 

applications in retail, health care, gaming, entertainment, 

transportation, government and educational facilities . The 

RA series delivers maximum flexibility for large multicamera 

projects by providing increased current capability and allow-

ing the user to select either 24 VAC or 28 VAC on each indi-

vidual output . For fused models each output is fused at 3A, 

but may be increased up to 7 .5A by the installer for powering 

high power devices such as heater/blowers or PTZs . Models 

ending in P are Class 2 Power Limited to 2 .5A each .

The 

FLEX

POWER

 

RD Series

 of DC power sup-

plies provide 12 and/or 24 VDC power at 25W - 500W of 

total power . They are available with 8, or 16 outputs and 

the 

capability of remote monitoring of the supply's pa-

rameters via internet or intranet connection (with RD-N  

option)

 . Ideal for Access Control, CCTV, Burglar, Fire, or 

Mass Notification applications . The RD series delivers max-

imum flexibility for large projects by providing increased 

current capability and allowing the user to select either 12 

VDC or 24 VDC on each output (dual supply units only) . For 

fused models each output is fused at 3A, but may be in-

creased up to 7 .5A by the installer for powering high power 

devices . Models ending in P are Class 2 Power Limited to 

2 .5A each .

Product Description

RA Series

RD Series

Содержание FlexPower RA100 Series

Страница 1: ...LifeSafety Power Inc PH 888 577 2898 TechSupport LifeSafetyPower com P03 032 Rev A06 RA RD Rackmount Installation Manual...

Страница 2: ...ly 4 1 4 Making the Wiring Connections RA and RD Series 6 FAI Input Usage 7 Section 2 Configuration and Usage 9 2 1 Removing the Faceplate of the Enclosure 9 2 2 Configuring the Outputs 9 2 3 Disablin...

Страница 3: ...ll wiring is routed and secured to prevent accidental open or short circuit conditions iThe system and any batteries if used should be tested at least once per year to ensure proper opera tion Regulat...

Страница 4: ...atures combine to significantly reduce installation and service costs Features include removable terminal strips for field wiring input and output surge suppression automotive blade fuses for im prove...

Страница 5: ...s or other appropriate support for heavy enclosures Keep heavier components near the bottom of the rack to reduce the risk of toppling of a top heavy rack NOTE For UL864 Installations the Rack Mount S...

Страница 6: ...h CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 FLT 1 2 3 4 5 6 7 8 3 3 3 3 3 3 3 3 1 B1 B2 JP1 2 3 CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 FLT 1 2 3 4 5 6 7...

Страница 7: ...ailable on these terminals Dual power supply models will have two DC1 outputs See Section 1 4 2 for more information DC2 This is an FAI controllable bulk power output with the full power of the associ...

Страница 8: ...to detect a missing bat tery set To enable battery presence detection place the BATDET jumper ON To disable battery presence detection remove the BATDET jumper or place it on only one pin See 2 in Fi...

Страница 9: ...h GND Battery DETECT Voltage SELECT 230VAC jumper Figure 3 Configuring the Internal FPO Power Supplies in an RD Series Supply Figure 4 FPO 230VAC jumper location AC Input cut jumper for 230VAC cut jum...

Страница 10: ...unaffected by the FAI input DC2 DC2 The DC2 output may optionally be controlled by the FAI input The full current of the FPO is available on these terminals The DC2 output may be set to power up when...

Страница 11: ...Input is achieved by placing a NC contact across the two L terminals The FAI may be activated by any of the methods listed FAI Deactivates when the input is deactivated AND the NC Latching contact is...

Страница 12: ...ut will damage the system and void the warranty 1 4 4 Ethernet Connection Optional RA and RD models with a model number ending in N con tain a Netlink communication ethernet module The Netlink allows...

Страница 13: ...To set the operation of the FAI controlled outputs see Section 1 3 6 B1 Left Continuous Output No FAI control B2 Right FAI Controlled Output RD Series Dual Supply Models Each output is configurable f...

Страница 14: ...these fields are not accurate measurements and only show the presence of voltage An approximate reading may be deter mined by multiplying the shown voltage by 0 71 Fault Notification Fault conditions...

Страница 15: ...ll Load No Batt 88 120VAC 60Hz In Full Load No Batt 89 120VAC 60Hz In Full Load No Batt Battery Size Type 4 40AH Lead Acid or Gel Cell 4 80AH Lead Acid or Gel Cell 4 80AH Lead Acid or Gel Cell Charge...

Страница 16: ...ad No Batt 88 120VAC 60Hz In Full Load No Batt 89 120VAC 60Hz In Full Load No Batt Battery for EACH internal supply Size Type 4 40AH Lead Acid or Gel Cell 4 80AH Lead Acid or Gel Cell 4 80AH Lead Acid...

Страница 17: ...max 3A per output 7 5A zone max 3A per output 7 5A zone max 3A per output 7 5A zone max Fuse Ratings Fused Models ATM 3A 7 5A Max ATM 3A 7 5A Max ATM 3A 7 5A Max ATM 3A 7 5A Max BTU Output BTU 68 102...

Страница 18: ...ty Power or its distributors be liable for any incidental indirect or consequential damages arising from the sale resale use or misuse of the product Specifications are subject to change without notic...

Отзывы: