Netlink Installation and Operation Manual
34
35
Installation and Operation
19
NS2 - ADC Output (ADC1 & ADC2)
This connector provides voltage outputs for measure-
ment by the Netlink board, indicating presence of volt-
age on SB1-1 and SB1-2 . Using the supplied cable, this
connects to the ADC Input of the Netlink board (J15) .
The voltages indicated are not accurate and are only for
indication of presence of voltage . Place jumper J9 on
the Netlink board ON when using this output .
20
NS2 - Buss Inputs - Power Source 1 (B1-1 & B2-1)
These faston connectors are the B1 and B2 power in-
puts to the NS2 for power source #1 . Typically, in a
LifeSafety Power FPA system, this would be the blue
and orange wires from Transformer #1 . The power re-
turn (brown wire in an FPA System) connects to the
BR1 faston - See #20 .
21
NS2 - Buss Inputs - Power Source 2 (B1-2 & B2-2)
These faston connectors are the B1 and B2 power in-
puts to the NS2 for power source #2 . Typically, in a
LifeSafety Power FPA system, this would be the blue
and orange wires from Transformer #2 . The power re-
turn (brown wire in an FPA System) connects to the
BR2 faston - See #20 .
22
NS2 - Buss Inputs - Power Returns (BR1 & BR 2)
These are the power returns for the Buss Inputs . See #18
and #19 . Typically, in a LifeSafety Power FPA system,
these would connect to the brown secondary wires of the
transformers .
23
NS2 - Buss Outputs - Power Returns (SBR1 & SBR2)
These are the switched power returns out to the BR
terminals of the A8 distribution boards in a LifeSafety
Power FPA system .
24
NS2 - Buss Outputs - Power Source 2 (SB1-2 & SB2-2)
These are the switched B1 and B2 outputs from pow-
er source 2 . When the control output #2 of the Netlink
board is activated, power will be removed from these
outputs . Typically, these are connected to the B1 and B2
inputs of the A8 distribution boards in a LifeSafety power
FPA system . The BR of the A8 connects to the SBR2 fas-
ton - See #21 .
25
NS2 - Buss Outputs - Power Source 1 (SB1-1 & SB2-1)
These are the switched B1 and B2 outputs from pow-
er source 1 . When the control output #1 of the Netlink
board is activated, power will be removed from these
outputs . Typically, these are connected to the B1 and B2
inputs of the A8 distribution boards in a LifeSafety power
FPA system . The BR of the A8 connects to the SBR1 fas-
ton - See #21 .
26
NS2 - Control Inputs (J9)
This is the control input from the Netlink board, allow-
ing control of the power to the outputs via the Netlink's
web interface . Using the cable with two 2-pin plugs,
connect between this connector and J10 on the Netlink
board - See #13 in Section 1 .2 .
27
NS2 - Netlink Power Output (+12V-)
This is the power output for powering the Netlink board
in an AC-only system . The NS2 converts AC power from
the buss inputs to regulated DC power for the Netlink
board . Using the supplied cable, connect this connec-
tor to the V+/V- input of the Netlink .
A2 .2 NS2 Module Overview
Содержание FlexPower Netlink NL2
Страница 14: ...Netlink Installation and Operation Manual 10 Figure 2 4 Typical Netlink Home Page ...
Страница 24: ...Netlink Installation and Operation Manual 20 Figure 2 11 Typical Reporting Page ...
Страница 31: ...27 Installation and Operation Figure 3 5 Battery Test in Progress Figure 3 6 Battery Test Results ...
Страница 33: ...29 Installation and Operation Figure 3 7 Typical Power Supply Page bottom portion ...