background image

24

Fresh Air Supply System

The fresh air supply ductwork from the ERV may be
directly connected to the return air duct of the forced air
system. Check the air flow balance of the ERV with the
air handler blower both “ON” and “OFF” to determine that
it does not imbalance the ERV more than 10%. Also, it is
advisable to include a short length of flex duct or other
non-metallic connector in this hard ducted line in order to
keep the ERV acoustically isolated and separately
grounded (electrically) from the air handler. This will
avoid a possible shock hazard to service people if a short
to ground develops in one of the devices.

It may be necessary to install a separate fresh air supply
ductwork system if the heating is other than forced air.

When installing an ERV, the designer and installer should
be aware of local codes that may require smoke detec-
tors and/or firestats in the HVAC or ERV ductwork.

Because an ERV is designed to bring fresh air into the
building, structures may require supply voltage interrupt
when smoke or flame sensors are triggered, or when a
central fore alarm system is activated.

Supply air grilles may be ceiling or high wall mounted.
Avoid locating incoming fresh air grilles that could cause
a direct draft on the occupants.

The use of balancing dampers or adjustable grilles to bal-
ance the flow rates into various rooms is recommended.

The use of balancing dampers or adjustable grilles as
supply air diffusers and air exhaust covers are recom-
mended. TECHGRILLES™ are round, efficient, sound
absorbing devices available in 4”, 5”, 6” and 8” (100, 125,
150, and 200 mm) models.

The Integrated HVAC System

The ERV has become an integral component of the
HVAC system. Figure A shows an ERV unit providing
fresh air directly to the return air plenum of a rooftop unit.

In the balanced airflow system, the ERV exhaust
removes stale room air (eg. from lunch room, storage or
copy area) and returns to the space an equal amount of
fresh outdoor air, making the use of an economizer obso-
lete in conjunction with an ERV.

Many buildings have ceiling return air plenum as in
Figure B. Fresh air from the ERV can be introduced
directly into the ceiling space but this should occur near
the air handler’s intake.

By operating the ERV on a 24 hour/7 day battery backed
timer the unit can be set to operate only when occupancy
or indoor conditions require the air exchange.

In installations where it is satisfactory to provide gener-
al exhaust from the space, the air to be exhausted may
be taken directly from the return air plenum to the ERV
as it is drawn back to the air handler. Fresh air supplied
by the ERV is then introduced directly into the return air
plenum but at a location closer to the air handler. The
air handler would have a constant running blower to
effectively distribute the fresh air and remove the stale
air. Balancing dampers would be located in both the
ERV supply and exhaust ducts between the return air
plenum and the ERV.
NOTE: At no time should the air handler T.E.S.P. on
the return duct exceed that of the ERV. Supply Air
T.E.S.P.

AIR FLOW

SUPPLY

AIR FLOW
EXHAUST

Figure

TECHGRILLE™ (optional) schematic

Содержание 1200ERV

Страница 1: ... Recovery Ventilator ERV by using the balancing procedure in this manual It is always important to assess how the operation of any Energy Recovery Ventilator may interact with vented combustion equipment ie Gas Furnaces Oil Furnaces Wood Stoves etc NEVER install an Energy Recovery Ventilator in a situ ation where its normal operation lack of operation or partial failure may result in the backdraft...

Страница 2: ...tallation 22 26 Maintenance Troubleshooting Your ERV 27 Maintenance Routine 28 Wiring Diagram 29 31 TFP Information 32 INTRODUCTION The LIFEBREATH Enthalpic Core Energy Recovery Ventilator ERV is designed for warm humid regions and it uses the vapour transmission technology to transfer sensible and latent heat to the cooler drier air stream During the cooling season humidity drawn in from the outs...

Страница 3: ...hat an ERV is not a dehumidifier and on its own will not take moisture out of the air So why use an ERV A properly operating air conditioner will not only lower the temperature in your house but will also lower the humidity level This prevents an uncomfortable cold and damp situation In fact about 2 3 of the energy used by the air conditioner system is to remove moisture Therefore when ventilating...

Страница 4: ...8 SAVINGS WITH ERV ELECTRIC 69 86 133 61 179 89 228 79 285 22 76 20 SAVINGS WITH HRV ELECTRIC 65 05 85 68 192 65 257 23 322 46 110 80 SAVINGS WITH ERV FOSSIL 65 93 150 51 133 20 156 36 191 05 103 28 SAVINGS WITH HRV FOSSIL 64 52 129 98 129 32 154 00 187 35 102 85 TORONTO MONTREAL WINNIPEG HRV ELECTRIC HEAT 145 30 155 04 189 52 ERV ELECTRIC HEAT 179 78 196 74 253 93 HRV FOSSIL FUEL HEAT 82 72 84 87...

Страница 5: ... Total 34 ASHRAE requirement 20 cfm 10L s per person Ventilation required 34 x 20 680 cfm 320 L s Bar or Tavern Seats 50 Employees 7 Total 57 ASHRAE requirement 30 cfm 15L s per person Ventilation required 57 x 30 1710 cfm 855 L s Bingo Hall Customers 180 Staff 20 Total 200 ASHRAE requirement 30 cfm 15L s per person Ventilation required 200 x 30 6000 cfm 3000 L s Classroom and School Portables Sea...

Страница 6: ...76 0 5 125 Pa 145 68 Sensible Effectiveness 110 L s 55 cfm CSA C439M 80 Sensible Efficiency 110L s 55 cfm 0O C 32 F 70 Sensible Efficiency 110 L s 55 cfm 25O C 13 F 55 VAC 60HZ 120 WATTS Low speed 80 Amp rating 1 4 STALE AIR TO OUTSIDE FRESH AIR FROM OUTSIDE STALE AIR FROM INSIDE FRESH AIR TO INSIDE 14 3 4 375 19 483 DIMENSIONS 200 ERV inches mm All Duct Connections 6 150mm FILTERS BLOWERS NOTE Fr...

Страница 7: ...00 Pa 160 76 0 5 125 Pa 145 68 Sensible Effectiveness 110 L s 55 cfm CSA C439M 80 Sensible Efficiency 110L s 55 cfm 0O C 32 F 70 Sensible Efficiency 110 L s 55 cfm 25O C 13 F 55 VAC 60HZ 120 WATTS Low speed 80 Amp rating 1 4 STALE AIR TO OUTSIDE STALE AIR FROM HOUSE FRESH AIR TO INSIDE 14 3 4 375 19 483 DIMENSIONS 200 ERVD inches mm All Duct Connections 6 150mm FILTERS BLOWERS NOTE Front clearance...

Страница 8: ...mm EXTERIOR DUCT CONNECTION SIDE MOUNTING POINTS DRAIN CONNECTION DIMENSIONS 500 ERV inches mm EXHAUST AIR TO OUTSIDE EXHAUST AIR FROM BUILDING SUPPLY AIR TO BUILDING SUPPLY AIR FROM OUTSIDE NOTE Service clearance is 30 in 760 mm DEFROST OPTIONS 99 104 Digital Electronic Timer 20 40 60 min 3 wire 99 105 Programmable Ventilation Control includes Programmable Time Clock Dehumidistat and Air Sentry 9...

Страница 9: ... 5 year warranty on the energy recovery cores and 2 year replacement parts warranty It is recommended for regions where the temperature does not fall below 25 F 4 C DATE _________________________________________ PROJECT ______________________________________ MECHANICAL CONTRACTOR __________________________ TI 131 9807 511 McCormick Blvd London ON N5W 4C8 Phone 519 457 1904 Fax 519 457 1676 E mail ...

Страница 10: ...m CONTROLS DISCHARGE SIDE EXHAUST AIR TO OUTSIDE EXHAUST AIR FROM BUILDING SUPPLY AIR TO BUILDING SUPPLY AIR FROM OUTSIDE NOTE Service clearance is 30 in 760 mm from front access doors HEAT RECOVERY VENTILATORS HRVs 10 3 8 263 mm 10 3 8 263 mm OPTIONS 99 101 Sixty Minute Remote Timer 99 130 Remote Wall Mount Dehumidistat Control 24 VAC only W white or B beige All units conform to CSA and UL standa...

Страница 11: ...TERS BLOWERS NOTE Front clearance of 25 inches 635 mm is recommended for servicing unit MOTOR 31 787 Figure 2 The Duct Ports There are four duct ports on the ERV 1 Fresh air intake port It is connected to the exterior air intake hood using insulated duct with a vapour barrier 2 The fresh air supply port is connected to the fresh air diffuser which is typically located in the major living areas or ...

Страница 12: ...ssor automatically activates the defrost system only as it is needed To be an efficient heat recovery device the ERV must effectively provide for core defrost as well as providing efficient heat exchange As outdoor conditions cool the temperature sensor thermistor tracks the supply air tem perature The thermistor then sends its signal to the micro processor circuit board which initiates only the d...

Страница 13: ...f Flashing Green LED and Yellow LED to indicate speed ERV will operate in ventilation mode at speed selected for 20 minutes and OFF for 40 minutes Recirculation Steady Red LED and Yellow LED to indicate Speed ERV Note Not available on all HRVs will operate in recirculate mode at the selected speed Optional remote controls will override unit into high speed ventilate mode To select speed Momentaril...

Страница 14: ...107W PART NO 99 104 Connects to RED GREEN and YELLOW terminals PROGRAMMABLE VENTILATION CONTROLLER PVC LOCATION Hallway kitchen office work place connect 1 unit only Advanced digital remote Digital dehumidistat Full fan speed control AIR SENTRY Air Quality Sensor built in Recirculation mode on compatible HRVs 7 day 24 hour programmable timer Digital display and status lights 100 30 m maximum wire ...

Страница 15: ...e location into a dou ble gang electrical enclosure or side by side One should be labeled on off and the other should be labeled high low Off 10 20 30 40 50 60 DEHUMIDISTAT VENTILATION CONTROL DVC PART NO 99 116 Turns ERV ON OFF Dehumidistat increases ventilation when required Speed Selection and Controls DEHUMIDISTAT PART NO 99 130W Provides high speed ventilation when humidity level exceeds sett...

Страница 16: ...reduce the possibility of noise resonance or harmonics therefore using the full length of the strap between the ERV and the floor joists is recommended Electrical The ERV should be plugged into a standard designated 120VAC electrical outlet with ground It is not recom mended that an extension cord be used for this appliance If further wiring is required then a licensed electrician should make all ...

Страница 17: ...t will seal the inner flexible duct to both the ERV port and the weatherhood prior to clamping To minimize air flow restriction the flexible insulated duct that connects the two outside weatherhoods to the ERV should be stretched tightly and be as short as possible Twisting or folding the duct will severely restrict air flow See Figure 6 for the recommended connection of flexible insu lated ducts ...

Страница 18: ...hich can then be drawn into the return ducting and circulated throughout the dwelling This method should be used only in cases where the furnace and water heater are directly vented appliances with 100 outside air for combus tion supplied directly to the equipment Stale Air Exhaust System The stale air exhaust system is used to draw air from the points in the house where the worst air quality prob...

Страница 19: ...or bends These are recommended distances but the actual installation may limit the amount of straight duct The Pitot tube should be connected to a magnehelic gauge or other manometer capable of reading from 0 to 0 25 in 0 62 Pa of water preferably to 3 digits of resolution The tube coming out of the top of the pitot is connected to the high pressure side of the gauge The tube coming out of the sid...

Страница 20: ... a vapour barrier Note ERV exhausts from kitchen and or bathrooms or other central location to outdoors ERV supplies outdoor air directly to each bedroom to each floor without a bedroom and to the principal living areas ERV shown is for illustrative purposes only Actual port location varies depending on model See schematic diagrams on page 4 Figure 7 Round adjustable TECHGRILLES Optional controls ...

Страница 21: ...ust be confirmed on site using the balancing procedure found in this manual Return Air Return Air 40 inches minimum 1m separation 3 min recommended DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN Combustion or Electric Forced Air Furnace Balancing damper in both air streams Outdoors Unit is normally balanced on HIGH speed with furnace blower ON EXHAUST AIR from various pa...

Страница 22: ...y Air flow will be restricted by undersized ducting use of too many elbows tees bends etc Always try to keep duct runs as short and straight as possible NOTE Fully insulated ducting with an integral vapour barrier must be used on all runs passing through unconditioned areas in order to avoid condensation problems and energy losses from the air steams All joints must be airtight sealed and impervio...

Страница 23: ... and wrapped with a quality duct tape to prevent leak age We recommend aluminum foil tape Stale Air Return System The stale air return system is used to draw air from the points in the building where the worst air quality problems occur Balancing dampers and or adjustable grilles are rec ommended on all return air lines which are used during installation to help balance the draw from different are...

Страница 24: ...rs are recom mended TECHGRILLES are round efficient sound absorbing devices available in 4 5 6 and 8 100 125 150 and 200 mm models The Integrated HVAC System The ERV has become an integral component of the HVAC system Figure A shows an ERV unit providing fresh air directly to the return air plenum of a rooftop unit In the balanced airflow system the ERV exhaust removes stale room air eg from lunch...

Страница 25: ...IR DUCT or BREATHER T FRESH AIR SUPPLY STALE AIR EXHAUST ROOFTOP UNIT A B B D B D ROOFTOP UNIT ERV FRESH AIR SUPPLY SUPPLY DUCTWORK CEILING RETURN AIR PLENUM ROOF DECK STALE AIR EXHAUST ERV UNIT FRESH AIR SUPPLY STALE AIR EXHAUST ECONOMIZER DISABLED B A 12 BREATHER SPACE B D B D Figure 6A Figure 6B ...

Страница 26: ...plied by others Vibration Isolators Supplied by others Figure 7B Curb Mounted Mount unit on wooden or metal curb assembly Unit must be raised an adequate height for installation and slope of drain lines Curb is wood or metal Supplied by others May be anchored to floor leaving space for drain connections Vibration Isolators Supplied by others PVC Support Straps Supplied by others Figure 7C Suspende...

Страница 27: ...d clean filters Remove and clean core vacuum or blow out do not wash Open and adjust grilles Open and adjust dampers Have electrician check voltage Have HVAC contractor check ducting Increase speed setting Have HVAC contractor re balance system Relocate air supply grilles so airflow does not affect occupant Adjust grille so that airflow is entrained along wall or ceiling Note closing the grille to...

Страница 28: ...ters Four Times a Year The standard filters equipped with your ERV are removable and washable A simply open access door and slide core out refer to core maintenance B remove filter clips Note approximate location and attachment of clips so that they can be returned the same way C once clips are removed filters can be taken off the core to be rinsed with water or a combination of soap and water D t...

Страница 29: ...R DETAIL 3 2 2 1 1 5 6 4 P5 P6 P5 PIN 1 BLUE PIN 4 RED PIN 2 YELLOW PIN 5 WHITE PIN 3 BROWN PIN 6 BLACK P6 PIN 1 GREEN PIN 2 GREEN PLUG IN CONNECTOR AUTO TRANSFORMER FAN MOTOR DETAILS TI 89A NE 0006 2 1 P6 DEFROST DETAILS PLUG IN CONNECTOR P1 BLK RED P1 4 3 2 1 PIN 1 BLACK PIN 2 ORANGE PIN 3 RED PIN 4 SPARE PCB PLUG IN BI DIRECTIONAL DAMPER MOTOR ORANGE RED ORANGE BLK MAXTOP ONLY PIN 1 RED PIN 2 O...

Страница 30: ... DETAIL MICRO PROCESSOR BOARD DEHUMIDISTAT P2 P5 INTERNAL IMPORTANT Control Low Voltage is 12VAC DO NOT CONNECT EXTERNAL POWER SOURCES TO UNIT SEE DEFROST DETAIL WARNING 750 ma MAX FUSE AUTO TRANSFORMER DETAIL 3 2 2 1 1 5 6 4 P5 P6 P5 PIN 1 BLUE PIN 4 RED PIN 2 YELLOW PIN 5 WHITE PIN 3 BROWN PIN 6 BLACK P6 PIN 1 GREEN PIN 2 GREEN PLUG IN CONNECTOR AUTO TRANSFORMER TI 126 NE 0005 2 1 P6 WIRING DIAG...

Страница 31: ...INAL BLOCK TERMINAL BLOCK BROWN BLUE WHITE BLUE BLUE BLUE BLUE BLACK BLACK BLACK BLACK WHITE YELLOW RED RED RED RED BLACK BROWN WHITE WHITE WHITE BLACK BLUE RED BLACK BLACK 3 SPEED CONTROL INTAKE CCW ON OFF SWITCH 24V TERMINAL BOARD COMMON WHITE LINE NEUT BLACK 110 VAC POWER SUPPLY GND HIGH ON OFF 1 1 1 2 2 2 3 3 3 L G R E E N EXHAUST CW UPPER FAN MOTOR LOWER FAN MOTOR GREEN GND GND GREEN FAN MOTO...

Страница 32: ...or free standing Very quiet EBM high efficiency motor standard 120 VAC Tested by an independent lab to ASHRAE 52 1 the accepted standard in air cleaning Today s tightly built homes need help They require that the air inside be cleaned constantly to prevent the development of asthma and allergies The TFP Air Cleaner can remove 97 5 of airborne particles in 24 hours in a modern tight home Now you ca...

Отзывы: