RA Series, RD Series Rackmount Installation Manual

10

11

Specifications

Section 3 – Specifications

3 .1  Electrical Specifications

RD Series DC Power Supplies - 

Single Voltage

Specifications

RD75 Series

RD150 Series

RD250 Series

AC Input

Voltage

120/230VAC 

±15% at 50-60Hz

120/230VAC 

±15% at 50-60Hz

120/230VAC 

±15% at 50-60Hz

Power

100 Watts

200 Watts

300 Watts

Standby

Current

100mA

100mA

100mA

Rated Current for UL603 Proprietary 

Alarm Installations

Current

1 .25A maximum from 

all circuits in system

2 .5A maximum from all 

circuits in system

2 .5A maximum from all 

circuits in system

DC Output at 12V Setting

Voltage

12 .5V ±0 .5V nominal

12 .5V ±0 .5V nominal

12 .5V ±0 .5V nominal

Max Current

6A

12A

20A

Ripple

120mV

120mV

120mV

Regulation

±2%

±2%

±2%

Efficiency

85% (120VAC  

60Hz In, Full Load, No 

Batt)

88% (120VAC  

60Hz In, Full Load, No 

Batt)

89% (120VAC  

60Hz In, Full Load, No 

Batt)

DC Output at 24V Setting

Voltage

25 .0V ±0 .5V nominal

25 .0V ±0 .5V nominal

25 .0V ±0 .5V nominal

Max Current

3A

6A

10A

Ripple

120mV

120mV

120mV

Regulation

±2%

±2%

±2%

Efficiency

85% (120VAC  

60Hz In, Full Load, No 

Batt)

88% (120VAC  

60Hz In, Full Load, No 

Batt)

89% (120VAC  

60Hz In, Full Load, No 

Batt)

Battery

Size & Type

4-40AH Lead Acid  

or Gel Cell

4-80AH Lead Acid  

or Gel Cell

4-80AH Lead Acid  

or Gel Cell

Charge Current

1A (±10%) Maximum 

(Adjustable via  

PowerCom Software)

2A (±10%) Maximum 

(Adjustable via  

PowerCom Software)

2A (±10%) Maximum 

(Adjustable via  

PowerCom Software)

Fuse Ratings

DC1 (Internal)

ATM 7 .5A

ATM 15A

ATM 30A

DC2 (Internal)

ATM 7 .5A

ATM 15A

ATM 30A

Battery (Internal)

ATM 7 .5A

ATM 15A

ATM 30A

Distributed Zones 

(Fused Models)

ATM 3A

ATM 3A

ATM 3A

BTU Output

BTU

33

66

109

Fault Setpoints

Low AC

95V (±6%)

95V (±6%)

95V (±6%)

Earth GND

2000 Ohms

2000 Ohms

2000 Ohms

Output Voltage

±10% of nominal

±10% of Nominal

±10% of Nominal

Batt Voltage

±10% of nominal

±10% of Nominal

±10% of Nominal

Batt Presence

6–15V (12V Setting), 

11–29V (24V Setting)

6–15V (12V Setting), 

11–29V (24V Setting)

6–15V (12V Setting), 

11–29V (24V Setting)

Fault Relay Contacts

AC FLT

1A at 24VDC

1A at 24VDC

1A at 24VDC

SYS FLT

1A at 24VDC

1A at 24VDC

1A at 24VDC

Distributed Outputs

Count

2, 8, or 16

2, 8, or 16

2, 8, or 16

Fused

3A (7 .5A max with fuse 

change)

3A (7 .5A max with fuse 

change)

3A (7 .5A max with fuse 

change)

Models ending in "P"

2 .5A (PTC)

2 .5A (PTC)

2 .5A (PTC)

Содержание FlexPower RA100 Series

Страница 1: ...LifeSafety Power Inc PH 888 577 2898 TechSupport LifeSafetyPower com P03 032 Rev A06 RA RD Rackmount Installation Manual...

Страница 2: ...ly 4 1 4 Making the Wiring Connections RA and RD Series 6 FAI Input Usage 7 Section 2 Configuration and Usage 9 2 1 Removing the Faceplate of the Enclosure 9 2 2 Configuring the Outputs 9 2 3 Disablin...

Страница 3: ...ll wiring is routed and secured to prevent accidental open or short circuit conditions iThe system and any batteries if used should be tested at least once per year to ensure proper opera tion Regulat...

Страница 4: ...atures combine to significantly reduce installation and service costs Features include removable terminal strips for field wiring input and output surge suppression automotive blade fuses for im prove...

Страница 5: ...s or other appropriate support for heavy enclosures Keep heavier components near the bottom of the rack to reduce the risk of toppling of a top heavy rack NOTE For UL864 Installations the Rack Mount S...

Страница 6: ...h CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 FLT 1 2 3 4 5 6 7 8 3 3 3 3 3 3 3 3 1 B1 B2 JP1 2 3 CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 FLT 1 2 3 4 5 6 7...

Страница 7: ...ailable on these terminals Dual power supply models will have two DC1 outputs See Section 1 4 2 for more information DC2 This is an FAI controllable bulk power output with the full power of the associ...

Страница 8: ...to detect a missing bat tery set To enable battery presence detection place the BATDET jumper ON To disable battery presence detection remove the BATDET jumper or place it on only one pin See 2 in Fi...

Страница 9: ...h GND Battery DETECT Voltage SELECT 230VAC jumper Figure 3 Configuring the Internal FPO Power Supplies in an RD Series Supply Figure 4 FPO 230VAC jumper location AC Input cut jumper for 230VAC cut jum...

Страница 10: ...unaffected by the FAI input DC2 DC2 The DC2 output may optionally be controlled by the FAI input The full current of the FPO is available on these terminals The DC2 output may be set to power up when...

Страница 11: ...Input is achieved by placing a NC contact across the two L terminals The FAI may be activated by any of the methods listed FAI Deactivates when the input is deactivated AND the NC Latching contact is...

Страница 12: ...ut will damage the system and void the warranty 1 4 4 Ethernet Connection Optional RA and RD models with a model number ending in N con tain a Netlink communication ethernet module The Netlink allows...

Страница 13: ...To set the operation of the FAI controlled outputs see Section 1 3 6 B1 Left Continuous Output No FAI control B2 Right FAI Controlled Output RD Series Dual Supply Models Each output is configurable f...

Страница 14: ...these fields are not accurate measurements and only show the presence of voltage An approximate reading may be deter mined by multiplying the shown voltage by 0 71 Fault Notification Fault conditions...

Страница 15: ...ll Load No Batt 88 120VAC 60Hz In Full Load No Batt 89 120VAC 60Hz In Full Load No Batt Battery Size Type 4 40AH Lead Acid or Gel Cell 4 80AH Lead Acid or Gel Cell 4 80AH Lead Acid or Gel Cell Charge...

Страница 16: ...ad No Batt 88 120VAC 60Hz In Full Load No Batt 89 120VAC 60Hz In Full Load No Batt Battery for EACH internal supply Size Type 4 40AH Lead Acid or Gel Cell 4 80AH Lead Acid or Gel Cell 4 80AH Lead Acid...

Страница 17: ...max 3A per output 7 5A zone max 3A per output 7 5A zone max 3A per output 7 5A zone max Fuse Ratings Fused Models ATM 3A 7 5A Max ATM 3A 7 5A Max ATM 3A 7 5A Max ATM 3A 7 5A Max BTU Output BTU 68 102...

Страница 18: ...ty Power or its distributors be liable for any incidental indirect or consequential damages arising from the sale resale use or misuse of the product Specifications are subject to change without notic...

Отзывы: