ERV Questions & Answers

What is the difference between an HRV 
and an ERV?

The core in an HRV (Heat Recovery Ventilator) trans-
fers heat from one air stream to the other. This is called
sensible heat. The term ERV (Energy Recovery
Ventilator) is usually used to describe a unit with an
enthalpic core that transfers moisture as well as heat
from one air stream to the other. This (moisture trans-
fer) is called 

latent heat.

Enthalpic - what does it mean?

Enthalpy is the term used to describe the energy con-
tent of air. This energy is a combination of the sensible
and latent heat. Therefore, a core which transfers ener-
gy is called an enthalpic core.

Is an ERV better than an HRV?

NOT NECESSARILY!! In cold climates such as most of
North America, an HRV works better than an ERV. This
is because the air inside the home during the winter
months will be more humid than the outside air. An ERV
would transfer the latent heat (humidity) from the
exhaust air back into the incoming airstream. This will
aggravate moisture problems in the home and encour-
age the growth of mold and mildew. If the air in the
home is too dry for comfort, an ERV will not help. A
humidifier should be used to increase the humidity to a
comfortable level.

Where do you use an ERV instead 
of an HRV?

An ERV is recommended for warm, humid areas with
heavy air conditioning use. As there is no defrost in an
ERV it is not recommended for areas where the temper-
ature drops below   -4

˚

C (25

˚

F)

Why transfer moisture in the summer 
(cooling season)?

The enthalpic core will allow moisture to be transferred
from a humid air flow to a dry air flow. This property is
useful in the cooling season if an air conditioning sys-
tem is used to lower the indoor humidity. You will then
have dry, cool air in the exhaust of the ERV, and warm
humid air in the supply stream. With these conditions,
the ERV will be able to transfer the moisture and heat of
the supply air to the exhaust air. In this way, the ERV
will supply to the home air which is cooler and drier than
outside. Remember that an ERV is not a dehumidifier,
and on its own will not take moisture out of the air.

So why use an ERV?

A properly operating air conditioner will not only lower
the temperature in your house, but will also lower the
humidity level. This prevents an uncomfortable cold and

damp situation. In fact, about 2/3 of the energy used by
the air conditioner system is to remove moisture.
Therefore, when ventilating in the summer, less mois-
ture brought into the home means less work for the air
conditioner, and energy savings for you.

During the winter, an ERV recovers some humidity
from the exhaust air, reducing the need for humidifica-
tion, if the required ventilation rate would make the
home too dry.

What's the difference between this type of
core and a rotary type?

Here's a list of characteristics of the fixed plate core.

1. No rotating parts, so maintenance is easy and the

unit lasts a long time.

2. It is very flexible in terms of installation.
3. The core can easily be changed.
4. Because the supply and exhaust air streams are

completely separate, there is very little cross leakage

of any dust or germs.

Can the core become clogged with dust?

Because the surface of the core is a turbulent flow
area, dust sticks to it easily; however, because the
inside of the element is a laminar flow area, virtually no
dust sticks to it.

What is the maintenance?

About once a year you should use a vacuum cleaner to
remove the dust from the core's surface. DO NOT
WASH WITH WATER!!

Is an air filter needed?

To prevent clogging of the core, an air filter should
always be installed on the supply and exhaust sides of
the core.

How much ventilation do I need?

During seasons when your windows and doors are
closed, the ERV should operate continuously when the
dwelling is occupied, and either continuously or intermit-
tently when not occupied.

For most installations the ERV will normally be set to
operate continuously on low speed with the option of
going to high speed as the need arises. For example; if
you are entertaining and there is a large number of
people present (some may be smoking), the unit
should be switched to high speed.

Your ERV may be equipped with automatic or manual
switches, but all ERVs will have a manual speed control
override.

Содержание 1200ERV

Страница 1: ... Recovery Ventilator ERV by using the balancing procedure in this manual It is always important to assess how the operation of any Energy Recovery Ventilator may interact with vented combustion equipment ie Gas Furnaces Oil Furnaces Wood Stoves etc NEVER install an Energy Recovery Ventilator in a situ ation where its normal operation lack of operation or partial failure may result in the backdraft...

Страница 2: ...tallation 22 26 Maintenance Troubleshooting Your ERV 27 Maintenance Routine 28 Wiring Diagram 29 31 TFP Information 32 INTRODUCTION The LIFEBREATH Enthalpic Core Energy Recovery Ventilator ERV is designed for warm humid regions and it uses the vapour transmission technology to transfer sensible and latent heat to the cooler drier air stream During the cooling season humidity drawn in from the outs...

Страница 3: ...hat an ERV is not a dehumidifier and on its own will not take moisture out of the air So why use an ERV A properly operating air conditioner will not only lower the temperature in your house but will also lower the humidity level This prevents an uncomfortable cold and damp situation In fact about 2 3 of the energy used by the air conditioner system is to remove moisture Therefore when ventilating...

Страница 4: ...8 SAVINGS WITH ERV ELECTRIC 69 86 133 61 179 89 228 79 285 22 76 20 SAVINGS WITH HRV ELECTRIC 65 05 85 68 192 65 257 23 322 46 110 80 SAVINGS WITH ERV FOSSIL 65 93 150 51 133 20 156 36 191 05 103 28 SAVINGS WITH HRV FOSSIL 64 52 129 98 129 32 154 00 187 35 102 85 TORONTO MONTREAL WINNIPEG HRV ELECTRIC HEAT 145 30 155 04 189 52 ERV ELECTRIC HEAT 179 78 196 74 253 93 HRV FOSSIL FUEL HEAT 82 72 84 87...

Страница 5: ... Total 34 ASHRAE requirement 20 cfm 10L s per person Ventilation required 34 x 20 680 cfm 320 L s Bar or Tavern Seats 50 Employees 7 Total 57 ASHRAE requirement 30 cfm 15L s per person Ventilation required 57 x 30 1710 cfm 855 L s Bingo Hall Customers 180 Staff 20 Total 200 ASHRAE requirement 30 cfm 15L s per person Ventilation required 200 x 30 6000 cfm 3000 L s Classroom and School Portables Sea...

Страница 6: ...76 0 5 125 Pa 145 68 Sensible Effectiveness 110 L s 55 cfm CSA C439M 80 Sensible Efficiency 110L s 55 cfm 0O C 32 F 70 Sensible Efficiency 110 L s 55 cfm 25O C 13 F 55 VAC 60HZ 120 WATTS Low speed 80 Amp rating 1 4 STALE AIR TO OUTSIDE FRESH AIR FROM OUTSIDE STALE AIR FROM INSIDE FRESH AIR TO INSIDE 14 3 4 375 19 483 DIMENSIONS 200 ERV inches mm All Duct Connections 6 150mm FILTERS BLOWERS NOTE Fr...

Страница 7: ...00 Pa 160 76 0 5 125 Pa 145 68 Sensible Effectiveness 110 L s 55 cfm CSA C439M 80 Sensible Efficiency 110L s 55 cfm 0O C 32 F 70 Sensible Efficiency 110 L s 55 cfm 25O C 13 F 55 VAC 60HZ 120 WATTS Low speed 80 Amp rating 1 4 STALE AIR TO OUTSIDE STALE AIR FROM HOUSE FRESH AIR TO INSIDE 14 3 4 375 19 483 DIMENSIONS 200 ERVD inches mm All Duct Connections 6 150mm FILTERS BLOWERS NOTE Front clearance...

Страница 8: ...mm EXTERIOR DUCT CONNECTION SIDE MOUNTING POINTS DRAIN CONNECTION DIMENSIONS 500 ERV inches mm EXHAUST AIR TO OUTSIDE EXHAUST AIR FROM BUILDING SUPPLY AIR TO BUILDING SUPPLY AIR FROM OUTSIDE NOTE Service clearance is 30 in 760 mm DEFROST OPTIONS 99 104 Digital Electronic Timer 20 40 60 min 3 wire 99 105 Programmable Ventilation Control includes Programmable Time Clock Dehumidistat and Air Sentry 9...

Страница 9: ... 5 year warranty on the energy recovery cores and 2 year replacement parts warranty It is recommended for regions where the temperature does not fall below 25 F 4 C DATE _________________________________________ PROJECT ______________________________________ MECHANICAL CONTRACTOR __________________________ TI 131 9807 511 McCormick Blvd London ON N5W 4C8 Phone 519 457 1904 Fax 519 457 1676 E mail ...

Страница 10: ...m CONTROLS DISCHARGE SIDE EXHAUST AIR TO OUTSIDE EXHAUST AIR FROM BUILDING SUPPLY AIR TO BUILDING SUPPLY AIR FROM OUTSIDE NOTE Service clearance is 30 in 760 mm from front access doors HEAT RECOVERY VENTILATORS HRVs 10 3 8 263 mm 10 3 8 263 mm OPTIONS 99 101 Sixty Minute Remote Timer 99 130 Remote Wall Mount Dehumidistat Control 24 VAC only W white or B beige All units conform to CSA and UL standa...

Страница 11: ...TERS BLOWERS NOTE Front clearance of 25 inches 635 mm is recommended for servicing unit MOTOR 31 787 Figure 2 The Duct Ports There are four duct ports on the ERV 1 Fresh air intake port It is connected to the exterior air intake hood using insulated duct with a vapour barrier 2 The fresh air supply port is connected to the fresh air diffuser which is typically located in the major living areas or ...

Страница 12: ...ssor automatically activates the defrost system only as it is needed To be an efficient heat recovery device the ERV must effectively provide for core defrost as well as providing efficient heat exchange As outdoor conditions cool the temperature sensor thermistor tracks the supply air tem perature The thermistor then sends its signal to the micro processor circuit board which initiates only the d...

Страница 13: ...f Flashing Green LED and Yellow LED to indicate speed ERV will operate in ventilation mode at speed selected for 20 minutes and OFF for 40 minutes Recirculation Steady Red LED and Yellow LED to indicate Speed ERV Note Not available on all HRVs will operate in recirculate mode at the selected speed Optional remote controls will override unit into high speed ventilate mode To select speed Momentaril...

Страница 14: ...107W PART NO 99 104 Connects to RED GREEN and YELLOW terminals PROGRAMMABLE VENTILATION CONTROLLER PVC LOCATION Hallway kitchen office work place connect 1 unit only Advanced digital remote Digital dehumidistat Full fan speed control AIR SENTRY Air Quality Sensor built in Recirculation mode on compatible HRVs 7 day 24 hour programmable timer Digital display and status lights 100 30 m maximum wire ...

Страница 15: ...e location into a dou ble gang electrical enclosure or side by side One should be labeled on off and the other should be labeled high low Off 10 20 30 40 50 60 DEHUMIDISTAT VENTILATION CONTROL DVC PART NO 99 116 Turns ERV ON OFF Dehumidistat increases ventilation when required Speed Selection and Controls DEHUMIDISTAT PART NO 99 130W Provides high speed ventilation when humidity level exceeds sett...

Страница 16: ...reduce the possibility of noise resonance or harmonics therefore using the full length of the strap between the ERV and the floor joists is recommended Electrical The ERV should be plugged into a standard designated 120VAC electrical outlet with ground It is not recom mended that an extension cord be used for this appliance If further wiring is required then a licensed electrician should make all ...

Страница 17: ...t will seal the inner flexible duct to both the ERV port and the weatherhood prior to clamping To minimize air flow restriction the flexible insulated duct that connects the two outside weatherhoods to the ERV should be stretched tightly and be as short as possible Twisting or folding the duct will severely restrict air flow See Figure 6 for the recommended connection of flexible insu lated ducts ...

Страница 18: ...hich can then be drawn into the return ducting and circulated throughout the dwelling This method should be used only in cases where the furnace and water heater are directly vented appliances with 100 outside air for combus tion supplied directly to the equipment Stale Air Exhaust System The stale air exhaust system is used to draw air from the points in the house where the worst air quality prob...

Страница 19: ...or bends These are recommended distances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a magnehelic gauge or other manometer capable of reading from 0 to 0 25 in 0 62 Pa of water preferably to 3 digits of resolution The tube coming out of the top of the pitot is connected to the high pressure side of the gauge The tube coming out of the sid...

Страница 20: ... a vapour barrier Note ERV exhausts from kitchen and or bathrooms or other central location to outdoors ERV supplies outdoor air directly to each bedroom to each floor without a bedroom and to the principal living areas ERV shown is for illustrative purposes only Actual port location varies depending on model See schematic diagrams on page 4 Figure 7 Round adjustable TECHGRILLES Optional controls ...

Страница 21: ...ust be confirmed on site using the balancing procedure found in this manual Return Air Return Air 40 inches minimum 1m separation 3 min recommended DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN Combustion or Electric Forced Air Furnace Balancing damper in both air streams Outdoors Unit is normally balanced on HIGH speed with furnace blower ON EXHAUST AIR from various pa...

Страница 22: ...y Air flow will be restricted by undersized ducting use of too many elbows tees bends etc Always try to keep duct runs as short and straight as possible NOTE Fully insulated ducting with an integral vapour barrier must be used on all runs passing through unconditioned areas in order to avoid condensation problems and energy losses from the air steams All joints must be airtight sealed and impervio...

Страница 23: ... and wrapped with a quality duct tape to prevent leak age We recommend aluminum foil tape Stale Air Return System The stale air return system is used to draw air from the points in the building where the worst air quality problems occur Balancing dampers and or adjustable grilles are rec ommended on all return air lines which are used during installation to help balance the draw from different are...

Страница 24: ...rs are recom mended TECHGRILLES are round efficient sound absorbing devices available in 4 5 6 and 8 100 125 150 and 200 mm models The Integrated HVAC System The ERV has become an integral component of the HVAC system Figure A shows an ERV unit providing fresh air directly to the return air plenum of a rooftop unit In the balanced airflow system the ERV exhaust removes stale room air eg from lunch...

Страница 25: ...IR DUCT or BREATHER T FRESH AIR SUPPLY STALE AIR EXHAUST ROOFTOP UNIT A B B D B D ROOFTOP UNIT ERV FRESH AIR SUPPLY SUPPLY DUCTWORK CEILING RETURN AIR PLENUM ROOF DECK STALE AIR EXHAUST ERV UNIT FRESH AIR SUPPLY STALE AIR EXHAUST ECONOMIZER DISABLED B A 12 BREATHER SPACE B D B D Figure 6A Figure 6B ...

Страница 26: ...plied by others Vibration Isolators Supplied by others Figure 7B Curb Mounted Mount unit on wooden or metal curb assembly Unit must be raised an adequate height for installation and slope of drain lines Curb is wood or metal Supplied by others May be anchored to floor leaving space for drain connections Vibration Isolators Supplied by others PVC Support Straps Supplied by others Figure 7C Suspende...

Страница 27: ...d clean filters Remove and clean core vacuum or blow out do not wash Open and adjust grilles Open and adjust dampers Have electrician check voltage Have HVAC contractor check ducting Increase speed setting Have HVAC contractor re balance system Relocate air supply grilles so airflow does not affect occupant Adjust grille so that airflow is entrained along wall or ceiling Note closing the grille to...

Страница 28: ...ters Four Times a Year The standard filters equipped with your ERV are removable and washable A simply open access door and slide core out refer to core maintenance B remove filter clips Note approximate location and attachment of clips so that they can be returned the same way C once clips are removed filters can be taken off the core to be rinsed with water or a combination of soap and water D t...

Страница 29: ...R DETAIL 3 2 2 1 1 5 6 4 P5 P6 P5 PIN 1 BLUE PIN 4 RED PIN 2 YELLOW PIN 5 WHITE PIN 3 BROWN PIN 6 BLACK P6 PIN 1 GREEN PIN 2 GREEN PLUG IN CONNECTOR AUTO TRANSFORMER FAN MOTOR DETAILS TI 89A NE 0006 2 1 P6 DEFROST DETAILS PLUG IN CONNECTOR P1 BLK RED P1 4 3 2 1 PIN 1 BLACK PIN 2 ORANGE PIN 3 RED PIN 4 SPARE PCB PLUG IN BI DIRECTIONAL DAMPER MOTOR ORANGE RED ORANGE BLK MAXTOP ONLY PIN 1 RED PIN 2 O...

Страница 30: ... DETAIL MICRO PROCESSOR BOARD DEHUMIDISTAT P2 P5 INTERNAL IMPORTANT Control Low Voltage is 12VAC DO NOT CONNECT EXTERNAL POWER SOURCES TO UNIT SEE DEFROST DETAIL WARNING 750 ma MAX FUSE AUTO TRANSFORMER DETAIL 3 2 2 1 1 5 6 4 P5 P6 P5 PIN 1 BLUE PIN 4 RED PIN 2 YELLOW PIN 5 WHITE PIN 3 BROWN PIN 6 BLACK P6 PIN 1 GREEN PIN 2 GREEN PLUG IN CONNECTOR AUTO TRANSFORMER TI 126 NE 0005 2 1 P6 WIRING DIAG...

Страница 31: ...INAL BLOCK TERMINAL BLOCK BROWN BLUE WHITE BLUE BLUE BLUE BLUE BLACK BLACK BLACK BLACK WHITE YELLOW RED RED RED RED BLACK BROWN WHITE WHITE WHITE BLACK BLUE RED BLACK BLACK 3 SPEED CONTROL INTAKE CCW ON OFF SWITCH 24V TERMINAL BOARD COMMON WHITE LINE NEUT BLACK 110 VAC POWER SUPPLY GND HIGH ON OFF 1 1 1 2 2 2 3 3 3 L G R E E N EXHAUST CW UPPER FAN MOTOR LOWER FAN MOTOR GREEN GND GND GREEN FAN MOTO...

Страница 32: ...or free standing Very quiet EBM high efficiency motor standard 120 VAC Tested by an independent lab to ASHRAE 52 1 the accepted standard in air cleaning Today s tightly built homes need help They require that the air inside be cleaned constantly to prevent the development of asthma and allergies The TFP Air Cleaner can remove 97 5 of airborne particles in 24 hours in a modern tight home Now you ca...

Отзывы: